CHAPTER 3: MENU COMMANDSSetup Menu (continued)Menu Item Function OptionsAlarms Sets the alarm thresholds. NoneRedundancyLoadRuntimeAn audible alarm sounds if the redundancy falls belowthis level.An audible alarm sounds when the load exceeds thislimit. (Upper value is limited by the maximum power ofthe <strong>UPS</strong>.)An audible alarm sounds if the available runtime fallsbelow this level (Hours:min).0(default), 1, or 2Never(default), 1, 2, 3, 4,5, 6, 7, 8, 9, 10, or 12 <strong>kVA</strong>0:0(default),5m, 10m,15m, 30m, 45m,1h, 2h, 3h,4h, 5h, 6h, 7h, or 8hBypassIn the unlikely event that both the <strong>UPS</strong> fails and the inputvoltage or line frequency is outside of normal range, thisoption lets you choose to go into Bypass mode or dropthe load.Go to Bypass orDrop LoadCopy Not used with this <strong>UPS</strong>. NoneOther Remaining user-defined settings. NoneSelf Test<strong>UPS</strong> IDThe <strong>UPS</strong> can automatically test itself at this userspecifiedinterval.Assigns an eight-character text string to a system.At Power On, 7 days,14 days(default) , orDisabledOutputSets output voltage. Selection depends upon systemconfiguration.200V, 208V, 220V, 230V,or 240VVout Reporting Reports the most significant output voltage. Auto16