F. ELECTRICAL<br />

1. General. Install wiring and ground boiler in<br />

accordance with authority having jurisdiction or in<br />

absence of such requirements National Electrical<br />

Code, ANSI/NFPA 70 and/or CSA C22.1 Electrical<br />

Code.<br />

WARNING<br />

Failure to properly wire electrical connections to<br />

the boiler may result in serious physical harm.<br />

DO NOT ATTACH ADDITIONAL J-Box to back or<br />

top of boiler jacket.<br />

DANGER<br />

Positively assure all electrical connections are<br />

unpowered before attempting installation or<br />

service of electrical components or connections<br />

of the boiler or building. Lock out all electrical<br />

boxes with padlock once power is turned off.<br />

2. A separate electrical circuit must be run from<br />

the main electrical service with an over-current<br />

device/disconnect in the circuit. A service switch<br />

is recommended and may be required by some<br />

local jurisdictions. Locate the service switch such<br />

that the appliance can be shut off without exposing<br />

personnel to danger in the event of an emergency.<br />

3. Connect the main power supply and ground from<br />

fused disconnect to proper boiler electrical leads<br />

located in the junction box at the rear of the boiler.<br />

Refer to electrical consumption plate on boiler<br />

jacket.<br />

4. Protection for the factory installed circulator is<br />

provided by the factory. Install a separate fused<br />

disconnect switch for each additional circulator<br />

installed (i.e. boiler and system circulators).<br />

5. Connect field supplied safety limits or devices<br />

using proper terminals provided in boiler electrical<br />

cabinet. Refer to wiring diagram supplied with<br />

boiler for wiring information. Refer to Figures 9a -<br />

9f for typical wiring diagrams. Refer to Figure 1, for<br />

electrical requirements for boiler.<br />

WARNING<br />

Electrical power may be supplied from more than<br />

one service. Make sure all power is off before<br />

attempting any electrical work.<br />

The wiring diagrams contained in this manual are<br />

for reference purposes only. Each boiler may be<br />

wired differently according to the specifications<br />

given to <strong>Thermal</strong> <strong>Solutions</strong> at the time the boiler<br />

was purchased. Always use the wiring diagram<br />

provided with the boiler. If the wiring diagram<br />

provided with the boiler is unavailable, STOP all<br />

wiring work and contact <strong>Thermal</strong> <strong>Solutions</strong> for a<br />

replacement diagram.<br />

Do not directly connect low voltage (24 volt,<br />

milliamp, etc.) controls to this boiler. If low<br />

voltage controls are desired, isolating relays<br />

must be used.<br />

Never jump out any safety controls.<br />

Never jump out or make inoperative any safety<br />

or operating controls. Each boiler must be<br />

protected with a properly sized over-circuit<br />

device.<br />

6. The following pages have sample wiring diagrams.<br />

Contact <strong>Thermal</strong> <strong>Solutions</strong> Representative or visit<br />

website (www.thermalsolutions.com) for current<br />

wiring options.<br />

7. An as-built wiring diagram is included with every<br />

boiler when it ships.<br />

CAUTION<br />

Each boiler must be protected with a dedicated<br />

properly sized fused disconnect.<br />

24