01.07.2015 Views

I&O Manual - ECCS Control System - Categories On Thermal ...

I&O Manual - ECCS Control System - Categories On Thermal ...

I&O Manual - ECCS Control System - Categories On Thermal ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

INSTALLATION, OPERATING AND<br />

SERVICE INSTRUCTIONS<br />

<strong>ECCS</strong> CONTROL SYSTEM<br />

ON/OFF & MODULATION<br />

Price - $3.00<br />

For service and repairs to the heating plant, or this panel call your heating contractor. When seeking<br />

information from the manufacturer, provide boiler model and serial number as shown on rating label.<br />

<strong>ECCS</strong> <strong>Control</strong><br />

<strong>System</strong><br />

Serial<br />

Number<br />

Type <strong>System</strong><br />

Heating Contractor<br />

Address<br />

Phone Number<br />

Your Local <strong>Thermal</strong> Solutions Representative:<br />

81456003R2-12/05


IMPORTANT INFORMATION - READ CAREFULLY<br />

NOTE: The equipment shall be installed in accordance with those installation regulations required in the area where the<br />

installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction<br />

shall be consulted before installations are made.<br />

All wiring on boilers installed in the USA shall be in accordance with the National Electrical Code and/or local regulations.<br />

All wiring on boilers installed in Canada shall be in accordance with the Canadian Electrical Code and/or local regulations.<br />

The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to<br />

important information concerning product life.<br />

DANGER<br />

Indicates an imminently hazardous situation<br />

which, if not avoided, will result in death,<br />

serious injury or substantial property<br />

damage.<br />

CAUTION<br />

Indicates a potentially hazardous situation<br />

which, if not avoided, may result in<br />

moderate or minor injury or property<br />

damage.<br />

WARNING<br />

Indicates a potentially hazardous situation<br />

which, if not avoided, could result in death,<br />

serious injury or substantial property<br />

damage.<br />

NOTICE<br />

Indicates special instructions on<br />

installation, operation, or maintenance<br />

which are important but not related to<br />

personal injury hazards.<br />

2


Parameter Limits and Factory Defaults<br />

Initial Setup<br />

Parameter<br />

Range<br />

Factory Setting<br />

Password<br />

Level<br />

Total<br />

Boilers<br />

2 - 6<br />

3 5 25<br />

Boiler<br />

Type, Mod or <strong>On</strong>/Off<br />

1 - 2<br />

1 5 25<br />

Proportional<br />

0 - 25<br />

25<br />

5 25<br />

Integral<br />

0 - 2<br />

1 5 25<br />

Derivative<br />

0 - 1<br />

0 5 25<br />

Start<br />

Trigger (% of firing rate)<br />

50<br />

- 100<br />

90<br />

2 21<br />

Stop<br />

Trigger (% of firing rate)<br />

1 - 50<br />

25<br />

2 21<br />

<strong>On</strong> Point (degrees below setpoint) 1 - 15<br />

5 2 21<br />

Off<br />

Point (degrees above setpoint) 1 - 15<br />

5 2 21<br />

Start<br />

Time Delay (seconds)<br />

90<br />

- 900<br />

120<br />

2 21<br />

Stop<br />

Time Delay (seconds)<br />

0 - 1200<br />

120<br />

2 21<br />

Setpoint<br />

(degrees Fahrenheit)<br />

140<br />

- 230<br />

180<br />

1 20<br />

DHW Priority<br />

140<br />

- 230<br />

180<br />

1 20<br />

Local/Remote<br />

Switch<br />

Local/Remote<br />

Page<br />

Local<br />

0 23<br />

Rotation Time (hrs)<br />

8 - 720<br />

24<br />

2 22<br />

Rotation Enable/Disable<br />

<strong>On</strong>-Of<br />

f<br />

Off<br />

2 22<br />

Customer<br />

Setting<br />

Change Sequence<br />

Lead<br />

Lag<br />

Lag<br />

Lag<br />

Lag<br />

Lag<br />

#1<br />

#2<br />

#3<br />

#4<br />

#5<br />

1 - total blr<br />

1 2 22<br />

1 - total blr<br />

2 2 22<br />

1 - total blr<br />

3 2 22<br />

1 - total blr<br />

4 2 22<br />

1 - total blr<br />

5 2 22<br />

1 - total blr<br />

6 2 22<br />

Change<br />

Sequence Button<br />

2 22<br />

Enter<br />

Lead/Lag Sequence<br />

2 22<br />

Outdoor Reset & WWSD<br />

Low Air Temp<br />

-60<br />

- 50<br />

10<br />

3 23<br />

High Water Temp<br />

150<br />

- 240<br />

180<br />

3 23<br />

High Air Temp<br />

50<br />

- 120<br />

55<br />

3 23<br />

Low Water Temp<br />

140<br />

- 180<br />

140<br />

3 23<br />

WWSD <strong>System</strong> Pumps <strong>On</strong>/Off<br />

0 - 1<br />

0 3 25<br />

WWSD Boilers <strong>On</strong>/Off<br />

0 - 1<br />

0 3 25<br />

WWSD Enable/Disable<br />

Outdoor<br />

Switch<br />

Reset Enable/Dis Switch<br />

<strong>On</strong> - Off<br />

<strong>On</strong> - Off<br />

Off<br />

3 25<br />

Off<br />

2 23<br />

3


Table of Contents<br />

i. Programmable Ranges.................................................... 3<br />

