01.07.2015 Views

Thermal Solutions Boiler Controller To Building Automatio

Thermal Solutions Boiler Controller To Building Automatio

Thermal Solutions Boiler Controller To Building Automatio

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Thermal</strong> <strong>Solutions</strong> ProtoNode Startup Guide Page 29 of 32<br />

Appendix B.4. TSBC Modbus RTU Mappings to LonWorks.<br />

Point Name Lon Name Lon SNVT Type<br />

Outdoor Air Reset<br />

Enable/Disable nvoOAResEn_Disbl SNVT_switch<br />

Domestic Hot Water Priority nvoDomHotWtrPri SNVT_switch<br />

Local/Remote nvoLoc_Rem SNVT_switch<br />

Remote On/Off Modbus<br />

Command nvi/nvoRemOnOffMdCmd SNVT_switch<br />

Spare Input (Programmable) nvoSpareInput SNVT_switch<br />

Low Water Cutoff Switch nvoLoWtrCutoffSw SNVT_switch<br />

Burner On/Off Switch nvoBrnrOn_OffSw SNVT_switch<br />

Low Water Flow nvoLoWtrFLo SNVT_switch<br />

High and Low Gas Pressure<br />

Switches nvoHi_LoGasPrsSw SNVT_switch<br />

Operating or High Limit nvoOpOrHiLimit SNVT_switch<br />

Low Combustion Air Flow nvoLoCmbstAirFlo SNVT_switch<br />

Fuel Valve Energized nvoFlVlvEnergizd SNVT_switch<br />

Flame Safeguard Alarm nvoFlmSafegrdAlm SNVT_switch<br />

Call For Heat (CFH) nvoCallForHeat SNVT_switch<br />

General Alarm nvoGeneralAlm SNVT_switch<br />

Vent Inducer nvoVentInducer SNVT_switch<br />

<strong>Boiler</strong> Pump nvoBlrPump SNVT_switch<br />

System Pump nvoSystemPump SNVT_switch<br />

Spare Output (Programmable) nvoSpareOutput SNVT_switch<br />

State <strong>Boiler</strong> Disabled nvoStBlrDisabled SNVT_switch<br />

State Weather Shutdown nvoStWthrShtdwn SNVT_switch<br />

State Lockout nvoStLockout SNVT_switch<br />

State Pump Purge nvoStPumpPurge SNVT_switch<br />

State Limit Hold nvoStLimitHold SNVT_switch<br />

State Purge/Pilot Ign nvoStPrgPilotIgn SNVT_switch<br />

State Low Fire/Ignition nvoStLoFire_Ign SNVT_switch<br />

State Main Ignition nvoStMainIgn SNVT_switch<br />

State Low Fire Hold nvoStLoFireHold SNVT_switch<br />

State <strong>Boiler</strong> Running nvoStBlrRunning SNVT_switch<br />

State Fan Post Purge nvoStFanPostPrg SNVT_switch<br />

State Pump Cool Down nvoStPmpCoolDwn SNVT_switch<br />

State Standby nvoStStandby SNVT_switch<br />

Annunciator Low Water Level nvoAnnLoWtrLvl SNVT_switch<br />

Annunciator Off Switch nvoAnnOffSw SNVT_switch<br />

Annunciator Low Water Flow nvoAnnLoWtrFLo SNVT_switch<br />

Annunciator Fuel Limit nvoAnnFuelLimit SNVT_switch<br />

Annunciator High Temp Limit nvoAnnHiTmpLimit SNVT_switch<br />

Annunciator Low Air Flow nvoAnnLoAirFLo SNVT_switch<br />

Annunciator FSG Lockout nvoAnnFSGLockout SNVT_switch<br />

Annunciator Outlet Temp Fail nvoAnnOtltTmpFl SNVT_switch<br />

Annunciator Inlet Temp Fail nvoAnnInltTmpFl SNVT_switch<br />

Annunciator OA Temp Fail nvoAnnOATmpFail SNVT_switch<br />

Annunciator Remote Temp Fail nvoAnnRemTmpFail SNVT_switch<br />

Annunciator Remote In Fail nvoAnnRemInFail SNVT_switch<br />

Annunciator Comm Fail nvoAnnCommFail SNVT_switch<br />

Annunciator Low Inlet Temp nvoAnnLoInletTmp SNVT_switch<br />

ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com<br />