Section 6: Trouble Shooting Guide<br />

PROBLEM<br />

No boilers running<br />

Temperature<br />

OFF POINT.<br />

POSSIBLE CAUSE<br />

of water higher than the<br />

Boilers in local mode and boiler water<br />

temperature is above OFF POINT.<br />

POSSIBLE REMEDY<br />

Boilers will come on automatically when system<br />

water temperature drops below ON POINT.<br />

Switch to remote or wait for temperature to drop<br />

below ON POINT.<br />

B reaker in <strong>ECCS</strong> Panel in OFF or tripped. Turn on breaker in <strong>ECCS</strong> Panel.<br />

Touch Screen is not lit<br />

Power feeding <strong>ECCS</strong> Panel is OFF or<br />

tripped.<br />

Improper power supply to panel.<br />

Power<br />

to screen is not connected.<br />

Improper power supply to screen.<br />

Turn on breaker feeding <strong>ECCS</strong> Panel.<br />

Check power voltage and correct as needed.<br />

Panel requires 120VAC wired to 4 amp circuit<br />

breaker inside panel.<br />

Check wiring and correct as needed, 24VDC<br />

Screen uses 24VDC from PLC. Check voltage<br />

and correct if needed.<br />

B ad touch screen.<br />

Replace screen.<br />

No data being<br />

displayed on screen<br />

and no communication<br />

error or data on<br />

screen is not updating<br />

Modbus communication wires shorted<br />

together on any temperature controller or<br />

flame safeguard.<br />

Check Modbus wires A & B on all controllers for<br />

location where wires are touching each other<br />

and separate.<br />

P LC not in run mode.<br />

Flip switch on front of PLC to run position.<br />

P ower off to boiler.<br />

Turn power on to boiler.<br />

Alarm "Boiler #<br />

Communication<br />

Failure"<br />

Alarm "Boiler # Main<br />

Flame Failure"<br />

Modbus wiring disconnected on boiler<br />

showing alarm.<br />

Shield on wire not grounded properly.<br />

Baud rate setting on Fireye or Honeywell<br />

controller is wrong.<br />

Incorrect baud rate set on temperature<br />

controller.<br />

Modbus wiring A, B, C is not consistent<br />

throughout boiler devices.<br />

Boiler address not correct on flame<br />

safeguard or temperature controller.<br />

Boiler has faulted on a flame failure while<br />

in run mode.<br />

Connect Modbus wiring (3 wire shielded cable)<br />

to terminals A, B, C on devices.<br />

Shield should be grounded on one end of<br />

daisy chain only (panel end). Shields at wire<br />

junctions should be tied together.<br />

Set baud rate to 19,200.<br />

Configuration parameter check C113. Second<br />

value from right shall be a 6. Adjust as needed.<br />

Insure same wire is daisy chained to all A<br />

terminals, B to B terminals, and C to C<br />

terminals.<br />

Check appendix for correct setting on Modbus<br />

devices. See Section 4.<br />

Check controller manual. Reset flame<br />

safeguard controller.<br />

Alarm "Boiler # Pilot<br />

Flame Failure"<br />

Alarm "Boiler #<br />

Airflow Switch"<br />

B oiler has faulted while lighting pilot. Refer to boiler manual troubleshooting guide.<br />

F an did not energize.<br />

Refer to boiler manual troubleshooting guide.<br />

A ir flow switch set wrong or not working. Adjust or replace switch.<br />

F an running too slow.<br />

Check VFD to determine cause and correct.<br />