VI. Boiler Operational Sequence<br />

Product Features<br />

Boiler Sequence<br />

Pre-Sequence States<br />

Start/Stop Sequence States<br />

BOILER STATE<br />

LCD Display<br />

Terminal Number<br />

Parameter/Note<br />

Boiler Disable<br />

Warm Weather<br />

Shutdown<br />

Lockout<br />

St<strong>and</strong>by<br />

Pump Purge<br />

Limit Hold<br />

Purge / Pilot Ignition<br />

Low Fire / Ignition<br />

Main Ignition<br />

Low Fire Hold<br />

Boiler Running<br />

Fan Post Purge<br />

Pump Cooldown<br />

Limits<br />

Relay Outputs Interlock Inputs<br />

Inputs<br />

Parameter / Notes<br />

Boiler Disable or Remote On/Off RO -<br />

Outdoor Air Temp ><br />

Warm Weather Shutdown Setpoint<br />

Domestic Hot Water Priority<br />

Low Fire Hold<br />

Fuel Valve Energized<br />

Flame Safeguard Alarm<br />

System Pump Feedback<br />

Call For Heat<br />

Recycling Limits<br />

(LC, OO, WF, GP <strong>and</strong> HL inputs)<br />

Non-Recycling Limits<br />

(Combustion Air Flow (CA Input))<br />

Call For Heat Relay<br />

Lockout Indicator<br />

(Manual Reset Required)<br />

Spare Output<br />

Boiler Pump<br />

System Pump<br />

System Pump Backup Pump<br />

O+,O-<br />

DP<br />

SI<br />

CS<br />

AL<br />

SI<br />

R+,R-<br />

OR<br />

BO,BC<br />

LC , OO ,WF,<br />

GP ,HL<br />

CA<br />

CH<br />

VI<br />

BP<br />

44,30,<br />

75<br />

20,74<br />

9<br />

-<br />

-<br />

9<br />

70,71,<br />

72<br />

8,27,<br />

28<br />

-<br />

-<br />

LO -<br />

-<br />

2,30<br />

SP 25,30<br />

SO 10<br />

a<br />

b &c<br />

a<br />

a 3/d - - - - 53 - 54/d 4/d<br />

Boiler Enable/Disable On<br />

Domestic Hot Water Dem<strong>and</strong> Monitored<br />

System Pump Feedback Monitored<br />

Call For Heat<br />

Recycling Limits Made<br />

Non-Recycling Limits Made<br />

Call For Heat Relay On<br />

Spare Output On<br />

Boiler Pump On<br />

System Pump On<br />

Starts in response to System Pump Feedback Input SI<br />

Combustion Air Damper<br />

System Alarm<br />

SO<br />

10,27/<br />

e<br />

SO 10<br />

Combustion Air Damper Open<br />

Alarm Status is Monitored<br />

Modulation Outputs<br />

Firing Rate<br />

Mixing Valve Output<br />

Blower High Speed<br />

Purge %<br />

Modulation<br />

Low Fire %<br />

Blower 0 Volts<br />

MS,MR<br />

V+,V-,<br />

P+,P-<br />

V+,V-,<br />

P+,P-<br />

V+,V-,<br />

P+,P-<br />

V+,V-,<br />

P+,P-<br />

V+,V-,<br />

P+,P-<br />

Sage Boiler Control Instruction Manual Page 6 of 52<br />

6,79,<br />

80<br />

49<br />

52<br />

-<br />

9,51/f<br />

50<br />

46<br />

Modulate<br />

Notes<br />

a. Boiler Pump is “On” when the Boiler Pump is set to “On Always” or the boiler is lead boiler <strong>and</strong> Boiler Pump is set to “On Lead”.<br />

b. Boiler Pump is "On" when the Boiler Pump is set to "On Always" <strong>and</strong> WWSD is set to "WWSD of System Pump" or “Off”.<br />

c. System Pump is "On" when the System Pump is set to “yes” <strong>and</strong> WWSD is set to either "WWSD of Boiler" or "Off".<br />

d. Boiler pump is "On" during Prepurge <strong>and</strong> Post Purge when Boiler Pump is set to "Purge" or boiler is lead & Boiler Pump is set to “On Lead”.<br />

e. Combustion Air Damper Spare Output is maintained “On” for 2 minutes after the Call For Heat is removed.<br />

f. Modulation rate is held at purge % when low fire input is not provided.