Outdoor Reset Switch.<br />
Press and drag toggle<br />
switch from OFF to ON.<br />
The setpoint will now<br />
be generated by the<br />
curve entered above.<br />
Entering temperatures in these 4 input<br />
boxes will generate a linear curve in<br />
which a setpoint based on outdoor air<br />
temperature will be generated.<br />
This is the setpoint which<br />
is generated based on the<br />
outdoor air curve entered<br />
and the outdoor air<br />
temperature.<br />
Pressing this button will<br />
go to the screen to set<br />
up the Warm Weather<br />
Shutdown Options.<br />
CAUTION<br />
This system cannot protect the boiler from cold water returning back to the boiler as is the case<br />
when coming out of a warm weather shutdown scenario. In order to protect the boiler from<br />
condensing, a primary/secondary piping arrangement or mixing valve must be installed in the<br />
piping.<br />
Figure 5.6: Outdoor Reset Setup Screen<br />
This is the setpoint of the boiler water at the outlet of<br />
the boiler. When in local the boiler will use this as its<br />
operating setpoint.<br />
The values for Setpoint,<br />
<strong>On</strong> point and Off point are<br />
for display only and come<br />
directly from the boiler<br />
temperature controller via<br />
a Modbus connection.<br />
These values come<br />
directly from the Flame<br />
Safeguard via a Modbus<br />
connection.<br />
Pressing and dragging this<br />
switch with your finger will<br />
change control from local to<br />
remote operation.<br />
Figure 5.7: Boiler Parameters Screen<br />
23