<strong>Weishaupt</strong> dual fuel burnersSizes 30 to 70Version NR (NO X -<strong>reduction</strong> on gas <strong>operation</strong>)1/2003 CA


Description<strong>Weishaupt</strong> burners of sizes 30 to 70 were specially designed and developed forindustrial applications. The Monoblock-Burners are characterized with multipleexcellent features such as:• Big firing range and wide area of applications• Stable air fan performance – excellent combustion characteristics• Burner casing can be swung opened• Easy to install, setup and maintenance• Air damper closed off during burner stop• Oil pump and electric oil heater is standard for heavy oil burnersControlControl of air and fuel is performedaccording to the fuel type, burner sizeand requirement:• Two and three stageThe oil part of the dual fuel burnerhas a nozzle head with two or threenozzles. The capacity regulation isachieved by opening or closing the oilsolenoid valves 2 and 3 with correspondingchanges in air amount.• Sliding two stage<strong>On</strong> sliding two stage regulation, thelow fire and high fire points are assignedwithin the control range. Theburner slides depending on heat requirementbetween both operatingpoints. There is no sudden increase ordecrease of supplied fuel amount.• ModulatingModulating burners operate accordingto the heat requirement at any operatingpoint within the control range.Reduced starting capacityThe burner starts at ignition position viaseparated pilot line. This way only asmall amount of gas flows into the combustionchamber. After a certain delaytime the burner operates in low fire.Controlled shutdown from low fireControlled shutdown of the burner isperformed only at low fire. Sudden pressuresurge in the gas supply line can beavoided.Fuel – air ratioThe regulation of fuel to air ratio variesdepending on the burner model:Size 30Burner models RGL and RGMS:Pressure side air regulation via ratio controlledsliding sleeve in the mixing headBurner model GL: Pressure side air regulationvia adjustable flame tube accordingto the firing rate2Sizes 40 to 70Burner models GL, RGL and RGMS:Pressure side air regulation via ratiocontrolled sliding sleeve in the mixingheadHeavy oil burnersHeavy oil burners are equipped with oilpreheaters, which keep the oil atrequired temperature to guaranteeproper viscosity for good atomization.A temperature monitored sequenceprogram circulates the preheated oilto the nozzle head before start andtherefore keeps the nozzles at the sametemperature.<strong>Gas</strong> trainAs standard, <strong>Weishaupt</strong> gas and dualfuel burners are always equipped withtwo main gas valves.<strong>Gas</strong> train can be built according to mostapplicable North American codes andstandards.Digital combustion managerW-FM100 and W-FM200 combustionmanager control all essential burnerfunctions, e.g. fuel and air supply andmonitor the flame with digital precision.The target is optimization of operatingconditions, maximization of economicalaspect and minimizing the emissions.Thanks to the digital combustion technology,such optimization is availabletoday at reasonable cost. Expenses forinstallation and maintenance are evenclearly lower than with conventionaltechnologies. For example, a separateremote panel is no longer required forburner control. Furthermore, remote<strong>operation</strong>, remote diagnostic and remotemonitoring of the appliances are nowrealizable. This increases the safety andcomfort for operator.ApplicationsThe burners can be used with heatexchanger such as boilers, air heatersand for certain process applications.Due to the fact that the burner iscapable of overcoming high combustionchamber pressure, they are most compatiblewith modern high performanceboilers.FuelsOil sectionLight oil (#2 oil), viscosity 6mm 2 /s at68F (20°C)Medium to heavy oil (#4 to #6) with viscosityup to 50mm 2 /s at 212F (100°C)<strong>Gas</strong> sectionNatural gasPropane (LPG)Installation locationThe burners are designed for indoor<strong>operation</strong> with temperature of 5F(–15°C) up to 100F (+40°C) and relativehumidity of max. 80%CertificationThe burners are in compliance with mostapplicable European and NorthAmerican standardsExcellent service<strong>Weishaupt</strong> has a high density sales andservice network all over the world. Thecustomer service is available every dayaround the clock. Optimum in housetraining conditions ensure high quality ofservice personnel.


versionsDigital combustion manager(W-FM100)Electronic ratio controller (RVW)with O 2 -trimMechanical linkageDigital combustion manager(W-FM100)with modulating controllerElectronic ratio controller (RVW)with speed controlDigital combustion manager(W-FM100)with modulating controllerand speed controlDigital combustion manager(W-FM200)with modulating controllerO 2 -trim and speed controlCapacity regulationElectronic ratio controller (RVW)with O 2 -trim andspeed controlstandardoptionalTwo stage (ZM)Oil partHFSliding two stage(ZM)HFLFLFIPONOFFONOFFThree stage (TM)Oil partHFS2LFONOFFModulating(ZM)HF =High fireLF = Low fireIP = Ignition PositionS2 = Stage 2 (TM)HFLFIPONOFFBurner designationRGL 40/1 – B, Vers. ZM-NRSizeFuel: Light oilFuel: <strong>Gas</strong>Index for Mixing headCode for capacity rangeModulating burner (oil part)NO x -<strong>reduction</strong>ZM =<strong>Gas</strong>/Oil: sliding two stageor modulatingGL 40/1 – B, Vers. TM-NRNO x -<strong>reduction</strong>ZM =<strong>Gas</strong>: Sliding two stage ormodulatingOil: Two stageTM = <strong>Gas</strong>: Sliding two stage ormodulatingOil: Three stageIndex for mixing headCode for capacity rangeSizeFuel: Light oil (#2 oil)Fuel: <strong>Gas</strong>3


