22.11.2012 Views

Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco

Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco

Scanner 2000 Steam Mass Flow Transmitter ... - Spirax Sarco

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Scanner</strong> ® <strong>2000</strong> microEFM Appendix C<br />

Interval/Daily/Event Pointer Registers<br />

These registers provide an index of the last record that was stored in the log data. These values start at 1 and<br />

increment with each newly created log. When the maximum number of records is reached, the pointer resets<br />

to 1 and starts incrementing again.<br />

Register<br />

(Decimal)<br />

Holding Registers (32-bit)<br />

Register<br />

(Hex) Description<br />

Data<br />

Type Access<br />

7000 1B58 Interval Pointer FP RO<br />

7001 1B59 Daily Pointer FP RO<br />

7002 1B5A Event Counter FP RO<br />

7003 1B5B Real Date FP RO<br />

7004 1B5C Real Time FP RO<br />

7005 1B5D <strong>Flow</strong> Run Alarms FP RO<br />

7006 1B5E <strong>Flow</strong> Run Alarm Low FP RO<br />

7007 1B5F <strong>Flow</strong> Run Alarm High FP RO<br />

7008 1B60 Diagnostic 1 FP RO<br />

7009 1B61 Diagnostic 2 FP RO<br />

7010 1B62 Diagnostic 3 FP RO<br />

7011 1B63 Diagnostic 4 FP RO<br />

7012 1B64 Polling Index FP RO<br />

7013 1B65 FR1 Grand Volume Total FP RO<br />

7014 1B66 FR1 Instantaneous <strong>Flow</strong> Rate FP RO<br />

7015 1B67 FR1 Daily Total FP RO<br />

7016 1B68 FR1 Interval Total FP RO<br />

7017 1B69 FR1 Polling Total FP RO<br />

7018 1B6A FR1 Previous Day Total FP RO<br />

7019 1B6B FR1 Previous Interval FP RO<br />

7020 1B6C FR1 Previous Polling Total FP RO<br />

7021 1B6D FR1 Grand <strong>Mass</strong> Total FP RO<br />

7022 1B6E FR1 Instantanous <strong>Mass</strong> <strong>Flow</strong> Rate FP RO<br />

7023 1B6F FR1 Daily <strong>Mass</strong> Total FP RO<br />

7024 1B70 FR1 Interval <strong>Mass</strong> Total FP RO<br />

7025 1B71 FR1 Polling <strong>Mass</strong> Total FP RO<br />

7026 1B72 FR1 Previous Day <strong>Mass</strong> FP RO<br />

7027 1B73 FR1 Previous Interval <strong>Mass</strong> FP RO<br />

7028 1B74 FR1 Previous Polling <strong>Mass</strong> FP RO<br />

7029 1B75 FR1 Grand Energy Total FP RO<br />

7030 1B76 FR1 Instantaneous Energy <strong>Flow</strong> Rate FP RO<br />

7031 1B77 FR1 Daily Energy Total FP RO<br />

7032 1B78 FR1 Interval Energy Total FP RO<br />

7033 1B79 FR1 Polling Energy Total FP RO<br />

7034 1B7A FR1 Previous Day Energy FP RO<br />

7035 1B7B FR1 Previous Interval Energy FP RO<br />

C-35