Applicable to:E2-MIX24880E2-MIX24882E2-32O24E2-16DO24system dynamics require. Each output may be individually configured as a TPO or ordinarydiscrete output.In this example, TPO #1 has a 10 second cycle time <strong>and</strong> the analog value is 3276 (10% of fullscale, which is typically 32767). The output will be ON for 1 second <strong>and</strong> OFF for 9 secondsduring each 10 second period.TPO #2 has a 2 second cycle time <strong>and</strong> the analog value is 26214 (80% of full scale). Theoutput will be ON for 1.6 seconds <strong>and</strong> OFF for 0.4 seconds during each 2 second period.TPO #3 has a 2 second specified cycle time, an analog value of 820 (2.5% of full scale) <strong>and</strong> aminimum ON/OFF time of 100 mS. Since the minimum cycle time is 100 mS <strong>and</strong> thecalculated ON time is only 50 mS, the cycle time is readjusted by a factor of 2 to maintain thetime proportion. The output will be ON for 100 mS <strong>and</strong> OFF for 3.9 seconds beforerepeating.Note: Non-integral remainders of time are carried forward to the next cycle, to maintain longtermaccuracy. (In Example TPO #3 on page 20, the below minimum time is carried forwardto the next time cycle. When the below minimum value is calculated, no ON time is set forthat cycle.4-20 mA AnalogInput WiringApplicable to:E2-MIX24880E2-MIX24882E2-32AI20ME2-16AI20ME2-16AI8AOOpen Loop Detectionon4-20 mAInputsThe analog input channels accept 4-20mA signals from a variety of devices <strong>and</strong> are protectedby self-resetting current shunts to prevent shunt overheat/damage. One screw terminal isprovided for each input signal. All analog inputs return to a common ground (terminal 8).Refer to illustration: Base Power & Communications Wiring Diagram in Section 4, on page12.This module can detect <strong>and</strong> report an open instrumentation loop on its analog inputs. Byallowing the module to report a negative value if the current falls below 4 mA, low limit logicin your DCS, PLC, RTU or computer can signal the loss of current.To enable this feature, go to the web interface’s “Analog Input Channels” configurationscreen <strong>and</strong> select the corresponding “Feature 1” column. A dropdown menu will appear.Select the“– Below 4 mA” setting for each desired channel. Click on the Help button for furtherinformation.EtherTRAK-2 I/O <strong>Module</strong> User Manual Page 27 of 37 Last Revised: 05-NOV-2010<strong>Sixnet</strong> Technology Park 331 Ushers Ballston Lake, NY 12019 USA +1-518-877-5173 support@sixnet.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!