Appendix C <strong>Scanner</strong> ® <strong>2000</strong> microEFM<br />
C-6<br />
Register<br />
(Decimal)<br />
Communications Configuration<br />
Register<br />
(Hex) Description<br />
1100 44C Port 1 - Port Usage<br />
0 - Slave<br />
1 - Master<br />
1101 44D Port 1 Slave Address<br />
[1 to 65535, excluding 252 to 255 and 64764]<br />
1102 44E Port 1 - Baud Rate<br />
0 - 300<br />
1 - 600<br />
2 - 1200<br />
3 - 2400<br />
4 - 4800<br />
5 - 9600<br />
6 - 19200<br />
7 - 38400<br />
8 - 57600<br />
9 - 115200<br />
1103 44F Port 1 - Bus Delay<br />
mS of delay before transmitting data<br />
1104 450 Port 1 - Bus Timeout<br />
mS of delay before resetting communications<br />
1105 451 Port 2 - Port Usage<br />
0 - Slave Only<br />
1106 452 Port 2 Slave Address<br />
[1 to 65535, excluding 252 to 255 and 64764]<br />
1107 453 Port 2 - Baud Rate<br />
0 - 300<br />
1 - 600<br />
2 - 1200<br />
3 - 2400<br />
4 - 4800<br />
5 - 9600<br />
6 - 19200<br />
7 - 38400<br />
8 - 57600<br />
9 - 115200<br />
1108 454 Port 2 - Bus Delay<br />
mS of delay before transmitting data<br />
1109 455 Port 2 - Bus Timeout<br />
mS of delay before resetting communications<br />
Register<br />
(Decimal)<br />
Real Time<br />
Register<br />
(Hex) Description<br />
Data<br />
Type Access Default<br />
U16 R/W 0<br />
U16 R/W 1<br />
U16 R/W 5<br />
U16 R/W 10<br />
U16 R/W 50<br />
U16 R/W 0<br />
U16 R/W 1<br />
U16 R/W 5<br />
U16 R/W 10<br />
U16 R/W 50<br />
Data<br />
Type Access<br />
1200 4B0 Year (Real Year = register value plus <strong>2000</strong>) U16 R/W<br />
1201 4B1 Month [1-12] U16 R/W<br />
1202 4B2 Day [1-31] U16 R/W<br />
1203 4B3 Hour [0-23] U16 R/W<br />
1204 4B4 Minute [0-59] U16 R/W<br />
1205 4B5 Second [0-59] U16 R/W<br />
This block of registers is used to set the instrument’s internal clock. To set the time, it is recommended that all<br />
registers be written in one message.<br />
The time and date can also be read in the holding register groups as floating-point data.