<strong>Thermal</strong> <strong>Solutions</strong> ProtoNode Start Up guide Page 11 of 32<br />

3.2.1 Connecting TSBC <strong>Boiler</strong> <strong>Controller</strong>s to the ProtoNode’s RS485<br />

<br />

<br />

<br />

Connect TSBC’s RJ‐11 Pin 1 A (+) Black (RS485+) to ProtoNode’s pin 1 (RS485+) on the Phoenix 6 pin<br />

connector.<br />

Connect TSBC’s RJ‐11 Pin 2 B (‐) Red (RS485‐) to ProtoNode’s pin 2 (RS485‐) on the Phoenix 6 pin<br />

connector.<br />

Ground between TSBC and the ProtoNode does not need to be connected.<br />

ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com<br />

Tel: (408) 964 4444 Fax: (408) 964 4425 <strong>To</strong>ll Free: (800) 317 8319 x141 email: support@protocessor.com