The advantages ofdigital combustion managementControl and Display UnitDigital combustion managementmeans optimum combustion figures,continuous repeatability of settingvalues and ease of use.<strong>Weishaupt</strong> burners are equipped withelectronic ratio controller and digitalcombustion management to satisfy therequirements of modern combustiontechnology, which demand a precise andcontinuously reproducible supply of fueland combustion air. <strong>On</strong>ly in this wayoptimal combustion figures can beensured over extended periods of time.If required, the burners can also beequipped with O 2 trim* and variablespeed control.Error free <strong>operation</strong> via AZL displayand control unitSetting and control of the burner functionsare achieved using a control anddisplay unit, the AZL, which is equippedwith an LCD display. The AZL is connectedto the combustion manager via asafety bus system and can be positionedanywhere according to the user’spreferences within 325 ft. (100 m) distancefrom the burner.Flexible communication possibilitiesThe integrated communication interfaceenables all necessary information andfunctions to be transmitted to a BMSsystem. If required, remote <strong>operation</strong> andremote diagnosis functions, which areaccessible via modem, can be installed(e.g. oil/gas change-over, adjustment ofsetting values).Communication with external systemsvia BUSIf data has to be exchanged betweenburners and other heating systems withPLC devices, the information can beaccessible via eBUS or MODBUScommunication system.Integration with building managementFor control and management functions,<strong>Weishaupt</strong> offers ProGraf NT - asoftware product that provides a realtime solution to meet all requirements.The price advantage of the newtechnologyWith improved technology and ease ofuse, combustion plant is becoming evenmore economical than ever before.• No additional burner controls arerequired, since this function is alreadygoverned by the combustion manager.Fuses and burner motor starter are theonly additional items required.• Less installation work means lesserrors: the burners are tested as acomplete unit at the factory.• If required, the W-FM 100 is availablewith an integrated modulating controllerand variable speed module. Noseparate equipment is required. Themodulating controller and variablespeed module are included as standardwith the W-FM 200.• Commissioning and service worktakes less time. The initial presettingof the burner is carried out at the factory.<strong>On</strong> site, only the site specificoperating points have to be adjusted.• To facilitate O 2 trim, only an O 2 probeand O 2 module have to be installedand connected with the W-FM 200via the internal safety BUS.* In conjunction with W-FM 200 combustionmanager4


O 2 probe*O 2 module*<strong>Gas</strong> butterflySliding sleeveSteppingmotorsOil regulatorAir damperFrequencyconverterImpulse senderCAN-BUSW-FM 200 combustionmanagerCAN-BUSControl andDisplay UnitAZLeBUS/MODBUSBMSvisualizationProGraf NTExample of O 2 trim and speed control with W-FM 2005


Proven quality in detailIncreased safety via shut offassembly with solenoidvalveThe electromagnetic actuated safetyshut off device isolates the oil supply andreturn on burner models RGL40 to 70and RGMS30 to 70 when the burnershuts down. Oil shut off directly at thenozzle ensures a drip free burner shutdown. (Burner type RGL30 uses asystem without nozzle shut off).Considerable noise<strong>reduction</strong> due to soundabsorbing air inletBy utilizing sound absorbing materials onthe fan suction side it has been possibleto reduce <strong>operation</strong>al noise considerably.Cut-away view of a nozzle shut of assemblyPressure side air regulationvia mixing head with ratiocontrolled sliding sleeveCut-away view of the fan housingThe forward and reverse movements ofthe regulating sleeve in the mixing headensure that the air supply gap is correctat every operating point throughout thecapacity range. This results in optimumvelocities over the whole range ofregulation. With this system, the mixingpressure is increased at low fire,improving the mixing effect of fuel and air.This results in a <strong>reduction</strong> in excess airand improved combustion efficiency dueto the constant air/fuel ratio.Turn down ratio up to 1:5Turn down ratio up to 1:3Burner sizes 40 to 70 with pressure side ratio controlled sliding sleeveBurner without pressure side sliding sleeveExample of turn down ratio for different burner models6


RGL70/2-A ZM NR dual fuel burnerBurner with integrated AZL Control and Display Unit7


RGMS30/2-A ZM NR dual fuel burner complete with burner mounted oil preheaterBurner with inbuilt Control and Display Unit8


Dual fuel burner selectionModels GL, RGL and RGMS30, NR version[“WC ] Burner model GL30/2-A, vers. ZM-NRGL30/2-A, vers. TM-NRCombustion headG30/2-NR 190x65MBH Nat. <strong>Gas</strong>/LPG 1,000 – 7,850GPH Light oil #2 12 – 56543210<strong>Gas</strong>/LPGLight oil<strong>Gas</strong>/LPGLight oilComb. head openComb. head closed-1[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000[GPH] #2 0 10 20 30 40 50[“WC] Burner model RGL30/2-A, vers. ZM-NR RGMS30/2-A, vers. ZM-NRCombustion head G30/2-NR 190x65 G30/2-NR 190x65MBH Nat. <strong>Gas</strong>/LPG 1,000 – 7,850 1,000 – 7,850GPH Light oil #2 12– 56 –Heavy oil #6 – 17 – 526543210Nat. <strong>Gas</strong>PropaneLight oilHeavy oil-1[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000[GPH] #2 0 10 20 30 40 50[GPH] #6 0 10 20 30 40 50Models GL, RGL and RGMS40, NR version[“WC ] Burner model GL40/1-B, vers. TM-NRCombustion headG30/2-NR 190x58MBH Nat. <strong>Gas</strong>/LPG 1,535 – 9,215GPH Light oil #2 13 – 6676543210-1[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000<strong>Gas</strong>/LPGLight oil[GPH] #2 0 10 20 30 40 50 60[“WC] Burner model RGL40/1-B, vers. ZM-NR RGMS40/1-B, vers. ZM-NRCombustion head G30/2-NR 190x58 G30/2-NR 190x58MBH Nat. <strong>Gas</strong>/LPG 1,535 – 9,215 1,535 – 9,215GPH Light oil #2 13– 66 –Heavy oil #6 – 19 – 6276543210-1[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000<strong>Gas</strong>/LPGLight oilHeavy oil[GPH] #2 0 10 20 30 40 50 60[GPH] #6 0 10 20 30 40 50 60[“WC ] Burner model GL40/2-A, vers. TM-NRCombustion headG40/2-NR 217x75MBH Nat. <strong>Gas</strong>/LPG 1,700 – 11,800GPH Light oil #2 16 – 8476543210<strong>Gas</strong>/LPGLight oil-1[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000[GPH] #2 0 10 20 30 40 50 60 70 80[“WC] Burner model RGL40/2-A, vers. ZM-NR RGMS40/2-A, vers. ZM-NRCombustion head G40/2-NR 217x75 G40/2-NR 217x75MBH Nat. <strong>Gas</strong>/LPG 1,700 – 11,800 1,700 – 11,800GPH Light oil #2 16 – 84 –Heavy oil #6 – 25 – 7976543210-1[MBH] 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000<strong>Gas</strong>/LPGLight oilHeavy oilGPH] #2 0 10 20 30 40 50 60 70 80[GPH] #6 0 10 20 30 40 50 60 70 809


