Section 4 Scanner ® 2000 microEFM Entering the Slave Address The slave address is a setting used in Modbus ® communications. It is a number that ranges from 1 to 65535, excluding 252 to 255 and 64764, which are reserved. If the Modbus ® request message contains the matching address, the device will respond to the request. In network arrangements, the device must have a unique slave address. For more information about Modbus ® communications, refer to Section 1—Introduction. If Modbus ® communications are not used, leave the slave address at the factory setting (1). To Enter a Port 1 Slave Address: Enter the Access menu. Press UP ARROW and ENTER simultaneously. Locate the Slave Address setting. PORT 1 SLAVE ADDRESS will appear in the lower display, and the rightmost digit in the top display will begin blinking. Enter the Slave Address. (range: 1 to 65535; excluding 252 to 255 and 64764) To Enter a Port 2 Slave Address: 70 Press UP ARROW until the correct digit is displayed. Then press LEFT ARROW to select the next digit to the left. Repeat using UP and LEFT arrows to enter all remaining digits. Press ENTER. Enter the Access menu. Press UP ARROW and ENTER simultaneously. Locate the Slave Address setting. Press ENTER twice until PORT 2 SLAVE ADDRESS appears in the lower display. The rightmost digit in the top display will begin blinking. Enter the Slave Address. (range: 1 to 65535; excluding 252 to 255 and 64764) Press UP ARROW until the correct digit is displayed. Then press LEFT ARROW to select the next digit to the left. Repeat using UP and LEFT arrows to enter all remaining digits. Press ENTER. + 00000000 00000000 + ... ... 00000000 00000000 The Baud Rate menu prompt will appear immediately following the entry of the slave address. See Entering the Baud Rate below for the baud rate entry procedure. ... ...
Scanner ® 2000 microEFM Section 4 Entering the Baud Rate The baud rate is the number of bits per second that are on the serial port. This setting must match the setting of the master device polling the Scanner 2000 or the serial port. This only applies to the Modbus ® communications; if Modbus ® communications are not used, leave the baud rate at the factory setting (9600). To Enter the Port 1 Baud Rate: Enter the Access menu. Press UP ARROW and ENTER simultaneously. Locate the Baud Rate setting. Press ENTER. The words “PORT 1 BAUD RATE” will appear in the lower display. Enter the baud rate. Press UP ARROW until the correct baud rate is displayed. To Enter the Port 2 Baud Rate: Press ENTER. ”PORT 2 SLAVE ADDRESS” will appear in the bottom display. Enter the Access menu. Press UP ARROW and ENTER simultaneously. Locate the Baud Rate setting. Press ENTER three times. The words “PORT 2 BAUD RATE” will appear in the lower display. Enter the baud rate. Press UP ARROW until the desired baud rate is displayed. Press ENTER. ”EDIT DATE-TIME” will appear in the bottom display. + + 71
- Page 20 and 21: Section 1 Scanner ® 2000 microEFM
- Page 22 and 23: Section 1 Scanner ® 2000 microEFM
- Page 24 and 25: Section 1 Scanner ® 2000 microEFM
- Page 26 and 27: Section 2 Scanner ® 2000 microEFM
- Page 28 and 29: Section 2 Scanner ® 2000 microEFM
- Page 30 and 31: Section 2 Scanner ® 2000 microEFM
- Page 32 and 33: Section 2 Scanner ® 2000 microEFM
- Page 34 and 35: Section 2 Scanner ® 2000 microEFM
- Page 36 and 37: Section 2 Scanner ® 2000 microEFM
