Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco
Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco
Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Section 4 <strong>Scanner</strong> ® <strong>2000</strong> microEFM<br />
Entering the Slave Address<br />
The slave address is a setting used in Modbus ® communications. It is a number that ranges from 1 to 65535,<br />
excluding 252 to 255 and 64764, which are reserved. If the Modbus ® request message contains the matching<br />
address, the device will respond to the request. In network arrangements, the device must have a unique slave<br />
address. For more information about Modbus ® communications, refer to Section 1—Introduction. If Modbus ®<br />
communications are not used, leave the slave address at the factory setting (1).<br />
To Enter a Port 1 Slave Address:<br />
Enter the Access menu. Press UP ARROW and ENTER<br />
simultaneously.<br />
Locate the Slave Address setting. PORT 1 SLAVE ADDRESS will<br />
appear in the lower display, and the<br />
rightmost digit in the top display will<br />
begin blinking.<br />
Enter the Slave Address.<br />
(range: 1 to 65535; excluding 252 to<br />
255 and 64764)<br />
To Enter a Port 2 Slave Address:<br />
70<br />
Press UP ARROW until the correct<br />
digit is displayed.<br />
Then press LEFT ARROW to select<br />
the next digit to the left.<br />
Repeat using UP and LEFT arrows to<br />
enter all remaining digits.<br />
Press ENTER.<br />
Enter the Access menu. Press UP ARROW and ENTER<br />
simultaneously.<br />
Locate the Slave Address setting. Press ENTER twice until PORT 2<br />
SLAVE ADDRESS appears in the<br />
lower display. The rightmost digit in<br />
the top display will begin blinking.<br />
Enter the Slave Address.<br />
(range: 1 to 65535; excluding 252 to<br />
255 and 64764)<br />
Press UP ARROW until the correct<br />
digit is displayed.<br />
Then press LEFT ARROW to select<br />
the next digit to the left.<br />
Repeat using UP and LEFT arrows to<br />
enter all remaining digits.<br />
Press ENTER.<br />
+<br />
00000000 00000000<br />
+<br />
...<br />
...<br />
00000000 00000000<br />
The Baud Rate menu prompt will appear immediately following the entry of the slave address. See Entering<br />
the Baud Rate below for the baud rate entry procedure.<br />
...<br />
...