Thermal Solutions Boiler Controller To Building Automatio
Thermal Solutions Boiler Controller To Building Automatio
Thermal Solutions Boiler Controller To Building Automatio
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Thermal</strong> <strong>Solutions</strong> ProtoNode Startup Guide Page 29 of 32<br />
Appendix B.4. TSBC Modbus RTU Mappings to LonWorks.<br />
Point Name Lon Name Lon SNVT Type<br />
Outdoor Air Reset<br />
Enable/Disable nvoOAResEn_Disbl SNVT_switch<br />
Domestic Hot Water Priority nvoDomHotWtrPri SNVT_switch<br />
Local/Remote nvoLoc_Rem SNVT_switch<br />
Remote On/Off Modbus<br />
Command nvi/nvoRemOnOffMdCmd SNVT_switch<br />
Spare Input (Programmable) nvoSpareInput SNVT_switch<br />
Low Water Cutoff Switch nvoLoWtrCutoffSw SNVT_switch<br />
Burner On/Off Switch nvoBrnrOn_OffSw SNVT_switch<br />
Low Water Flow nvoLoWtrFLo SNVT_switch<br />
High and Low Gas Pressure<br />
Switches nvoHi_LoGasPrsSw SNVT_switch<br />
Operating or High Limit nvoOpOrHiLimit SNVT_switch<br />
Low Combustion Air Flow nvoLoCmbstAirFlo SNVT_switch<br />
Fuel Valve Energized nvoFlVlvEnergizd SNVT_switch<br />
Flame Safeguard Alarm nvoFlmSafegrdAlm SNVT_switch<br />
Call For Heat (CFH) nvoCallForHeat SNVT_switch<br />
General Alarm nvoGeneralAlm SNVT_switch<br />
Vent Inducer nvoVentInducer SNVT_switch<br />
<strong>Boiler</strong> Pump nvoBlrPump SNVT_switch<br />
System Pump nvoSystemPump SNVT_switch<br />
Spare Output (Programmable) nvoSpareOutput SNVT_switch<br />
State <strong>Boiler</strong> Disabled nvoStBlrDisabled SNVT_switch<br />
State Weather Shutdown nvoStWthrShtdwn SNVT_switch<br />
State Lockout nvoStLockout SNVT_switch<br />
State Pump Purge nvoStPumpPurge SNVT_switch<br />
State Limit Hold nvoStLimitHold SNVT_switch<br />
State Purge/Pilot Ign nvoStPrgPilotIgn SNVT_switch<br />
State Low Fire/Ignition nvoStLoFire_Ign SNVT_switch<br />
State Main Ignition nvoStMainIgn SNVT_switch<br />
State Low Fire Hold nvoStLoFireHold SNVT_switch<br />
State <strong>Boiler</strong> Running nvoStBlrRunning SNVT_switch<br />
State Fan Post Purge nvoStFanPostPrg SNVT_switch<br />
State Pump Cool Down nvoStPmpCoolDwn SNVT_switch<br />
State Standby nvoStStandby SNVT_switch<br />
Annunciator Low Water Level nvoAnnLoWtrLvl SNVT_switch<br />
Annunciator Off Switch nvoAnnOffSw SNVT_switch<br />
Annunciator Low Water Flow nvoAnnLoWtrFLo SNVT_switch<br />
Annunciator Fuel Limit nvoAnnFuelLimit SNVT_switch<br />
Annunciator High Temp Limit nvoAnnHiTmpLimit SNVT_switch<br />
Annunciator Low Air Flow nvoAnnLoAirFLo SNVT_switch<br />
Annunciator FSG Lockout nvoAnnFSGLockout SNVT_switch<br />
Annunciator Outlet Temp Fail nvoAnnOtltTmpFl SNVT_switch<br />
Annunciator Inlet Temp Fail nvoAnnInltTmpFl SNVT_switch<br />
Annunciator OA Temp Fail nvoAnnOATmpFail SNVT_switch<br />
Annunciator Remote Temp Fail nvoAnnRemTmpFail SNVT_switch<br />
Annunciator Remote In Fail nvoAnnRemInFail SNVT_switch<br />
Annunciator Comm Fail nvoAnnCommFail SNVT_switch<br />
Annunciator Low Inlet Temp nvoAnnLoInletTmp SNVT_switch<br />
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com<br />
Tel: (408) 964 4444 Fax: (408) 964 4425 <strong>To</strong>ll Free: (800) 317 8319 x141 email: support@protocessor.com