Section 4: Setting the Modbus Addresses<br />

4.1 COMMUNICATION SETUP FOR BOILERS<br />

Each Modbus device in each boiler must be addressed to<br />

properly communicate with the <strong>ECCS</strong> system. The<br />

Temperature <strong>Control</strong>ler must be addressed through the<br />

configuration level and the flame safeguard will be<br />

addressed according to the following instructions. Refer to<br />

Appendix A, system wiring, or individual component<br />

manuals.<br />

4.2 SETTING THE ADDRESS OF THE HONEYWELL<br />

MODBUS MODULE<br />

Addressing for the HW Modbus Module correlates to the<br />

Temp <strong>Control</strong>lers Modbus addressing on the same unit.<br />

There are 2 dials on the bottom of the module that need to<br />

be set and a jumper that needs to be removed. Refer to<br />

Figure 4.1: Honeywell S7810M Modbus Module Mounting<br />

and 4.2: S7810M Address Switches and Baud Rate Jumper.<br />

4.3 SETTING THE MODBUS ADDRESS OF THE<br />

FIREYE MICRO M<br />

Addressing for the Fireye correlates to the Temperature<br />

<strong>Control</strong>lers Modbus addressing on the same unit. Refer to<br />

MicroM manual for instructions.<br />

Fireye MicroM<br />

Fireye<br />

Temperature Parameter<br />

<strong>Control</strong>ler Baud Rate @<br />

(C113)<br />

19,200<br />

Unit Address<br />

Boiler<br />

1 0160<br />

11<br />

Boiler<br />

2 0260<br />

12<br />

Boiler<br />

3 0360<br />

13<br />

Boiler<br />

4 0460<br />

14<br />

Boiler<br />

5 0560<br />

15<br />

Boiler<br />

6 0660<br />

16<br />

Honeywell<br />

Temperature<br />

<strong>Control</strong>ler<br />

(C113)<br />

S7810M<br />

Modbus<br />

Module<br />

Baud Rate @<br />

19,200<br />

remove<br />

jumper<br />

10"s<br />

Dial<br />

1"s<br />

Dial<br />

Boiler<br />

1<br />

0160<br />

1 1<br />

Boiler<br />

2<br />

0260<br />

1 2<br />

Boiler<br />

3<br />

0360<br />

1 3<br />

Boiler<br />

4<br />

0460<br />

1 4<br />

Boiler<br />

5<br />

0560<br />

1 5<br />

Boiler<br />

6<br />

0660<br />

1 6<br />

16