Dual fuel burner selectionModels RGL and RGMS50, NR version[“WC] Burner model RGL50/1-B, vers. ZM-NR RGMS50/1-B, vers. ZM-NRCombustion head G40/2-NR 217x75 G40/2-NR 217x75MBH Nat. <strong>Gas</strong>/LPG 1,875 – 13,650 1,875 – 13,650GPH Light oil #2 16 – 97 –Heavy oil #6 – 28 – 91876543210<strong>Gas</strong>/LPGLight oilHeavy oil-1[MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000[GPH] #2 0 10 20 30 40 50 60 70 80 90[“WC ] Burner model RGL50/2-A, vers. ZM-NR RGMS50/2-A, vers. ZM-NRCombustion head G50/2-NR 290x185 G50/2-NR 290x185MBH Nat. <strong>Gas</strong> 2,050 – 18,450 2,730 – 18,450LPG 2,730 – 18,450 2,730 – 18,450GPH Light oil #2 27 – 131 –Heavy oil #6 – 36 – 123876543210<strong>Gas</strong>PropaneLight oilHeavy oil-1[MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000[GPH] #2 0 20 40 60 80 100 120[GPH] #6 0 10 20 30 40 50 60 70 80 90 [GPH] #6 0 20 40 60 80 100 120Models RGL and RGMS60, NR version[“WC ] Burner model RGL60/2-A, vers. ZM-NR RGMS60/2-A, vers. ZM-NRCombustion head G60/2-NR 345x230 G60/2-NR 345x230MBH Nat. <strong>Gas</strong>/LPG 2,730 – 20,800 2,730 – 20,800GPH Light oil #2 32 – 148 –Heavy oil #6 – 44 – 139876543210<strong>Gas</strong>/LPGLight oilHeavy oil-1[MBH] 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000[GPH] #2 0 20 40 60 80 100 120 140The ratings given are based on fuel with low calorific value,an air temperature of 68F (20°C) and an installation altitudeof 1,640 ft. (500 m).The stated oil throughputs are based on a calorific value of140,000 BTU/Gal for light oil and 150,000 BTU/Gal for heavyoilVoltages and frequencies:As standard, the burners are suitable for three phase alternatingcurrent with voltages available between 208 - 600V, 60Hz.Different voltages and frequency available on request.Standard burner motor:Isolation class F, IP 54 protection[GPH] #6 0 20 40 60 80 100 120 14010


Dual fuel burner selectionModels RGL and RGMS70, NR version[“WC] Burner model RGL70/1-B, vers. ZM-NR RGMS70/1-B, vers. ZM-NRCombustion head G60/2A-NR 345x230 G70/2A-NR 345x230MBH Nat. <strong>Gas</strong>/LPG 2,730 – 25,250 2,730 – 25,250GPH Light oil #2 29 – 179 –Heavy oil #6 – 48 – 168.59876543210-1[MBH] 0 4,000 8,000 12,000 16,000 20,000 24,000<strong>Gas</strong>/LPGLight oilHeavy oil[GPH] #2 0 20 40 60 80 100 120 140 160 180[“WC] Burner model RGL70/2-A, vers. ZM-NR RGMS70/2-A, vers. ZM-NRCombustion head G70/2A-NR 425x295 G70/2A-NR 425x290MBH Nat. <strong>Gas</strong> 3,400 – 35,850 3,400 – 35,850LPG 4,750 – 35,850 4,750 – 35,850GPH Light oil #2 46 – 255 –Heavy oil #6 – 52 – 2399876543210-1[MBH] 0 6,000 12,000 18,000 24,000 30,000 36,000<strong>Gas</strong>PropaneLight oilHeavy oil[GPH] #2 0 30 60 90 120 150 180 210 240 270[GPH] #6 0 20 40 60 80 100 120 140 160 [GPH] #6 0 30 60 90 120 150 180 210 240The ratings given are based on fuel with low calorific value,an air temperature of 68F (20°C) and an installation altitudeof 1,640 ft. (500 m).The stated oil throughputs are based on a calorific value of140,000 BTU/Gal for light oil and 150,000 BTU/Gal for heavyoilVoltages and frequencies:As standard, the burners are suitable for three phase alternatingcurrent with voltages available between 208 - 600V, 60Hz.Different voltages and frequency available on request.Standard burner motor:Isolation class F, IP 54 protection11


Scope of deliveryDescription GL30-ZM GL30-TM RGL30 RGMS30 GL40-TM RGL40 RGMS40 RGL60 RGMS60RGL50 RGMS50 RGL70 RGMS70Burner housing, hinged flange, housing cover,<strong>Weishaupt</strong> burner motor, air intake housing, fanwheel, combustion head, ignition unit, ignition cable,ignition electrodes, nozzle assembly with oil nozzle(s),combustion manager with control unit, flame sensor,flange gasket, limit switch on hinged flange,fixing bolts ● ● ● ● ● ● ● ● ●W-FM 100 combustion manager ● ● ● ● ● ● ● ● ●Double main gas valves ● ● ● ● ● ● ● ● ●<strong>Gas</strong> butterfly valve ● ● ● ● ● ● ● ● ●Pilot valves ● ● ● ● ● ● ● ● ●Connection piece ● ● ● ● ● ● ● ● ●Air pressure switch ● ● ● ● ● ● ● ● ●Oil pressure switch in return ● ● ● ● ● ● ●<strong>Gas</strong> pressure switch ● ● ● ● ● ● ● ● ●Adjustable regulating sleevein the mixing head ● ●Ratio controlled sliding sleevein the mixing head ● ● ● ● ● ● ●Servomotor for fuel/air ratioregulation via W-FM 100Servomotor for air damper ● ● ● ● ● ● ● ● ●Servomotor for gas butterfly ● ● ● ● ● ● ● ● ●Servomotor for oil regulator ● ● ● ● ● ●Servomotor for regulating sliding sleeve ● ● ● ● ● ● ●Oil pump ● ● ● ●➀ ● ● ●➀ ● ●➁Oil preheater ●➀ ●➀ ●➁Oil hoses ● ● ● ● ● ● ● ● ●2 oil solenoid valves, 1 safety valve,two stage nozzle assembly without shut off●2 oil solenoid valves, 1 safety valve, threestage nozzle assembly with solenoid shut off ● ● ●3 oil solenoid valves, 1 safety valve, three stagenozzle assembly without shut off ● ●2 solenoid valves in flow and return,nozzle assembly without shut off1 solenoid valve in flow and return,nozzle assembly with solenoid shut off ● ●Electromagnetic clutch ● ● ● ● ● ● ● ● ●●➀ Heavy oil burners, sizes 30 to 50, are equipped as standard with integral oil pump and electric oil preheater. If required, an additionalmedium oil preheater can be supplied as an option (refer to special equipment).➁ For heavy oil burners, sizes 60 and 70 remote pump and preheater stations are required.12


