Section 2 <strong>Scanner</strong> ® <strong>2000</strong> microEFM<br />

36<br />

Hazardous<br />

location<br />

wiring<br />

Static pressure input<br />

(manifold equalizer valve<br />

must remain open)<br />

10 pipe diameters<br />

upstream<br />

Conduit seal<br />

(required for hazardous<br />

area installations)<br />

H L<br />

5 pipe diameters<br />

downstream<br />

<strong>Flow</strong><br />

Figure 2.7—Remote-mount installation in an AGA-7 turbine meter run<br />

Manifold<br />

Model 21<br />

explosion-proof RTD<br />

assembly or equivalent<br />

6. Install the RTD assembly in the thermowell. Remove the plug from the other conduit opening in the top<br />

of the <strong>Scanner</strong> <strong>2000</strong> enclosure, route the RTD assembly cable through the conduit opening in the top of<br />

the <strong>Scanner</strong> <strong>2000</strong>, and connect it to the main circuit board. A wiring diagram for the RTD assembly is<br />

provided in Figure 3.5, page 64.<br />

Note If additional inputs/outputs or communication connections are required, a condulet box should be<br />

added to the installation.<br />

7. Zero the static pressure and recalibrate the static pressure, if required. See the ModWorX Pro Software<br />

User Manual, Part No. 9A-30165025, for complete instructions. See also Zero Offset (Static Pressure or<br />

Differential Pressure), page 53, and Static Pressure Calibration and Verification, page 53.<br />

CAUTION Do not put the <strong>Scanner</strong> into operation until the valves are positioned properly so that<br />

pressure is supplied to both sides of the MVT. For instructions on proper valve positions,<br />

see Placing the <strong>Scanner</strong> into Operation, page 55.