CHAPTER 4: MESSAGESPowerView Message Meaning Corrective ActionGeneral Fault(continued)Input circuit breakertripped open.The input circuit breaker on the <strong>UPS</strong>tripped open. Input voltage isdisconnected to the <strong>UPS</strong>.Option 1: If this occurs inconjunction with an overloadcondition, decrease the load andreset the breaker.Option 2: If no overloadcondition exists, reset breaker. Ifit trips open again, call yourcontract service provider or <strong>APC</strong>Technical Support.System level fan failed. A cooling fan in the <strong>UPS</strong> frame failed. Call your contract serviceprovider or <strong>APC</strong> TechnicalSupport.The RedundantIntelligence Module (RIM)is in control.IIC inter-modulecommunications failed.The MIM failed, and the RIM isfunctioning as the primary intelligencemodule.The communications between the MIMand at least one other module failed.Replace the intelligence module.Refer to module replacementprocedure.Call your contract serviceprovider or <strong>APC</strong> TechnicalSupport.22