Special equipmentDescription Size 30 Size 40 Size 50 Size 60 Size 70Vertically firing burner version standard standard standard standard standardAir intake flange for connection of an air duct 280 003 47 280 001 68 280 000 92 280 000 38 280 000 13Combustion head extension by 6” (150 mm) GL../2-A, vers. ZM-NR 290 005 15 – – – –GL../1-B, vers. TM-NR – 290 005 27 – – –GL../2-A, vers. TM-NR 290 005 17 290 005 07 – – –RGL../1-B, vers. ZM-NR – 290 005 29 290 005 09 – 290 011 40RGL../2-A, vers. ZM-NR 290 005 19 290 005 09 290 004 99 290 004 19 290 004 85RGMS../1-B, vers. ZM-NR – 290 011 25 290 009 42 – 290 011 42RGMS../2-A, vers. ZM-NR * 290 011 27 290 011 30 290 011 32 290 011 34by 12” (300 mm) GL../2-A, vers. ZM-NR 290 005 16 – – – –GL../1-B, vers. TM-NR – 290 005 28 – – –GL../2-A, vers. TM-NR 290 005 18 290 005 08 – – –RGL../1-B, vers. ZM-NR – 290 005 30 290 005 10 – 290 011 41RGL../..-A, vers. ZM-NR 290 005 20 290 005 10 290 005 00 290 004 20 290 004 86RGMS../1-B, vers. ZM-NR – 290 011 26 290 011 29 – 290 011 43RGMS../2-A, vers. ZM-NR * 290 011 28 290 011 31 290 011 33 290 010 96W-FM 100 with internal modulating controller 290 010 60 290 010 60 290 010 60 290 010 60 290 010 60Burner controllerMechanical linkage with LFL in lieu of W-FM 100 -price <strong>reduction</strong>- 290 011 02 290 011 02 290 011 02 290 011 02 290 011 02Mechanical linkage with LGK in lieu of W-FM 100 -price <strong>reduction</strong>- 290 011 03 290 011 03 290 011 03 290 011 03 290 011 03Solenoid valve for air pressure switch testfor continuous run fan or post purge 290 004 29 290 004 29 290 000 31 290 000 31 290 000 31Oil preheaterWEV2.2 in lieu of EV2D on RGMS 30 and 40 RGMS../1-B, vers. ZM-NR – 290 001 68 290 002 26 – –WEV3/01 in lieu of WEV2.2/01 on RGMS50 RGMS../2-A, vers. ZM-NR 290 001 68 290 001 68 290 002 26 – –MV9C oil preheater (medium) in addition to standard integral electric oil preheaterRGMS../1-B, vers. ZM-NR – 280 003 34 280 002 98 – –RGMS../2-A, vers. ZM-NR 280 003 60 280 003 34 280 001 17 – –Fittings type for medium preheater station in conjunction with electric preheaterscrewed for warm water up to 230F (110°C) 120 001 70 120 001 70 120 001 70 – –flanged for warm water up to 230F (110°C) 120 001 78 120 001 78 120 001 78 – –flanged for hot water from 230F (110°C) 120 001 79 120 001 79 120 001 79 – –up to 355F (180°C)screwed for low pressure steam from 7.2 PSI (0.5 bar) 280 001 18 280 001 18 280 001 18 – –up to 21.7 PSI (1.5 bar)screwed for high pressure steam from 21.7 PSI (1.5 bar) 280 001 19 280 001 19 280 001 19 – –up to 217.5 PSI (15 bar)flanged for high pressure steam from 174 PSI (12 bar) 280 001 21 280 001 21 280 001 21 – –up to 290 PSI (20 bar)flanged for high pressure steam from 290 PSI (20 bar) 280 001 22 280 001 22 280 001 22 – –up to 362.5 PSI (25 bar)flanged for thermal fluid up to 480 F (250°C) 120 001 75 120 001 75 120 001 75 – –flanged for thermal fluid up to 570 F (300°C) 120 001 77 120 001 77 120 001 77 – –* on request13


Technical dataSizes 30 and 40Description GL30/2-A RGL30/2-A RGMS30/2-ABurner motor Model D112/110-2 D112/110-2 D112/110-2Motor rating HP (kW) 6.7 (5.0) 6.7 (5.0) 6.7 (5.0)Full Load Amps (FLA) at 460 V A 8.2 8.2 8.2Speed (60 Hz) rpm 3510 3510 3510Fan wheel colour / ø red / 248 x 100 red / 248 x 100 red / 248 x 100Combustion manager Model W-FM100 W-FM100 W-FM100Ignition unit Model W-ZG02/2 W-ZG02/2 W-ZG02/2Servomotor Model SQM 45 SQM 45 SQM 45Integral pump Model J6 TA3 TA3Oil preheater Model – – EV2DOil throughput GPH (kg/h) – – 72 (270)Heating capacity kW – – 13.2Oil solenoid valve 110V 1/4” 20 W Model 121 K 6220110V 1/8” 19 W Model 121 K 2423 – –55V 1/4” (supply) 20 W Model – 121 K 6220 –55V 1/8” (return) 20 W Model – 121 K 2423 –55V 3/8” (supply) 20 W Model – – 321 H 232255V 3/8” (return) 20 W Model – – 121 G 2320Oil pressure switch 1 - 10 bar (light oil return - 5 bar) Model – DSA 46 F0011 - 10 bar (heavy oil return - 7 bar) Model – – DSA 46 F001Oil hoses DN / Length 13/40” (1000mm) 20/40” (1000mm) –(High pressure metal hoses for RGMS) DN / Length – – 20/51” (1300mm)Burner weight lbs (kg) 297 (135) 319 (145) 385 (175)Description GL40/1-B RGL40/1-B RGMS40/1-BGL40/2-A* RGL40/2-A* RGMS40/2-A*Burner motor Model D112/140-2 D112/140-2 D112/140-2Motor rating HP (kW) 10.5 (7.8) 10.5 (7.8) 10.5 (7.8)Full Load Amps (FLA) at 460 V A 11.5 11.5 11.5Speed (60 Hz) rpm 3450 3450 3450Fan wheel colour / ø red / 275 x 100 red / 275 x 100 red / 275 x 100Combustion manager Model W-FM100 W-FM100 W-FM100Ignition unit Model W-ZG02/2 W-ZG02/2 W-ZG02/2Servomotor Model SQM 45 SQM 45 SQM 45Integral pump Model J6➀ TA3 TA3Oil preheater Model – – EV2D➁Oil throughput GPH (kg/h) – – 72 (270)Heating capacity kW – – 13.2Oil solenoid valve 110V 1/8” 19 W Model 121 K 2423 – –110V 1/4” (safety valve) 20 W Model 121 K 6220 – –55V 3/8” (supply) 20 W Model – 321 H 2322 321 H 232255V 3/8” (return) 20 W Model – 121 G 2320 121 G 2320Oil pressure switch 1 - 10 bar (light oil return - 5 bar) Model – DSA 46 F001 –1 - 10 bar (heavy oil return - 7 bar) Model – – DSA 46 F001Oil hoses DN / Length 13/40” (1000mm) 20/40” (1000mm) –(High pressure metal hoses for RGMS) DN / Length – – 20/51” (1300mm)Burner weight lbs (kg) 352 (160) 352 (160) 418 (190)➀ Light oil burners > 60 GPH (200 kg/h): oil pump J7 in lieu of J6 (refer to Special Equipment for additional cost)Light oil burners > 72 GPH (250 kg/h): oil pump TA2 in lieu of J6 (refer to Special Equipment for additional cost)➁ Heavy oil burners > 74 GPH (270 kg/h): oil preheater WEV2.2 in lieu of EV2D (refer to Special Equipment for additional cost)* Burner types …/2-A with burner motor type 112/140-2; nominal capacity 7 kW; nominal load 13.4 A; motor prefuse 25 A14


