Appendix C <strong>Scanner</strong> ® <strong>2000</strong> microEFM<br />
Fluid Property Register<br />
C-22<br />
<strong>Flow</strong> Rate Calculation<br />
6 ISA Nozzle (FUTURE)<br />
7 Long Radius Nozzle (FUTURE)<br />
8 Averaging Pitot Tube (Annubar®)<br />
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0<br />
HV SG V Isen LiqDC GPA HVRef Fluid Property Calc<br />
HV - Heating Value Selection<br />
0 Calculated<br />
1 Manual Entry<br />
SG - Specific Gravity Selection<br />
0 Calculated<br />
1 Manual Entry<br />
V - Viscosity Selection<br />
0 Calculated<br />
1 Manual Entry<br />
Isen - Isentropic Exponent Selection<br />
0 Calculated<br />
1 Manual Entry<br />
LiqDC – Liquid Density Control<br />
0 For Liquids: Register 3057 contains the flowing density<br />
For NGas: Register 3057 contains the base liquid oil density<br />
1 For Liquids: Register 3057 contains the coefficient of thermal<br />
expansion<br />
For NGas: Register 3057 contains the flowing liquid oil<br />
density<br />
GPA - GPA Table Selection<br />
0 Use 2008 Table<br />
1 Use 1996 Table<br />
HVRef - Heating Value Reference<br />
0 US (AGA) – 14.73 psi, 60 Deg F<br />
1 Canada, UK – 103.208 kPa, 15 Deg C<br />
2 Brazil (FUTURE)<br />
3 France (FUTURE)<br />
Fluid Property Calculation<br />
0 AGA-8 Detail<br />
1 AGA-8 Gross<br />
2 (FUTURE)<br />
3 IF-97 (STEAM ONLY)<br />
4 IF-97/James - (STEAM ONLY)<br />
5-15 (FUTURE)<br />
16 Generic Liquid (API 2145 Table 6C)