<strong>Thermal</strong> <strong>Solutions</strong> ProtoNode Startup Guide Page 28 of 32<br />

Operating or High Limit BI 10<br />

Low Combustion Air Flow BI 11<br />

Fuel Valve Energized BI 12<br />

Flame Safeguard Alarm BI 13<br />

Call For Heat (CFH) BI 14<br />

General Alarm BI 15<br />

Vent Inducer BI 16<br />

<strong>Boiler</strong> Pump BI 17<br />

System Pump BI 18<br />

Spare Output (Programmable) BI 19<br />

State <strong>Boiler</strong> Disabled BI 20<br />

State Weather Shutdown BI 21<br />

State Lockout BI 22<br />

State Pump Purge BI 23<br />

State Limit Hold BI 24<br />

State Purge/Pilot Ign BI 25<br />

State Low Fire/Ignition BI 26<br />

State Main Ignition BI 27<br />

State Low Fire Hold BI 28<br />

State <strong>Boiler</strong> Running BI 29<br />

State Fan Post Purge BI 30<br />

State Pump Cool Down BI 31<br />

State Standby BI 32<br />

Annunciator Low Water Level BI 33<br />

Annunciator Off Switch BI 34<br />

Annunciator Low Water Flow BI 35<br />

Annunciator Fuel Limit BI 36<br />

Annunciator High Temp Limit BI 37<br />

Annunciator Low Air Flow BI 38<br />

Annunciator FSG Lockout BI 39<br />

Annunciator Outlet Temp Fail BI 40<br />

Annunciator Inlet Temp Fail BI 41<br />

Annunciator OA Temp Fail BI 42<br />

Annunciator Remote Temp Fail BI 43<br />

Annunciator Remote In Fail BI 44<br />

Annunciator Comm Fail BI 45<br />

Annunciator Low Inlet Temp BI 46<br />

Annunciator Memory Failure BI 47<br />

<strong>Boiler</strong> Outlet Water Temp AI 48<br />

<strong>Boiler</strong> Inlet Water Temp AI 49<br />

Outside Air Temp AI 50<br />

<strong>Boiler</strong> Actual SP AI 51<br />

Remote System Temp AI 52<br />

Remote Firing Rate or Remote SP AV 53<br />

PCB Temp Sensor AI 54<br />

Firing Rate Output to Mod Motor AI 55<br />

Minimum Return Temp SP AI 56<br />

Mixing Valve Output AI 57<br />

Control Mode AI 58<br />

ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com<br />