<strong>Scanner</strong> ® <strong>2000</strong> microEFM Appendix C<br />

Register<br />

(Decimal)<br />

Device Status<br />

User-Defined Holding Registers<br />

Register<br />

(Hex) Description<br />

Data<br />

Type Access<br />

9148 23BC User-Defined Holding Register 25 FP RO<br />

The device status includes alarm status and diagnostic information such as input status and calculation status.<br />

The <strong>Scanner</strong> <strong>2000</strong> provides 16 user-configurable alarms designated as <strong>Flow</strong> Run Alarms. The user can assign<br />

the alarms to any parameter in the holding register map. Alarms can be defined as low alarms or high alarms.<br />

For details on configuring <strong>Flow</strong> Run Alarms, see Section 3 of the ModWorX Pro Software User Manual. The<br />

current status of the alarms can be obtained by reading the <strong>Flow</strong> Run Alarm registers in the device status map.<br />

A bit value of 1 indicates an alarm condition. Also contained in the device status map are diagnostic registers.<br />

The bits in these registers provide system status for inputs (under range, above range or failed), calculation<br />

status (for confirming whether the flow run is working properly) and details regarding the health of the MVT.<br />

Bit<br />

Register<br />

(Decimal)<br />

<strong>Flow</strong> Run<br />

Alarm High<br />

Device Status Registers<br />

Register<br />

(Hex) Description<br />

Data<br />

Type Access<br />

9900 26AC <strong>Flow</strong> Run Alarms High U32 R/W<br />

9902 26AE Input Status U32 R/W<br />

9904 26B0 Calculation Status U32 R/W<br />

Bit Definitions—Alarms and Diagnostics<br />

<strong>Flow</strong> Run<br />

Alarm Low Diagnostic 1 Diagnostic 2 Diagnostic 3 Diagnostic 4<br />

15 FRA16 High FRA16 Low FR1 Fail FR1 High Reserved Reserved<br />

14 FRA15 High FRA15 Low T1 Fail T1 High Reserved Reserved<br />

13 FRA14 High FRA14 Low T2 Fail T2 High<br />

12 FRA13 High FRA13 Low SP Fail SP High<br />

T2 Calc<br />

Warning<br />

T1 Calc<br />

Warning<br />

Reserved<br />

Reserved<br />

11 FRA12 High FRA12 Low DP Fail DP High Reserved Reserved<br />

10 FRA11 High FRA11 Low PT Fail PT High Reserved Reserved<br />

9 FRA10 High FRA10 Low A1 Fail A1 High Reserved Reserved<br />

8 FRA9 High FRA9 Low A2 Fail A2 High<br />

FR1 Calc<br />

Warning<br />

Reserved<br />

7 FRA8 High FRA8 Low FR1 Override FR1 Low NA Reserved<br />

6 FRA7 High FRA7 Low T1 Override T1 Low NA Reserved<br />

C-45