Technical dataSize 50Description RGL50/1-B RGL50/2-ABurner motor Model D132/170-2a D132/170-2Motor rating HP (kW) 14 (10.5) 20 (15)Full Load Amps (FLA) at 460 V A 17.2 23.2Speed (60 Hz) rpm 3500 3500Fan wheel colour / ø red / 330 x 100 red / 330 x 100Combustion manager Model W-FM100 W-FM100Ignition unit Model W-ZG02/2 W-ZG02/2Servomotor Model SQM 45 SQM 45Integral pump Model TA4C T2COil solenoid valve 55V 3/8” (supply) 20W Model 321 H 2322 321 H 232255V 3/8” (return) 20W Model 121 G 2320 121 G 2320Oil pressure switch 1 - 10 bar (light oil return - 5 bar) Model DSA 46 F001 DSA 46 F0011 - 10 bar (heavy oil return - 7 bar) Model – –Oil hoses DN / Length 25/51” (1300mm) 25/51” (1300mm)Burner weight lbs (kg) 517 (235) 528 (240)Description RGMS50/1-B RGMS50/2-ABurner motor Model D132/170-2 D132/170-2Motor rating HP (kW) 14 (10.5) 20 (15)Full Load Amps (FLA)at 460 V A 17.2 23.2Speed (60 Hz) rpm 3500 3500Fan wheel colour / ø red / 330 x 100 red / 330 x 100Combustion manager Model W-FM100 W-FM100Ignition unit Model W-ZG02/2 W-ZG02/2Servomotor Model SQM 45 SQM 45Oil preheater Model WEV2.2/01➂ WEV3/01Oil throughput GPH (kg/h) 80 (300) 133 (500)Heating capacity kW 13.8 22.4Integral pump Model TA4C T2COil solenoid valve 55V 3/8” (supply) 20W Model 321 H 2322 321 H 232255V 3/8” (return) 20W Model 121 G 2320 121 G 2320Oil pressure switch 1 - 10 bar (heavy oil return - 7 bar) Model DSA 46 F001 DSA 46 F001Oil hoses DN / Length 25/59” (1500mm) 25/59” (1500mm)Burner weight lbs (kg) 605 (275) 616 (280)➂Heavy oil burners > 80 GPH (300 kg/h): oil preheater WEV3 in lieu of WEV2.2 (refer to Special Equipment for extra cost)15


Technical dataSizes 60 and 70Description RGL60/2-A RGMS60/2-ABurner motor Model D132/170-2 D132/170-2Motor rating HP (kW) 20 (15) 20 (15)Full Load Amps (FLA) at 460 V A 23.2 23.2Speed (60 Hz) rpm 3500 3500Fan wheel colour / ø red / 465 x 103 red / 465 x 103Combustion manager Model W-FM100 W-FM100Ignition unit Model W-ZG02/2 W-ZG02/2Servomotor Model SQM 45 SQM 45Integral pump Model T2C –Oil solenoid valve 55V 3/8” (supply) 20W Model 321 H 2322 321 H 232255V 3/8” (return) 20W Model 121 G 2320 121 G 2320110V 3/8” (Bypass) 19W Model – 322 H 7306Oil pressure switch 2 – 40 bar (supply 18 bar) Model – DSA 58 F0011 - 10 bar (light oil return - 5 bar) Model DSA 46 F001 –1 - 10 bar (heavy oil return - 7 bar) Model – DSA 46 F001Oil hoses DN / Length 25/51” (1300mm) –(High pressure metal hoses for RGMS) DN / Length – 16/59” (1500)Burner weight lbs (kg) 726 (330) 671 (305)➀➀ Weight excluding pump station and preheater stationDescription RGL70/1-B RGL70/2-A RGMS70/1-B RGMS70/2-ABurner motor Model D160/215-2B D160/215-2 D160/215-2B D160/215-2Motor rating HP (kW) 25 (19) 29.5 (22) 25 (19) 29,5 (22)Full Load Amps (FLA) at 460 V A 32.2 36 32.2 36Speed (60 Hz) rpm 3400 3500 3400 3500Fan wheel colour / ø green / 530 x 120 green / 530 x 120 green / 530 x 120 green / 530 x 120Combustion manager Model W-FM100 W-FM100 W-FM100 W-FM100Ignition unit Model W-ZG02/2 W-ZG02/2 W-ZG02/2 W-ZG02/2Servomotor Model SQM 45 SQM 45 SQM 45 SQM 45Integral pump Model T2C (< 175 GPH) T2C (< 175 GPH) – –(< 600 kg/h) (< 600 kg/h)Model T3C (> 175 GPH) T3C (> 175 GPH) – –(> 600 kg/h) (> 600 kg/h)Oil solenoid valve 55V 1/2” (supply) 20W Model 321 H 2522 321 H 2522 321 H 2522 321 H 252255V 1/2” (return) 20W Model 121 G 2520 121 G 2520 121 G 2520 121 G 2520110V 3/8” (Bypass) 19W Model – – 322 H 7306 322 H 7306Oil pressure switch2 – 40 bar (supply - 18 bar) Model – – DSA 58 F001 DSA 58 F0011 - 10 bar (light oil return - 5 bar) Model DSA 46 F001 DSA 46 F001 – –1 - 10 bar (heavy oil return - 7 bar) Model – – DSA 46 F001 DSA 46 F001Oil hoses DN / Length 25/51” (1300mm) 25/51” (1300mm) – –(High pressure metal hoses for RGMS) DN / Length – – 20/59” (1500mm) 20/59” (1500mm)Burner weight lbs (kg) 957 (435) 957 (435) 902 (410)➀ 902 (410)➀➀ Weight excluding pump station and preheater station16


