<strong>Thermal</strong> <strong>Solutions</strong> ProtoNode Start Up guide Page 13 of 32<br />

3.4 Wiring the ProtoNode LER Field Port to a LonWorks network<br />

<br />

Connect the ProtoNode to the field network with the LonWorks terminal using a twisted pair nonshielded<br />

cable. LonWorks has no polarity.<br />

3.5 Power-Up the ProtoNode RER or LER<br />

Apply power to the device. Ensure that the power supply used complies with the specifications provided in<br />

Appendix C.1. Ensure that the cable is grounded using the “Frame-GND” terminal. The ProtoNode is<br />

factory set for 9-30VDC or 12-24 VAC.<br />

Voltage Pinouts<br />

ProtoNode Pin # Pin assignment<br />

Pin 1 RS-485 +<br />

Pin 2 RS-485 -<br />

Pin 3<br />

RS-485 GND<br />

Pin 4 V +<br />

Pin 5 V -<br />

Pin 6<br />

FRAME GND<br />

ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com<br />