Sensor error<br />
Error<br />
No.<br />
Designation Description<br />
130 Flow sensor HC C Short circuit<br />
131 Interruption<br />
132 Flow sensor HC D Short circuit<br />
133 Interruption<br />
134 Room sensor HC C Short circuit<br />
135 Interruption<br />
136 Room sensor HC D Short circuit<br />
137 Interruption<br />
138 Flow sensor HC E Short circuit<br />
139 Interruption<br />
140 Flow sensor HC F Short circuit<br />
141 Interruption<br />
142 Flow sensor HC G Short circuit<br />
143 Interruption<br />
144 Room sensor HC E Short circuit<br />
145 Interruption<br />
146 Room sensor HC F Short circuit<br />
147 Interruption<br />
148 Room sensor HC G Short circuit<br />
149 Interruption<br />
System error<br />
Error<br />
No.<br />
Designation Description<br />
Faults<br />
020 Heat pump fl ow maximum temperature Heat pump fl ow temperature is above the set maximum temperature.<br />
021 Heat pump fl ow minimum temperature Heat pump fl ow temperature is below the set minimum temperature.<br />
022 Low pressure switch The low pressure switch has switched off the heat pump (< 3 times<br />
in 24h).<br />
023 Low pressure lock pressure fault The low pressure switch has switched off the heat pump (> 3 times<br />
in 24h). The heat pump is no longer triggered.<br />
024 High pressure switch The high pressure switch has switched off the heat pump (< 3 times<br />
in 24h).<br />
025 High pressure lock pressure fault The high pressure switch has switched off the heat pump (> 3 times<br />
in 24h). The heat pump is no longer triggered.<br />
(C) IDM ENERGIESYSTEME GMBH Operating Manual NAV 1.0 21<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12<br />
13<br />
Faults