CHAPTER 5: SPECIFICATIONSTechnical ReferenceThis section contains operation, input, output, physical, and compliance specifications for the <strong>UPS</strong>.Operational SpecificationsSystemTopologyPower Array with hot-swappable modules that are redundant, scalable,self-diagnosing, and fault-tolerantOn-line, double conversion with input power factor correctionPower Capacity 4 –16 <strong>kVA</strong> N, 12 <strong>kVA</strong> N+1Battery TypeBattery ChargerBattery Recharge TimeExtended Battery OptionHot-swappable, sealed, maintenance-free, lead acid, 3 – 5 years lifeAutomatic float, equalized high frequency PWM charger< 4 hours with standard supplied packs in the frameYesAmbient Temperature 0 – 40 °CRelative HumidityElevation< 95% non-condensing0 – 10,000 ft (3,000 mm)Input SpecificationsNominal Input VoltageInput Voltage RangeInput Frequency RangeInput Power FactorInput Current THDInput Inrush CurrentInput Generator Sizing200, 208, 220, 230, 240 Vac; 60 or 50 Hz, 1 phase, 3 wire155 to 276 Vac with batteries charging & supporting full load47 – 63 HzApproximately. 0.98 @ full loadApproximately. 6% @ full loadMaximum 150% of full load current1.5 x <strong>UPS</strong> capacity31