<strong>Scanner</strong> ® <strong>2000</strong> microEFM Appendix A<br />
Pulse Input<br />
The pulse input provides an optically isolated input for high-amplitude pulse (frequency) signals, which<br />
includes signals from a turbine meter equipped with a preamplifier (Figure A.16, top diagram) or signals from<br />
a positive displacement meter (Figure A.16, bottom diagram).<br />
The <strong>Scanner</strong> <strong>2000</strong> can calculate flow from no more than two pulse (frequency) inputs at a time. Therefore, a<br />
pulse input can be used simultaneously with only one turbine input (main board or expansion board).<br />
The pulse input can also be used as a status input for monitoring a parameter via Modbus registers. See Pulse<br />
Input for Status Indication, page C-25, for details.<br />
PULSE INPUT (TB8)<br />
TB4<br />
Expansion<br />
Board PN:<br />
9A-30160014<br />
TB8 TB7<br />
25 26<br />
TB9<br />
TB6<br />
TB5<br />
PULSE INPUT/SWITCH (TB7 &TB8)<br />
TB4<br />
Expansion<br />
Board PN:<br />
9A-30160014<br />
Figure A.16—Pulse input wiring<br />
TB8 TB7<br />
23<br />
25<br />
24<br />
26<br />
TB9<br />
TB6<br />
TB5<br />
PULSE INPUT<br />
3 TO 30 VDC<br />
SWITCH CLOSURE<br />
TB7 AND TB8 ARE CONNECTED BY JUMPER;<br />
TB7 IS THEN WIRED TO THE SWITCH.<br />
A-11