- Page 38 and 39: Section 2 Scanner ® 2000 microEFM
- Page 40 and 41: Section 2 Scanner ® 2000 microEFM
- Page 42 and 43: Section 2 Scanner ® 2000 microEFM
- Page 44 and 45: Section 2 Scanner ® 2000 microEFM
- Page 46 and 47: Section 2 Scanner ® 2000 microEFM
- Page 48 and 49: Section 2 Scanner ® 2000 microEFM
- Page 50 and 51: Section 2 Scanner ® 2000 microEFM
- Page 52 and 53: Section 2 Scanner ® 2000 microEFM
- Page 54 and 55: Section 2 Scanner ® 2000 microEFM
- Page 56 and 57: Section 2 Scanner ® 2000 microEFM
- Page 58 and 59: Section 2 Scanner ® 2000 microEFM
- Page 60 and 61: Section 3 Scanner ® 2000 microEFM
- Page 62 and 63: Section 3 Scanner ® 2000 microEFM
- Page 64 and 65: Section 3 Scanner ® 2000 microEFM
- Page 66 and 67: Section 3 Scanner ® 2000 microEFM
- Page 68 and 69: Section 3 Scanner ® 2000 microEFM
- Page 72 and 73: Section 4 Scanner ® 2000 microEFM
- Page 74 and 75: Section 4 Scanner ® 2000 microEFM
- Page 76 and 77: Section 5 Scanner ® 2000 microEFM
- Page 78 and 79: Section 5 Scanner ® 2000 microEFM
- Page 80 and 81: Section 5 Scanner ® 2000 microEFM
- Page 82 and 83: Section 6 Scanner ® 2000 microEFM
- Page 84 and 85: Section 6 Scanner ® 2000 microEFM
- Page 86 and 87: Appendix A Scanner ® 2000 microEFM
- Page 88 and 89: Appendix A Scanner ® 2000 microEFM
- Page 90 and 91: Appendix A Scanner ® 2000 microEFM
- Page 92 and 93: Appendix A Scanner ® 2000 microEFM
- Page 94 and 95: Appendix A Scanner ® 2000 microEFM
- Page 96 and 97: Appendix A Scanner ® 2000 microEFM
- Page 98 and 99: Appendix A Scanner ® 2000 microEFM
- Page 100 and 101: Appendix A Scanner ® 2000 microEFM
- Page 102 and 103: Appendix B Scanner ® 2000 microEFM
- Page 104 and 105: Appendix C Scanner ® 2000 microEFM
- Page 106 and 107: Appendix C Scanner ® 2000 microEFM
- Page 108 and 109: Appendix C Scanner ® 2000 microEFM
- Page 110 and 111: Appendix C Scanner ® 2000 microEFM
- Page 112 and 113: Appendix C Scanner ® 2000 microEFM
- Page 114 and 115: Appendix C Scanner ® 2000 microEFM
- Page 116 and 117: Appendix C Scanner ® 2000 microEFM
- Page 118 and 119: Appendix C Scanner ® 2000 microEFM
<strong>Scanner</strong> ® <strong>2000</strong> microEFM Section 4<br />
Entering the Baud Rate<br />
The baud rate is the number of bits per second that are on the serial port. This setting must match the setting<br />
of the master device polling the <strong>Scanner</strong> <strong>2000</strong> or the serial port. This only applies to the Modbus ® communications;<br />
if Modbus ® communications are not used, leave the baud rate at the factory setting (9600).<br />
To Enter the Port 1 Baud Rate:<br />
Enter the Access menu. Press UP ARROW and ENTER<br />
simultaneously.<br />
Locate the Baud Rate setting. Press ENTER. The words “PORT 1<br />
BAUD RATE” will appear in the lower<br />
display.<br />
Enter the baud rate. Press UP ARROW until the correct<br />
baud rate is displayed.<br />
To Enter the Port 2 Baud Rate:<br />
Press ENTER. ”PORT 2 SLAVE<br />
ADDRESS” will appear in the bottom<br />
display.<br />
Enter the Access menu. Press UP ARROW and ENTER<br />
simultaneously.<br />
Locate the Baud Rate setting. Press ENTER three times. The<br />
words “PORT 2 BAUD RATE” will<br />
appear in the lower display.<br />
Enter the baud rate. Press UP ARROW until the desired<br />
baud rate is displayed.<br />
Press ENTER. ”EDIT DATE-TIME”<br />
will appear in the bottom display.<br />
+<br />
+<br />
71