Burner fuel systemsModel GL30Z (oil part)10 1313a 16aModels GL30T / GL40T (oil part)10 1313a 16aModels RGL30 (oil part)10 1212 16a55V55V55VPM55V13a13a 13a12a 1415 12aModels RGL40 to RGL70 (oil part)10 17 11 18 14 12 16ϑ55VP55Vϑ PM12b 12a 18 14a 15Models RGMS30 to RGMS50 (oil part)Integral pump and preheater10 11 12 17 18 1655V55VP12a 14ϑM15Models 30 to 70 (gas part)2P6Models RGMS60 and RGMS70 (oil part)With separate pump and preheater stations10 17 11 18 14 12 16ϑ73 455VP4b55Vϑ PM12b 12a 18 14a 1514bP598Legend1 Isolating cock2 Main gas pressure regulator3 Low gas pressure switch4 Double main gas valve4b Pilot gas valve5 High gas pressure switch6 Isolating valve (pilot)7 Pilot gas pressure regulator8 <strong>Gas</strong> butterfly valve9 Burner10 Oil pump11 Oil filter12 Normally closed oil solenoid valve (55 V,electrically connected in series with 12a)12a Normally closed oil solenoid valve (55 V,electrically connected in series with 12,installed against the direction of flow)12b Normally open bypass oil solenoid valve13 Normally closed oil solenoid valve13a Normally closed oil solenoid valve forstages 1, 2 and 314 Oil pressure switch in supply line14a Oil pressure switch in return line15 Oil regulator16 Nozzle assembly with shut off device(solenoid valve)16a Nozzle assembly without shut off device17 Oil preheater18 Pt100 temperature sensor (to monitorminimum oil temperature17


Pump and preheater stationsDescriptionScope of delivery - pump stationsPump unit (screw spindle pump withmotor), pressure gauge, vacuum gauge,pressure regulating valve, ball valves,suction flange, pressure flange includingcounter flanges, screws and washers,suction-side filter. All parts fullyassembled on an oil drip tray.The pump station is available in twodifferent versions - either as a singlestation unit with one pump, or as a twinstation unit with two pumps, one pumpbeing a backup unit. Should one of thepump fail, it is possible to quickly switchover to the other one.<strong>On</strong>ly proven makes of pump are used.The pumps are carefully matched to thecapacity of the burner.Scope of delivery - preheater stationsPreheater stations are supplied fullyassembled on an oil drip tray. Thepreheater ensures a constant oiltemperature and as result, theappropriate viscosity of the fuel oil.There are two basic versions of thepreheater station available:1. Electric preheating (model WEV...)2. Medium preheating (model MV...)MV.. medium oil preheaterMedium preheaters are high capacity,forced circulation heat exchangers. Highcapacity is achieved with a compact,space saving construction. Hot water,steam or thermo fluid can be used asheating medium. The oil preheatersguarantee substantially stable oiltemperatures and thus good combustionfigures. The oil temperature achieveddepends on the heating medium used.When selecting and sizing, please referto the oil temperature diagrams inchapter 5.3 of the technical brochure“<strong>Weishaupt</strong> electric and medium oilpreheaters”, print No. 18. <strong>Weishaupt</strong>medium oil preheaters can be useduniversally. It is possible to change themedium at any time. The mediumpreheater can be used either as standalone unit or in conjunction with anelectric oil preheater.If operating steam at more than 110 PSI(7.5 bar) or hot water between 355F(180°C) and 390F (200°C) iscontinuously available, then an electricpreheater is not required. This is alsopossible if plant with the above minimumpressures or temperatures to beoperated with light oil or gas.If the medium temperature is notsufficient to adequately preheat the fueloil, then the electric oil preheater inputsthe additional heat required. The electricoil preheater heats the oil for the start upof the plant. If the required mediumtemperature is available then the stationswitches over to the medium oilpreheater thus saving on electricity.Suitable connection types for medium oilpreheaters can be selected, dependingon the medium available. If medium oilpreheaters are provided without electricoil preheaters, a mechanical temperatureregulator must be used with the mediumconnection fittings.Air / gas separators or oil circulationtanksPatented air / gas separators orcirculation tanks are always required andmust be quoted with the burner.By using an air / gas separator orcirculation tank, it is possible for thepreheated oil from the burner return to bemixed with oil from the burner supply line.This results in an energy saving, as it isonly necessary to partially heat the fueloil.Where one burner is operating on lightoil, it is then possible to use a two pipesystem so long as the suction vacuumdoes not exceed 6 PSI (0.5 bar). Ifseveral burners with air / gas separatorsor oil circulation tanks are being suppliedby a ring main system, then it is a goodidea to provide a manually actuateddouble shut off device with limit switchimmediately after the air / gas separatoror circulation tank. The air / gasseparator or circulation tank must beselected according to the ring mainpump rating and the burner size. Whenchoosing ring main pump units, pleaseensure that the capacity is around 1.5 - 2times of the nozzle rating.General instructionsWhen starting a boiler from a coldcondition with residual oil, the capacity ofelectric oil preheater must be at least30% of the boiler rating. <strong>On</strong> hot waterboilers up to 265F (130°C) operatingtemperature, the electric oil preheatersmust be able to produce the full boileroutput without utilizing mediumpreheaters. Use of a medium preheater isnot suitable for medium temperaturesbelow 212F (100°C). The number ofmedia oil preheaters to be selecteddepends on the oil throughput and canbe taken from the capacity charts (seethe technical brochure “<strong>Weishaupt</strong>electric and media oil preheaters”).Planning and installation instructionsAir /<strong>Gas</strong> separator, circulation tank,pump station and oil preheater stationmust be installed close to the burner aspossible.<strong>On</strong> RGMS type burners, sizes 60 and70, the time required for oil circulationduring start sequence depends on thelength of the pipework between theburner and the air gas separator orcirculation tank.The shorter the pipeline, the shorter theperiod between call for heat and oilrelease / burner start after a controlledshutdown.18


