<strong>Scanner</strong> ® <strong>2000</strong> microEFM Appendix C<br />
Enron Interval/Daily Record Format<br />
The interval and daily record contents are user-configurable. The following table shows the default values.<br />
For more information, see Section 3 of the ModWorX Pro Software User Manual.<br />
Parameter Data Type<br />
Date (MMDDYY) FP32<br />
Time (HH:MM:SS) FP32<br />
FR1 Previous Volume (base units) FP32<br />
FR1 Previous <strong>Mass</strong> (base units) FP32<br />
FR1 Previous Energy (base units) FP32<br />
Differential Pressure Previous Average (InH2O) FP32<br />
Static Pressure Previous Average<br />
(PSIA default, can be PSIG)<br />
FP32<br />
Process Temperature Previous Average (DegF) FP32<br />
FR1 Previous Run Time (seconds of flow) FP32<br />
Turbine 1 Previous Volume (base units) FP32<br />
Turbine 1 Previous Run Time (seconds of flow) FP32<br />
FP32<br />
FP32<br />
FP32<br />
FP32<br />
FP32<br />
Enron Event Record Format<br />
Parameter Data Type<br />
Status U16<br />
Address U16<br />
Time (HH:MM:SS) FP32<br />
Date (MMDDYY) FP32<br />
As-Found FP32<br />
As-Left FP32<br />
The status parameter in the event record can be decoded with the following table.<br />
Alarm Decoding<br />
Description Bit<br />
0-8<br />
User Change/Event 9<br />
Low Low Alarm 10<br />
Low Alarm 11<br />
Hi Alarm 12<br />
Hi Hi Alarm 13<br />
14<br />
Alarm Set/Reset (1=Set, 0=Reset) 15<br />
C-49