01.07.2015 Views

I&O Manual - ECCS Control System - Categories On Thermal ...

I&O Manual - ECCS Control System - Categories On Thermal ...

I&O Manual - ECCS Control System - Categories On Thermal ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Section 2: Principles of Operation<br />

2.1 SYSTEM DESCRIPTION<br />

The <strong>ECCS</strong> (Electronic <strong>Control</strong>s and Communication<br />

<strong>System</strong>) is a Lead Lag sequencer for modulating and<br />

on/off boilers capable of auto rotation, Outdoor reset,<br />

and communication using a Modbus protocol.<br />

All the control signals between the boiler and the <strong>ECCS</strong><br />

panel are transmitted over a 3 wire shielded cable using<br />

the Modbus protocol. This includes the enable/disable<br />

signal, the modulating signal, and the local/remote<br />

signal.<br />

<strong>System</strong> water temperature is continuously monitored<br />

through the header water temperature sensor. The<br />

system compares this temperature to the setpoint which<br />

is fixed or generated from the outdoor reset curve. If<br />

the system water temperature falls below the adjustable<br />

system ON POINT set on the screen (refer to Figure<br />

5.3) the lead boiler will turn on via a signal from the<br />

<strong>ECCS</strong> system. For a modulating boiler, The PID<br />

control will generate a signal and send it to the boilers<br />

via the MODBUS. If the firing rate goes above the<br />

START TRIGGER Point set on the screen for the<br />

amount of time set in the START DELAY, the first lag<br />

boiler will start. <strong>On</strong>ce the lag boiler starts it will drive<br />

to the same firing rate as the lead boiler. Both boilers<br />

will fire in tandem, at the same firing rate. Additional<br />

lag boilers will start by the same criteria in the order<br />

that set as the LEAD LAG SEQUENCE. Boilers will<br />

be shed in the reverse order of which they came on<br />

(AKA: First <strong>On</strong>, Last Off). As load is shed the boilers<br />

will use the STOP TRIGGER point and the STOP<br />

DELAY parameters set on the screen.<br />

For <strong>On</strong>/Off boilers, additional boilers will be added<br />

when the system water temperature drops below the<br />

system ON POINT for the time set in the boiler START<br />

DELAY. Boilers will be shed in reverse order using<br />

the OFF POINT and STOP DELAY parameters.<br />

The Lead Lag (LL) system will be capable of running a<br />

maximum number of 6 boilers. Parameters in the<br />

temperature controller and flame safeguard are<br />

transmitted via the Modbus connection to the PLC and<br />

Touch screen.<br />

2.2 LEAD LAG<br />

2.2.1. In a Lead Lag (LL) system (refer to Figure 5.4),<br />

one boiler is designated as a lead boiler. The lead<br />

boiler will always be the first boiler to come on and the<br />

last boiler to shut off. The lag boilers will always<br />

come on after the lead in order of their number. The<br />

first lag (lag#1) will always be the second boiler to<br />

come on, the second lag (lag#2) will always be the<br />

third to come on, etc. They will turn off in reverse<br />

order.<br />

6<br />

2.2.2. There is a sequence preprogrammed from the<br />

factory as a default of: Lead = boiler 1, Lag #1 =<br />

boiler 2, Lag #2 = boiler 3, etc., in sequential order.<br />

Sequence can be changed to any order that is<br />

desired. Numbers cannot be duplicated or out of<br />

range.<br />

2.2.3. To change the lead lag sequence go to the<br />

SEQUENCE AND ROTATION SCREEN<br />

(Figure 5.5). From the main screen press the system<br />

setup button, then the Enter Lead Lag Sequence<br />

button.<br />

2.2.4. The system will turn on the lead boiler when the<br />

temperature drops below the <strong>System</strong> ON POINT. The<br />

boiler will turn the lead off only if it is the only<br />

boiler running and the temperature is above the<br />

<strong>System</strong> OFF POINT.<br />

The <strong>ECCS</strong> system turns on additional boilers when the<br />

firing rate of the lead boiler rises above the START<br />

TRIGGER (See Figure 5.4: Lead Lag Trigger Setup<br />

Screen) point for the length of time in the BOILER<br />

START DELAY box. The START TRIGGER is the<br />

percentage of the firing rate that a modulating boiler<br />

must reach in order to start the delay timer. <strong>On</strong>ce the<br />

delay timer finishes timing, the next boiler in the<br />

sequence will start. If the firing rate drops below the<br />

START TRIGGER before the timer is complete, the<br />

timer will reset.<br />

ON/OFF boilers will sequence in accordance with the<br />

<strong>System</strong> ON and OFF POINTS. See Figure 5.4 under<br />

Setpoint differential.<br />

2.3. UNAVAILABLE BOILERS<br />

2.3.1. If a boiler is unavailable for any one of the<br />

following reasons the LL sequence will remove them<br />

and adjust the sequence until they become available<br />

again. The purpose of this is to save time between<br />

stages if there is an unavailable boiler. If the<br />

desired lead boiler is unavailable, Lag #1 will<br />

become the lead and other boilers will shift<br />

accordingly. The program will rotate based on the<br />

sequence that has been entered onto the screen.<br />

Flame fail – If the boiler has a flame failure the boiler<br />

will be removed from the LL sequence until the unit<br />

has been reset.<br />

Boiler in Local mode – If the Local/Remote switch is<br />

in Local the boiler will be removed from the LL<br />

sequence until the unit has been placed back in<br />

Remote.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!