Pump and preheater stationsTypesPump stations - 60 Hz frequencyBurner Technical data - pump Version with 1 pump Version with 2 pumpscapacity Supply at Speed Motor at Pump type Order No. Pump type Order No.in GPH 150 mm 2 /s rpm 450 mm 2 /sGPH (l/h)HP (kW)74 – 115 270 (1020) 3400 3 (2.2) SPF 10-38 170 003 09 SPZ 10-38 170 003 11115 – 215 540 (2050) 3400 3.5 (2.6) SPF 20-38 170 003 10 SPZ 20-38 170 003 12215 – 265 720 (2720) 3400 5.3 (4.0) SPF 20-46 170 003 13 SPZ 20-46 170 003 14Preheater stationsType Number Medium preheater Electric preheater Order No.lbs/h (kg/h)at ∆t = 135F (75°C)WEV3.1/01 1 – 100 GPH (375 kg/h) 170 003 55WEV3.1/01 2 – 200 GPH (750 kg/h) 170 003 52WEV3/01 1 – 133 GPH (500 kg/h) 170 002 23WEV3/01 2 – 266 GPH (1000 kg/h) 170 002 24MV9C with temperature contr. 1 1100 (500) – 170 001 03MV9C without temperature contr. 1 1100 (500) – 170 001 04MV10A with temperature contr. 1 2200 (1000) – 170 000 94MV10A without temperature contr. 1 2200 (1000) – 170 002 30Connection fittings for preheater stations with 1 oil preheaterDescriptionOrder No.Fittings for MV9C medium preheater station(with electric preheater stations)– screwed for warm water up to 230F (110°C) 120 001 70– screwed for high pressure steam up to 21.75PSI (1.5 bar) 170 003 59– screwed for high pressure steam from 21.75PSI (1.5 bar) up to 217.5PSI (15 bar) 170 003 60– flanged for warm water up to 230F (110°C) 120 001 78– flanged for hot water from 230F (110°C) up to 355F (180°C) 120 001 79– flanged for high pressure steam up to 21.75PSI (1.5 bar) 170 003 61– flanged for high pressure steam from 87PSI (6 bar) up to 290PSI (20 bar) 170 003 62– flanged for high pressure steam from 290PSI (20 bar) up to 363PSI (25 bar) 170 003 67– flanged for thermal fluid up to 480F (250°C) 120 001 75– flanged for thermal fluid up to 570F (300°C) 120 001 77Fittings for MV9C medium preheater station (with thermostat valve. without electric preheater)– flanged for hot water from 355F (180°C) up to 390F (200°C) 120 001 81– flanged for high pressure steam from 109PSI (7.5 bar) up to 188.5PSI (13 bar) 170 003 63– flanged for high pressure steam from 188.5PSI (13 bar) up to 290PSI (20 bar) 170 003 64– flanged for high pressure steam from 290PSI (20 bar) up to 363PSI (25 bar) 170 003 65– flanged for thermal fluid from 390F (200°C) up to 480F (250°C) 120 001 84– flanged for thermal fluid from 480F (250°C) up to 570F (300°C) 120 001 85Fittings for MV10A medium preheater station (with electric preheater stations)– screwed for warm water up to 230F (110°C) 170 001 35– screwed for high pressure steam up to 21.75PSI (1.5 bar) 170 001 47– screwed for high pressure steam from 21.75PSI (1.5 bar) up to 217.5PSI (15 bar) 170 001 53– flanged for warm water up to 230F (110°C) 170 001 38– flanged for hot water from 230F (110°C) up to 355F (180°C) 170 001 44– flanged for high pressure steam up to 21.75PSI (1.5 bar) 170 001 50– flanged for high pressure steam from 87PSI (6 bar) up to 290PSI (20 bar) 170 001 56– flanged for high pressure steam from 290PSI (20 bar) up to 363PSI (25 bar) 170 002 00– flanged for thermal fluid up to 480F (250°C) 170 001 59– flanged for thermal fluid up to 570F (300°C) 170 001 62Fittings for MV10A medium preheater station (with thermostat valve, without electric preheater)– flanged for hot water from 355F (180°C) up to 390F (200°C) 170 001 68– flanged for high pressure steam from 109PSI (7.5 bar) up to 188.5PSI (13 bar) 170 001 71– flanged for high pressure steam from 188.5PSI (13 bar) up to 290PSI (20 bar) 170 001 74– flanged for high pressure steam from 290PSI (20 bar) up to 363PSI (25 bar) 170 001 85– flanged for thermal fluid from 390F (200°C) up to 480F (250°C) 170 001 77– flanged for thermal fluid from 480F (250°C) up to 570F (300°C) 170 001 8019


Pump and preheater stationsConnection fittingsPump station (with 2 pumps) Medium preheater station Electric preheater stationPossible connections of mediumpreheaterHW outletHW inletHot waterMediumpreheaterElectricpreheaterHW outletThermo fluid outletBrenner-AnschlußHW inletThermo fluid inletHot water and thermo fluidSteam inletCondensate outletLow pressure steam up to 22PSI (1.5 bar)Mechanicallyconnectedshut offassemblywith limitswitch andsafety valveAir/gas separatorMechanically connected shut offassembly with limit switch andsafety valveDescriptionThe connection fittings are to bechosen depending on the availablemedium and the number of preheaters.Condensate outletIncluded with pump stationIncluded with preheaterPreheater (not includedin delivery)Condensate sight glassSteam trapHPS inletHigh pressure steam up to 217.5PSI (15 bar)AccessoriesLines shown in black to beprovided on siteBall valveRegulatorFilterPressure gaugeDiagram - separate pump and preheater stations20


