22.11.2012 Views

Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco

Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco

Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Scanner</strong> ® <strong>2000</strong> microEFM Section 2<br />

6. Repeat steps 3 through 5 to retest the manifold for leaks.<br />

An additional test can verify the condition of the equalizing valves. Assuming the above test has confirmed<br />

the system is leak free, close both equalizing valves and open the vent. Monitor the differential pressure<br />

reading for any change. Repair or replace the manifold as required if the differential pressure varies.<br />

Zero Offset (Static Pressure or Differential Pressure)<br />

The static pressure input for the <strong>Scanner</strong> <strong>2000</strong> is zeroed at the factory before shipment. However, changes in<br />

temperature and atmospheric pressure can cause the static pressure and differential pressure readings to vary.<br />

The inputs can be easily zeroed in the field, if necessary, prior to putting the <strong>Scanner</strong> <strong>2000</strong> into service.<br />

To zero the static pressure or differential pressure<br />

1. Close the bypass valves to isolate the pressure below<br />

the manifold.<br />

2. Open the equalizer and vent valves.<br />

3. Connect to the <strong>Scanner</strong> <strong>2000</strong> with the ModWorX<br />

Pro software, and apply zero pressure from the<br />

Calibrate Inputs screen (see the ModWorX Pro<br />

Software User Manual; Part No. 9A-30165025; for<br />

complete instructions).<br />

Static Pressure Calibration and Verification<br />

Note The pressure range stamped on the MVT is expressed as psia (absolute). However, <strong>Scanner</strong> <strong>2000</strong><br />

pressure inputs are recalibrated as psig (gauge) at the factory before the device is shipped. Therefore,<br />

pressure readings displayed on the LCD and in the ModWorX Pro software are in terms of psig.<br />

The static pressure and differential pressure inputs are calibrated and verified before the <strong>Scanner</strong> <strong>2000</strong> leaves<br />

the factory, and recalibration in the field may or may not be required. To comply with API standards for<br />

verification, “as found” readings should be recorded at approximately 0, 50, and 100 percent of the operating<br />

pressure range, increasing, and at 80, 20 and 0 percent of the operating pressure range, decreasing. For<br />

example, the static pressure measurements of a 1500-psi sensor should be verified at 0 psi, 750 psi, and 1500<br />

psi, then at 1200 psi, 300 psi, and 0 psi.<br />

!<br />

WARNING: Do not subject the <strong>Scanner</strong> <strong>2000</strong> microEFM to unnecessary shock or over-range<br />

pressure during maintenance operations.<br />

To calibrate the static pressure<br />

1. Close the bypass valves to isolate the pressure below<br />

the manifold.<br />

2. Open the equalizer valves and vent valve to purge<br />

the lines.<br />

3. Close the vent valve.<br />

4. Connect a static pressure simulator to the manifold<br />

(either side).<br />

EQUALIZER<br />

BYPASS/<br />

BLOCK<br />

EQUALIZER<br />

BYPASS/<br />

BLOCK<br />

EQUALIZER<br />

VENT<br />

BYPASS/<br />

BLOCK<br />

EQUALIZER<br />

VENT<br />

BYPASS/<br />

BLOCK<br />

53

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!