Faults<br />
7. Allgemeine Beschreibung<br />
Faults<br />
System error<br />
Error<br />
No.<br />
Designation Description<br />
22<br />
Operating Manual NAV 1.0<br />
T HE POWER FAMILY<br />
026 Flow monitoring The fl ow switch in ground water systems has switched off the heat<br />
pump (< 3 times in 24h).<br />
027 Flow lock The fl ow switch in ground water systems has switched off the heat<br />
pump (> 3 times in 24h). The heat pump is no longer triggered.<br />
028 Start-up current limiter see LED Error start-up current limiter (< 5 times in 24h). The type of error is<br />
displayed on the start-up current limiter.<br />
029 Start-up current limiter 5x in 24h Error start-up current limiter (> 5 times in 24h). The heat pump is no<br />
longer triggered.<br />
030 Motor protection heat source pump The motor protection for the heat source pump has been triggered<br />
(< 5 times in 24h).<br />
031 Motor protection heat source 5x in 24h The motor protection for the heat source pump has been triggered<br />
(> 5 times in 24h). The heat pump is no longer triggered.<br />
032 Maximum defrosting time exceeded The maximum defrosting time has been exceeded<br />
033 Minimum condenser temperature undershot<br />
The heat pump has been switched off due to undershooting the minimum<br />
condenser temperature.<br />
034 Fan error The control system for the fan has detected a functional error.<br />
036 Electric immersion heater overheating The safety thermostat of the immersion heater has been activated.<br />
050 Dew-point monitoring device has been<br />
activated<br />
The heat pump has been switched off by the dew-point monitoring<br />
device.<br />
060 Heat source temperature The measured heat source outlet temperature undershoots the<br />
minimum heat source temperature.<br />
061 Warning heat source temperature The heat source outlet temperature reaches a critical value min. heat<br />
source temperature + 2K<br />
(C) IDM ENERGIESYSTEME GMBH