22.11.2012 Views

Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco

Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco

Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Section 2 <strong>Scanner</strong> ® <strong>2000</strong> microEFM<br />

Installation Procedure—Direct Mount to a Barton 7000 Series Turbine<br />

Meter (ATEX Compliant)<br />

A <strong>Scanner</strong> <strong>2000</strong> without the MVT bottomworks can be mounted directly to a Barton 7000 series turbine meter<br />

for measuring liquid (Figure 2.15). A stainless steel turbine meter pickup extension supports the <strong>Scanner</strong> <strong>2000</strong><br />

and provides the elevation necessary for good visibility of the display.<br />

52<br />

Turbine meter pickup<br />

extension (ATEX-approved)<br />

10 pipe diameters<br />

upstream (minimum)<br />

<strong>Flow</strong><br />

5 pipe diameters<br />

downstream (minimum)<br />

Figure 2.15—Direct-mount installation for use with a Barton 7000 Series meter<br />

To connect the <strong>Scanner</strong> <strong>2000</strong> to a turbine meter using this method, perform the following steps:<br />

1. Position the <strong>Scanner</strong> <strong>2000</strong> and pickup extension assembly above the flowmeter.<br />

2. Plug the <strong>Scanner</strong> <strong>2000</strong> cable connector into the magnetic pickup of the turbine meter and hand-tighten the<br />

knurled nut on the connector.<br />

3. Screw the <strong>Scanner</strong> <strong>2000</strong>/pickup extension assembly onto the flowmeter threads surrounding the magnetic<br />

pickup with the display facing the desired direction, and tighten.<br />

Performing a Manifold Leak Test<br />

A manifold leak test is recommended prior to operating any differential pressure meter into service. Check the<br />

manifold for leaks as follows.<br />

1. Verify that the instrument is approximately level and<br />

is properly connected to the pressure source.<br />

2. Make sure the vent valve in the manifold is closed.<br />

(The bypass/block valves should be open.)<br />

3. Close both bypass/block valves on the manifold to<br />

isolate pressure between the block valve and the<br />

MVT.<br />

4. Open both equalizer valves to distribute pressure throughout.<br />

EQUALIZER<br />

BYPASS/<br />

BLOCK<br />

EQUALIZER<br />

5. Monitor the pressure readout and watch for a steady decrease in pressure. If leakage is indicated, depressurize<br />

the system by opening both bypass/block valves, then check all manifold and piping joints. Tighten<br />

connections as necessary.<br />

VENT<br />

BYPASS/<br />

BLOCK

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!