Section 6: Trouble Shooting Guide<br />
PROBLEM<br />
No boilers running<br />
Temperature<br />
OFF POINT.<br />
POSSIBLE CAUSE<br />
of water higher than the<br />
Boilers in local mode and boiler water<br />
temperature is above OFF POINT.<br />
POSSIBLE REMEDY<br />
Boilers will come on automatically when system<br />
water temperature drops below ON POINT.<br />
Switch to remote or wait for temperature to drop<br />
below ON POINT.<br />
B reaker in <strong>ECCS</strong> Panel in OFF or tripped. Turn on breaker in <strong>ECCS</strong> Panel.<br />
Touch Screen is not lit<br />
Power feeding <strong>ECCS</strong> Panel is OFF or<br />
tripped.<br />
Improper power supply to panel.<br />
Power<br />
to screen is not connected.<br />
Improper power supply to screen.<br />
Turn on breaker feeding <strong>ECCS</strong> Panel.<br />
Check power voltage and correct as needed.<br />
Panel requires 120VAC wired to 4 amp circuit<br />
breaker inside panel.<br />
Check wiring and correct as needed, 24VDC<br />
Screen uses 24VDC from PLC. Check voltage<br />
and correct if needed.<br />
B ad touch screen.<br />
Replace screen.<br />
No data being<br />
displayed on screen<br />
and no communication<br />
error or data on<br />
screen is not updating<br />
Modbus communication wires shorted<br />
together on any temperature controller or<br />
flame safeguard.<br />
Check Modbus wires A & B on all controllers for<br />
location where wires are touching each other<br />
and separate.<br />
P LC not in run mode.<br />
Flip switch on front of PLC to run position.<br />
P ower off to boiler.<br />
Turn power on to boiler.<br />
Alarm "Boiler #<br />
Communication<br />
Failure"<br />
Alarm "Boiler # Main<br />
Flame Failure"<br />
Modbus wiring disconnected on boiler<br />
showing alarm.<br />
Shield on wire not grounded properly.<br />
Baud rate setting on Fireye or Honeywell<br />
controller is wrong.<br />
Incorrect baud rate set on temperature<br />
controller.<br />
Modbus wiring A, B, C is not consistent<br />
throughout boiler devices.<br />
Boiler address not correct on flame<br />
safeguard or temperature controller.<br />
Boiler has faulted on a flame failure while<br />
in run mode.<br />
Connect Modbus wiring (3 wire shielded cable)<br />
to terminals A, B, C on devices.<br />
Shield should be grounded on one end of<br />
daisy chain only (panel end). Shields at wire<br />
junctions should be tied together.<br />
Set baud rate to 19,200.<br />
Configuration parameter check C113. Second<br />
value from right shall be a 6. Adjust as needed.<br />
Insure same wire is daisy chained to all A<br />
terminals, B to B terminals, and C to C<br />
terminals.<br />
Check appendix for correct setting on Modbus<br />
devices. See Section 4.<br />
Check controller manual. Reset flame<br />
safeguard controller.<br />
Alarm "Boiler # Pilot<br />
Flame Failure"<br />
Alarm "Boiler #<br />
Airflow Switch"<br />
B oiler has faulted while lighting pilot. Refer to boiler manual troubleshooting guide.<br />
F an did not energize.<br />
Refer to boiler manual troubleshooting guide.<br />
A ir flow switch set wrong or not working. Adjust or replace switch.<br />
F an running too slow.<br />
Check VFD to determine cause and correct.<br />
28