<strong>CD</strong> 30 ÷ 5207.1. Heating and cooling capacity mod. 30 KwCooling capacityOutlet water temperaturePower inputOutlet water temperatureAmbient temp. °C 5℃ 7℃ 9℃ 12℃ 5℃ 7℃ 9℃ 12℃25 31.2 33.1 34.4 35.5 8.6 8.8 9 9.328 30.9 32.4 33.9 35.2 8.8 8.9 9.1 9.430 29.9 31.5 33 34.7 9.2 9.3 9.5 9.832 29.7 31.2 32.7 34.2 9.4 9.5 9.7 1035 28.5 30 31.8 33 9.7 10 10.3 10.538 27.6 29.1 30.6 31.8 10.3 10.5 10.8 10.840 27 28.2 29.7 31.2 10.6 10.8 <strong>11</strong>.1 <strong>11</strong>.1Cooling capacityKw3735333129275ºC7ºC9ºC12ºCThe diagram shows the capacityprogress among ambienttemperature and outlet watertemperature of 5°C, 7°C, 9°C,12°C2525ºC 28ºC 30ºC 32ºC 35ºC 38ºC 40ºCAmbient temperature12Power input in coolingKw<strong>11</strong>10985ºC7ºC9ºC12ºCThe diagram shows the powerinput progress among ambienttemperature and outlet watertemperature of 5°C, 7°C, 9°C,12°C725ºC 28ºC 30ºC 32ºC 35ºC 38ºC 40ºCAmbient temperature17