CHAPTER 3: SITE PREPARATIONShipping & ReceivingThe <strong>UPS</strong> and modular components are shipped on one or more pallets, depending on the configuration. The frame isinstalled first and then modular components are installed within the frame.Weights andMeasurementsLengthInches (cm)WidthInches (cm)HeightInches (cm)Weightlbs (kg)UnpackagedChassis* 27.8 (70.6) 18.9 (48.0) 26.1 (66.3) 185.0 (84.1)Power module 23.4 (59.4) 10.0 (25.4) 5.2 (13.2) 29.0 (13.2)Battery module 23.5 (59.7) 6.6 (16.8) 5.2 (13.2) 64.0 (29.1)Intelligence modules 19.6 (49.8) 6.6 (16.8) 1.6 (4.1) 5.0 (2.3)PackagedChassis** 36.0 (91.4) 30.0 (76.2) 37.4 (95.0) 264.0 (120.0)Power module 30.8 (78.2) 12.3 (31.2) 17.0 (43.2) 35.0 (15.9)Battery module 30.8 (78.2) 12.3 (31.2) 17.0 (43.2) 70.0 (31.8)Intelligence modules 22.8 (57.9) 12.5 (31.8) 7.3 (18.5) 7.0 (3.2)* Overall length including bezel** Includes rail and accessory bezel kitShort-Term Battery Module Storage RequirementsDo not install battery modules until you are ready to power up the <strong>UPS</strong>. Batteries can bepermanently damaged if loaded prematurely.• Store the battery module(s) at a cool ambient temperature of < 25 °C.• Storage of batteries longer than six months without recharging may result in permanentdamage.14