DimensionsSizes 30 and 40Size Dimensions in inches (mm)l1 l2 l3 l5 l6 l7 l8 l9 l10 l11 l12 l13 b1 b2 b3 b430/2-A 42.6 9.6 10.7 0.3 13.9 11.8 2.3 9.4 4.8 1.3 12.1 7.7 35.2 14.6 8.2 27.6(1083) (245) (272) (8) (354) (300) (58) (238) (123) (32) (308) (195) (895) (371) (208) (700)40/1-B 44.4 10.6 10.7 0.3 16.3 12.6 2.3 9.4 4.8 1.3 12.9 7.7 37.4 15.8 9.5 29.7(1128) (270) (272) (8) (414) (320) (58) (238) (123) (32) (328) (195) (950) (401) (242) (755)40/2-A 45.2 10.6 13.1 0.3 16.3 13.4 2.6 10.2 5.2 1.7 13.7 7.7 37.4 15.8 9.5 29.7(1148) (270) (332) (8) (414) (340) (67) (258) (133) (42) (348) (195) (950) (401) (242) (755)b5 b6 h1 h2 h3 h4 h5 h6 d1 d2 d4 d5 d6 d7 d8➀ r1➂ r230/2-A 16.5 13.0 22.5 8.1 16.0 8.1 8.3 13.0 11.0 9.8 8.6 14.2 11.2 38.2 35.0(418) (330) (572) (207) (407) (207) (210) (330) (280) (250) (218) M12 (360) (285) DN50 (970) (890)40/1-B 18.2 13.0 23.9 8.3 16.6 8.1 8.3 13.0 11.0 9.8 8.6 14.2 11.2 41.3 38.2(462) (330) (607) (211) (422) (207) (210) (330) (280) (250) (218) M12 (360) (285) DN50 (1050) (970)40/2-A 18.2 14.6 23.9 8.3 16.6 8.9 8.3 14.6 12.6 11.4 8.6 15.7 12.8 41.3 38.2(462) (370) (607) (211) (422) (227) (210) (370) (320) (290) (218) M12 (400) (325) DN65 (1050) (970)➀ <strong>Gas</strong> butterfly valve with flange connection➁ Pilot line connection either side➂ With electromagnetic clutchAll measurements are approximate. <strong>Weishaupt</strong> reserves the right to make alterations in light of future developments.21


DimensionsSize 50Size Dimensions in inches (mm)l1 l2 l3 l5 l6 l7 l8 l9 l10 l11 l12 l13 b1 b2 b3 b4 b550/1-B 47.0 12.4 13.1 0.3 16.6 14.3 2.6 10.2 5.2 1.7 14.5 10.0 41.7 17.3 10.9 32.3 21.7(1195) (315) (332) (8) (422) (363) (67) (258) (133) (42) (368) (254) (1060) (440) (277) (820) (550)50/2-A 49.0 12.4 13.1 0.3 16.6 16.3 2.8 12.1 6.2 2.6 15.3 12.4 43.3 18.3 10.9 33.9 21.7(1245) (315) (332) (8) (422) (413) (72) (308) (158) (65) (388) (314) (1100) (465) (277) (860) (550)b6 h1 h2 h3 h4 h5 h6 d1 d2 d4 d5 d6 d7 d8➀ r1➂ r250/1-B 14.6 28.7 10.4 20.2 8.9 7.2 14.6 12.6 11.4 10.2 15.7 12.8 46.5 39.4(370) (730) (263) (513) (227) (183) (370) (320) (290) (258) M12 (400) (325) DN65 (1180) (1000)50/2-A 16.9 28.7 10.4 20.2 10.1 7.8 16.9 15.0 13.8 10.2 18.9 15.4 46.5 40.4(430) (730) (263) (513) (257) (197) (430) (380) (350) (258) M16 (480) (390) DN80 (1180) (1025)➀ <strong>Gas</strong> butterfly valve with flange connection➁ Pilot line connection either side➂ With electromagnetic clutchAll measurements are approximate. <strong>Weishaupt</strong> reserves the right to make alterations in light of future developments.22


DimensionsSizes 60 and 70d 5d 7d 6SizeDimensions in inches (mm)l1 l2 l3 l5 l6 l7 l8 l9 l10 l11 b1 b2 b3 b4 b5 b660/2-A 58.2 15.9 14.1 0.3 20.0 17.5 3.5 13.7 7.0 3.3 47.8 19.2 11.0 38.6 26.4 20.5(1478) (405) (357) (8) (508) (440) (89) (348) (178) (85) (1215) (487) (280) (980) (670) (520)70/1-B 64.9 19.0 14.1 0.3 24.2 20.1 3.5 13.7 7.0 3.4 55.5 23.7 13.4 44.3 29.9 20.5(1648) (483) (357) (8) (614) (510) (89) (348) (178) (87) (1410) (602) (340) (1125) (760) (520)70/2-A 65.7 19.0 14.3 0.3 24.2 20.9 4.0 14.5 7.4 3.4 55.5 23.7 13.4 46.1 29.9 23.6(1668) (483) (362) (8) (614) (530) (102) (368) (188) (87) (1410) (602) (340) (1170) (760) (600)h1 h2 h3 h4 h5 d1 d2 d4 d5 d6 d7 d8➀ r1➁ r260/2-A 36.6 14.2 26.4 11.9 20.5 17.0 15.7 10.2 18.5 17.1 53.1 44.9(930) (360) (670) (302) (520) (432) (400) (258) M16 (470) (435) DN100 (1350) (1140)70/1-B 42.3 16.5 30.5 11.9 20.5 17.0 15.7 12.2 18.5 17.1 59.1 51.6(1075) (420) (775) (302) (520) (432) (400) (310) M16 (470) (435) DN100 (1500) (1310)70/2-A 42.3 16.5 30.5 12.4 23.6 18.5 18.9 12.2 21.7 19.7 59.1 51.6(1075) (420) (775) (315) (600) (470) (480) (310) M16 (550) (500) DN100 (1500) (1310)➀ <strong>Gas</strong> butterfly valve with flange connection➁ Pilot line connection either side➂ With electromagnetic clutchAll measurements are approximate. <strong>Weishaupt</strong> reserves the right to make alterations in light of future developments.23


Product and customer servicethe complete <strong>Weishaupt</strong> range<strong>Weishaupt</strong> Corporation6280 Danville RoadMississauga, ON L5T 2H7Ph.: (905) 564 0946, Fax.: (905) 564 0949www.weishaupt-corp.comPrint No. 83201316, August 2003Printed in Germany. All rights reserved.Regular maintenance reduces heatingcosts and environmental pollution. <strong>On</strong>ly aproperly adjusted burner can save energyand be environmentally friendly. Behindeach <strong>Weishaupt</strong> burner stands the whole<strong>Weishaupt</strong> customer service organization.The outstanding efforts made inmaintenance and service justify theenormous trust placed in <strong>Weishaupt</strong>’sburners, for at <strong>Weishaupt</strong> product andcustomer service belong together.<strong>Weishaupt</strong> customer service is there foryou all year round. Whenever you needhelp, be it the supply of spare parts,technical advice or a site visit. We arethere when you need us.