Faults<br />

7. Allgemeine Beschreibung<br />

Faults<br />

System error<br />

Error<br />

No.<br />

Designation Description<br />

22<br />

Operating Manual NAV 1.0<br />

T HE POWER FAMILY<br />

026 Flow monitoring The fl ow switch in ground water systems has switched off the heat<br />

pump (< 3 times in 24h).<br />

027 Flow lock The fl ow switch in ground water systems has switched off the heat<br />

pump (> 3 times in 24h). The heat pump is no longer triggered.<br />

028 Start-up current limiter see LED Error start-up current limiter (< 5 times in 24h). The type of error is<br />

displayed on the start-up current limiter.<br />

029 Start-up current limiter 5x in 24h Error start-up current limiter (> 5 times in 24h). The heat pump is no<br />

longer triggered.<br />

030 Motor protection heat source pump The motor protection for the heat source pump has been triggered<br />

(< 5 times in 24h).<br />

031 Motor protection heat source 5x in 24h The motor protection for the heat source pump has been triggered<br />

(> 5 times in 24h). The heat pump is no longer triggered.<br />

032 Maximum defrosting time exceeded The maximum defrosting time has been exceeded<br />

033 Minimum condenser temperature undershot<br />

The heat pump has been switched off due to undershooting the minimum<br />

condenser temperature.<br />

034 Fan error The control system for the fan has detected a functional error.<br />

036 Electric immersion heater overheating The safety thermostat of the immersion heater has been activated.<br />

050 Dew-point monitoring device has been<br />

activated<br />

The heat pump has been switched off by the dew-point monitoring<br />

device.<br />

060 Heat source temperature The measured heat source outlet temperature undershoots the<br />

minimum heat source temperature.<br />

061 Warning heat source temperature The heat source outlet temperature reaches a critical value min. heat<br />

source temperature + 2K<br />

(C) IDM ENERGIESYSTEME GMBH