CHAPTER 3: SITE PREPARATION<strong>Installation</strong> RequirementsWhen selecting a location for the <strong>UPS</strong>, consider the following:Physical RequirementsStandard <strong>Installation</strong> (4-post rack)• Standard 19 in. (46.5 cm) rack• At least 800 mm deep• 15U rack space• Recommended installation is in the bottom of the rack,due to its weight of up to 600 lbs (273 kg), dependingon the configuration.• Mounting rails and hardware providedFunctional Access• Front access for circuit breakers, maintenance bypass,PowerView, and module installation or replacement.• Rear access for system enable switch, power distributionand management communications.• Front to rear airflow.Air FlowDo not block front bezels and vents onrear or sides of the <strong>UPS</strong>.Environmental RequirementsInstall the <strong>UPS</strong> in a temperature controlled, clean, dry and protected indoor area that is free ofconductive contaminants.Temperature 0 – 40 degrees Celsius (32 – 104 degrees F)Relative HumidityElevation0 – 95% non-condensing0 – 3,000 m (0 – 10,000 ft above mean sea level)Thermal Dissipation<strong>UPS</strong> 12 <strong>kVA</strong> N+ 1(Full load)4246 BTUs typical – Batteries charged9664 BTUs typical – Batteries charging15