Temperature Settings<br />

4. Allgemeine Beschreibung<br />

Temperature Settings<br />

Heating circuit temperatures parameters<br />

Par.<br />

No.<br />

Name Description<br />

12<br />

Operating Manual NAV 1.0<br />

T HE POWER FAMILY<br />

HC108 Heating limit For mixer and uncontrolled heating circuits a heating limit can be set in the user menu<br />

above which the heating mode is blocked.<br />

HC109 Room infl uence<br />

Above this outside temperature, no further heating demand is generated by the<br />

heating circuit. The heating limit is deactivated <strong>with</strong> the setting 0.<br />

The room infl uence factor shows to what extent the control system reacts to the room<br />

temperature.<br />

HC110 Heating curve<br />

If the room unit is assembled in a room affected by other heat sources (e.g. a tiled<br />

stove) a smaller proportion should be selected. The temperature of the room in which<br />

the room unit is assembled, also affects the heating of the other rooms.<br />

Note: Parameter is only visible in the case of confi gured room unit.<br />

Given the steepness of the characteristic heating curve, the relation of the outside<br />

temperature to the required fl ow temperature is established.<br />

HC150 Normal Cooling Room<br />

Temp.<br />

HC151 ECO Cooling Room<br />

Temp.<br />

2,6<br />

2,4<br />

2,2<br />

2<br />

The greater the steepness of the characteristic curve is set, the higher the fl ow<br />

temperature for the heating depending on the outside temperature as well as on the<br />

heating and cooling limits.<br />

Parameter for the desired room temperature during Normal Cooling mode.<br />

Parameter for the desired room temperature during ECO Cooling mode.<br />

HC153 Cooling fl ow Parameter for the desired cooling circuit fl ow temperature.<br />

HC154 Dew-point gap This shows the minimum temperature difference between the dew-point (room humidity<br />

sensor) and the set fl ow temperature.<br />

HC108 Cooling limit Below this outside temperature no further cooling demand is generated by the<br />

cooling circuit.<br />

1,8<br />

Outside temperature [°C]<br />

1,6<br />

1,4<br />

1,2<br />

1<br />

0,8<br />

0,6<br />

0,4<br />

(C) IDM ENERGIESYSTEME GMBH<br />

65<br />

60<br />

55<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

[°C]<br />

Flow temperature