I&O Manual - ECCS Control System - Categories On Thermal ...
I&O Manual - ECCS Control System - Categories On Thermal ...
I&O Manual - ECCS Control System - Categories On Thermal ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SETTING THE TRIGGERS AND THE START /STOP TIME DELAYS FOR THE LEAD LAG SYSTEM<br />
The value entered in this box will be subtracted from the setpoint to create<br />
the boiler <strong>On</strong> point. This <strong>On</strong> point has two separate functions–<br />
1)If the system has ON/OFF boilers, it will use the ON POINT as a trigger<br />
to turn on the next boiler.<br />
2)If the system is using modulating boilers only the lead boiler will use<br />
the on point to turn on.<br />
0% of firing rate =<br />
low fire<br />
100% of firing rate<br />
= high fire<br />
Input box. Firing rate of<br />
the running boiler<br />
which when reached<br />
will start the timer to<br />
start the next boiler in<br />
sequence. The limits of<br />
this value are between<br />
50 and 100.<br />
Input box. Firing<br />
rate of the running<br />
boiler which when<br />
reached will start<br />
the timer to stop the<br />
last boiler in the<br />
sequence. The<br />
limits of this value<br />
are 0 - 50.<br />
Adjustable start time<br />
delay which delays<br />
the starting of the next<br />
boiler in the sequence<br />
once the start trigger<br />
is made. The limits of<br />
this value are 90-900.<br />
Adjustable stop time<br />
delay which delays<br />
the stopping of the last<br />
running boiler in the<br />
sequence once the stop<br />
trigger is made. The<br />
limits of this value are<br />
0-1200.<br />
Figure 5.4: Lead Lag Trigger Setup Screen<br />
The value entered in this<br />
box will be added to the<br />
setpoint to create the<br />
boiler Off point. This<br />
Offpoint has two separate<br />
functions–<br />
1)If the system has<br />
ON/OFF boilers, it<br />
will use the Off point<br />
as a trigger to turn<br />
off the last running<br />
boiler.<br />
2)If the system is using<br />
modulating boilers<br />
only the lead boiler<br />
will use the the Off<br />
point to turn off.<br />
Example, using the values above (Modulating boilers) :<br />
Boiler 1 is on and reaches 90% of firing rate. The firing rate<br />
will have to stay above 90% for 120 sec for the next boiler<br />
in the sequence to start. If it drops below 90% before the 120<br />
second time delay is complete, the timer will reset.<br />
Example (<strong>On</strong>/Off boilers) : Assume a setpoint of 180 °F.<br />
The <strong>On</strong> and Off points are programmed on the screen at 5<br />
and 5. Therefore the boilers will turn on a 175 °F and off at<br />
185 °F. The boilers have a differential of 10°F.<br />
Boiler 1 is on and the temp at the system water temperature<br />
sensor drops below 175 °F for 120 sec., the next boiler in the<br />
sequence will start. If the system water temperature rises to<br />
175 °F before the time is complete, the timer will reset.<br />
21