<strong>Thermal</strong> <strong>Solutions</strong> ProtoNode Start Up guide Page 7 of 32<br />
2.3 Configure the A, B, and S Bank of DIP Switches<br />
<br />
<br />
The A, B and S need to be set on the ProtoNode RER (FPC‐N34).<br />
The A and B banks of DIP switches are disabled on the ProtoNode LER (FPC‐N35) and are not set.<br />
2.3.1 Setting Device Node-ID’s and Serial Settings of the TSBC <strong>Controller</strong>s<br />
<br />
<br />
<br />
The baud rates on all the boilers need to match what is set on the ProtoNode’s Modbus RTU RS-485 port<br />
which is 19200 baud. See appendix B.1 for the serial settings<br />
All the boilers need to be set for odd parity, 8 date bits, and 1 stop bit.<br />
All of the <strong>Thermal</strong> <strong>Solutions</strong> TSBC <strong>Boiler</strong>s connected to the ProtoNode need to have their own unique<br />
Modbus Node address. They need to be set between 1 and 255.<br />
2.3.2 Setting the MAC Address (DIP Switch A0 – A7) for BACnet MS/TP<br />
<br />
The A Bank DIP switches on the ProtoNode RER allow users to set the MAC Address for BACnet<br />
MS/TP only.<br />
Figure 1: A0 – A7 DIP Switches<br />
<br />
Please refer to Error! Reference source not found. for the full range of addresses to set Node-<br />
ID/Device Instance.<br />
NOTE: When setting DIP Switches, please ensure that power to the board is OFF.<br />
2.3.3 Setting the Node-ID/Device Instance for Metasys N2, BACnet/IP, and<br />
Modbus TCP<br />
<br />
BACnet IP/BACnet MSTP Addressing: The BACnet device instances will be set by the node offset + the<br />
Modbus RTU device address set on the TSBC devices.<br />
o<br />
The node offset is currently set to 50000 in the config so Modbus address 1 would be assigned a<br />
device instance of 50001.<br />
<br />
o If the 2 nd Device is Modbus address set 2 then the device instance will be set to 50002.<br />
Metasys N2 Addressing: The Metasys N2 device addresses will be the same as the discovered TSBC<br />
Modbus RTU devices.<br />