Parameter Limits and Factory Defaults<br />

Initial Setup<br />

Parameter<br />

Range<br />

Factory Setting<br />

Password<br />

Level<br />

Total<br />

Boilers<br />

2 - 6<br />

3 5 25<br />

Boiler<br />

Type, Mod or <strong>On</strong>/Off<br />

1 - 2<br />

1 5 25<br />

Proportional<br />

0 - 25<br />

25<br />

5 25<br />

Integral<br />

0 - 2<br />

1 5 25<br />

Derivative<br />

0 - 1<br />

0 5 25<br />

Start<br />

Trigger (% of firing rate)<br />

50<br />

- 100<br />

90<br />

2 21<br />

Stop<br />

Trigger (% of firing rate)<br />

1 - 50<br />

25<br />

2 21<br />

<strong>On</strong> Point (degrees below setpoint) 1 - 15<br />

5 2 21<br />

Off<br />

Point (degrees above setpoint) 1 - 15<br />

5 2 21<br />

Start<br />

Time Delay (seconds)<br />

90<br />

- 900<br />

120<br />

2 21<br />

Stop<br />

Time Delay (seconds)<br />

0 - 1200<br />

120<br />

2 21<br />

Setpoint<br />

(degrees Fahrenheit)<br />

140<br />

- 230<br />

180<br />

1 20<br />

DHW Priority<br />

140<br />

- 230<br />

180<br />

1 20<br />

Local/Remote<br />

Switch<br />

Local/Remote<br />

Page<br />

Local<br />

0 23<br />

Rotation Time (hrs)<br />

8 - 720<br />

24<br />

2 22<br />

Rotation Enable/Disable<br />

<strong>On</strong>-Of<br />

f<br />

Off<br />

2 22<br />

Customer<br />

Setting<br />

Change Sequence<br />

Lead<br />

Lag<br />

Lag<br />

Lag<br />

Lag<br />

Lag<br />

#1<br />

#2<br />

#3<br />

#4<br />

#5<br />

1 - total blr<br />

1 2 22<br />

1 - total blr<br />

2 2 22<br />

1 - total blr<br />

3 2 22<br />

1 - total blr<br />

4 2 22<br />

1 - total blr<br />

5 2 22<br />

1 - total blr<br />

6 2 22<br />

Change<br />

Sequence Button<br />

2 22<br />

Enter<br />

Lead/Lag Sequence<br />

2 22<br />

Outdoor Reset & WWSD<br />

Low Air Temp<br />

-60<br />

- 50<br />

10<br />

3 23<br />

High Water Temp<br />

150<br />

- 240<br />

180<br />

3 23<br />

High Air Temp<br />

50<br />

- 120<br />

55<br />

3 23<br />

Low Water Temp<br />

140<br />

- 180<br />

140<br />

3 23<br />

WWSD <strong>System</strong> Pumps <strong>On</strong>/Off<br />

0 - 1<br />

0 3 25<br />

WWSD Boilers <strong>On</strong>/Off<br />

0 - 1<br />

0 3 25<br />

WWSD Enable/Disable<br />

Outdoor<br />

Switch<br />

Reset Enable/Dis Switch<br />

<strong>On</strong> - Off<br />

<strong>On</strong> - Off<br />

Off<br />

3 25<br />

Off<br />

2 23<br />