I&O Manual - EVCA - Categories On Thermal Solutions Products LLC
I&O Manual - EVCA - Categories On Thermal Solutions Products LLC
I&O Manual - EVCA - Categories On Thermal Solutions Products LLC
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
31.0<br />
[787.4]<br />
MOUNTED LOW<br />
WATER CUT-OFF<br />
MANUAL SHUT-OFF<br />
VALVE<br />
REQUIREMENT<br />
FOR BURNER<br />
REMOVAL<br />
19.0<br />
[482.6]<br />
12.0<br />
[304.8]<br />
3.0<br />
[76.2]<br />
GAS PILOT<br />
Ø.25 TUBE<br />
GAS VENT .75 NPT<br />
PIPE<br />
GAS SUPPLY<br />
1.5 NPT<br />
21.8<br />
[552.9]<br />
14.5<br />
[368.7]<br />
SUPPLY TO SYSTEM,<br />
2" VICTAULIC<br />
Notes:<br />
1. Piping<br />
removed for<br />
visual clarity.<br />
2. See notes<br />
concerning<br />
Net AHRI<br />
Ratings on<br />
page 4.<br />
79.1<br />
[2009.1]<br />
28.3<br />
[717.6]<br />
19.5<br />
[495.3]<br />
46.0<br />
[1169.5]<br />
56.5<br />
[1435.1]<br />
82.1<br />
[2085.3]<br />
16.5<br />
[418.8]<br />
FLUE OUTLET Ø6<br />
SAF-T-VENT<br />
WATER INLET<br />
2.5 NPT<br />
INLET AIR Ø8<br />
GALVANIZED DUCT<br />
4.6<br />
[116.7]<br />
6.2<br />
[157.2]<br />
9.4<br />
[239.7]<br />
14.2<br />
[360.0]<br />
21.8<br />
[552.5]<br />
CONDENSATE DRAINS TO BE<br />
PIPED TO AN EXTERNAL TRAP<br />
BOILER DRAIN<br />
1 NPT PIPE<br />
2.5<br />
[63.5]<br />
26.5<br />
[672.8]<br />
46.4<br />
[1177.8]<br />
BOILER MODEL<br />
NUMBER<br />
INPUT<br />
(MBH)<br />
GROSS<br />
OUTPUT<br />
(MBH)<br />
NET AHRI<br />
RATING<br />
(MBH) 2<br />
WATER<br />
VOLUME<br />
(gallons)<br />
CAPACITIES<br />
DRY WEIGHT<br />
(lbs.)<br />
WET WEIGHT<br />
(lbs.)<br />
<strong>EVCA</strong>-1500 1,500 1,420 1,235 19.8 1,704 1,994<br />
<strong>EVCA</strong>-2000 2,000 1,900 1,652 21.2 1,897 2,163<br />
BOILER MODEL<br />
RANGE<br />
1500/2000<br />
ELECTRICAL<br />
SUPPLY (volts/Hz/phase) blower motor (hp) pump motor (hp) Nominal power draw (amps)<br />
120/60/1<br />
19.3<br />
208/60/1 11.9<br />
230/60/1 11.8<br />
1 1/2 3/4<br />
208/60/3 9.3<br />
230/60/3 9.0<br />
460/60/3 4.5 7.2<br />
31.0<br />
[787.4]<br />
MOUNTED LOW<br />
WATER CUT-OFF<br />
MANUAL SHUT-OFF<br />
VALVE<br />
REQUIREMENT<br />
FOR BURNER<br />
REMOVAL<br />
31.0<br />
[787.4]<br />
12.0<br />
[304.8]<br />
3.0<br />
[76.2]<br />
GAS PILOT<br />
Ø.25 TUBE<br />
GAS VENT<br />
.75 NPT PIPE<br />
GAS SUPPLY<br />
1.5 NPT<br />
21.8<br />
[552.9]<br />
15.1<br />
[384.0]<br />
SUPPLY TO SYSTEM,<br />
2" VICTAULIC<br />
91.8<br />
[2331.7]<br />
92.8<br />
[2357.1]<br />
FLUE OUTLET Ø6<br />
SAF-T-VENT<br />
CONDENSATE DRAINS TO BE<br />
PIPED TO AN EXTERNAL TRAP<br />
51.9<br />
[1318.5]<br />
WATER INLET<br />
2.5 NPT<br />
17.1<br />
[433.6]<br />
INLET AIR Ø8<br />
GALVANIZED DUCT<br />
BOILER DRAIN<br />
1 NPT PIPE<br />
30.4<br />
[771.7]<br />
28.3<br />
[717.6]<br />
19.5<br />
[495.3]<br />
44.5<br />
[1131.0]<br />
53.0<br />
[1346.2]<br />
6.2<br />
[157.2]<br />
4.6<br />
[116.7]<br />
9.4<br />
[239.7]<br />
14.2<br />
[360.0]<br />
2.5<br />
[63.5]<br />
21.8<br />
[552.5]<br />
Figure 1b: Dimensions and Capacities <strong>EVCA</strong> 1500 & 2000<br />
6