Section 1. Component Description .................................... 5<br />

Section 2. Principles of Operation ..................................... 6<br />

2.1. <strong>System</strong> Description<br />

2.2. Lead Lag<br />

2.3. Unavailable Boilers<br />

2.4. Auto Rotate .................................................. 7<br />

2.5. Outdoor Reset<br />

2.6. Warm Weather Shutdown & Enable/Disable<br />

2.7. Modbus Communication<br />

2.8. Trending<br />

2.9. Local/Remote Operation<br />

2.10 Domestic Hot Water Priority............................. 8<br />

2.11 Alarms<br />

Section 3. Installation.......................................................... 9<br />

3.1.Unpacking ....................................................... 9<br />

3.1.1. Inspection<br />

3.2. Mounting ....................................................... 9<br />

3.2.1. Panel<br />

3.2.2. <strong>System</strong> Water Temp Sensor<br />

3.2.3. Outdoor Air Temp Sensor<br />

Figure 3.1: Panel Mounting Layout .... 10<br />

3.3. Electrical ....................................................... 11<br />

3.3.1. General<br />

3.3.2. Wiring Power Supply to Panel<br />

3.3.3. Wiring Panel to Boilers<br />

3.3.4. Wiring Panel to Sensors<br />

Figure 3.2: Panel Layout ............................ 12<br />

Figure 3.3: <strong>System</strong> Wiring .......................... 13<br />

Figure 3.4: <strong>ECCS</strong> Panel Wiring ................... 14<br />

Figure 3.5: Boiler Wiring Diagram .............. 15<br />

Section 5. Touch Screen Programming .............................. 19<br />

5.1. Screen Description ....................................... 19<br />

5.2. General Guidelines for Using the<br />

Touchscreen ................................................. 19<br />

Figure 5.1 Touch Screen Login .................. 19<br />

Figure 5.2 Main Screen .............................. 20<br />

Figure 5.3 <strong>System</strong> Setup Screen................. 20<br />

Figure 5.4 Lead Lag Trigger Setup Screen . 21<br />

Figure 5.5 Sequence and Rotation Screen . 22<br />

Figure 5.6 Outdoor Reset Setup Screen ..... 23<br />

Figure 5.7 Boiler Parameters Screen ........... 23<br />

Figure 5.8 Alarm History Screen ................ 24<br />

Figure 5.9 Alarm Pop Up Screen ................ 24<br />

Figure 5.10 Warm Weather Shutdown<br />

Screen ....................................... 25<br />

Figure 5.11 Initial Setup Screen ................. 25<br />

Figure 5.12 Trend Screen ........................... 26<br />

Figure 5.13 Trend Screen Zoom <strong>Control</strong> .... 26<br />

Figure 5.14 Time/Date Screen ...................... 27<br />

Section 6. Troubleshooting Guide .................................... 28<br />

Section 7. Appendix ......................................................... 30<br />

7.A. Temperature <strong>Control</strong>ler Operation for<br />

Modulating Boilers (Modbus) ....................... 30<br />

7.1. Description ................................................... 30<br />

7.2. Setup ............................................................ 30<br />

7.3. Modbus Version Used on Boilers<br />

<strong>Control</strong>led by the <strong>ECCS</strong> <strong>System</strong> ..................... 30<br />

Figure 7.1 Process Data ............................. 30<br />

7.4. Adjustments ................................................. 31<br />

7.5. <strong>System</strong> Specifications .................................. 31<br />

Section 4. Setting the Modbus Module Address ............. 16<br />

4.1. Communication Setup for Boilers ................. 16<br />

4.2. Setting the Address of the Honeywell<br />

Modbus Module .......................................... 16<br />

4.3. Setting the Modbus Address of the Fireye<br />

Micro M ........................................................ 16<br />

Figure 4.1: Honeywell S7810M Modubus<br />

Module Mounting ..................................... 17<br />

Figure 4.2: S7810M Address Switches and<br />

Baud Rate Jumper ...................................... 18<br />

4


Section 1: Component Description<br />

COMPONENT DESCRIPTION Part #<br />

1) <strong>ECCS</strong> <strong>Control</strong> Panel– houses the touch screen, PLC, analog input/output card, and terminal strips. ...................... 60156400<br />

Built to UL 508A Standard. Refer to Figure 2, Panel Layout<br />

2) <strong>System</strong> water temperature sensor with Thermowell .................................................................................................. 80160721<br />

RTD Pt 1000<br />

3) Outdoor air temperature sensor ................................................................................................................................. 80160722<br />

RTD Pt. 1000<br />

4) Touch Screen ............................................................................................................................................................. 80160912<br />

5.7” monochromatic<br />

5) PLC 226XM 120Vac in, 24 Vac out ......................................................................................................................... 80160910<br />

24 Inputs<br />

16 Outputs<br />

6) RTD Module ............................................................................................................................................................. 80160917<br />

2 RTD Inputs<br />

7) Analog Input Module ............................................................................................................................................................... 80160911<br />

4 (4-20 ma or 0-10 Vsignal inputs)<br />

1 (output)<br />

8) PLC Memory Cartridge ............................................................................................................................................................. 80160925<br />

9) PLC Battery Cartridge ............................................................................................................................................................... 80160924<br />

Components in the boiler that interface with the <strong>ECCS</strong> panel.<br />

10) Modbus version of the boiler temperature controller ................................................................................................ 80160908<br />

11) Honeywell Modbus Module for the Flamesafeguard. ............................................................................................... 80160909<br />

5


Section 2: Principles of Operation<br />

2.1 SYSTEM DESCRIPTION<br />

The <strong>ECCS</strong> (Electronic <strong>Control</strong>s and Communication<br />

<strong>System</strong>) is a Lead Lag sequencer for modulating and<br />

on/off boilers capable of auto rotation, Outdoor reset,<br />

and communication using a Modbus protocol.<br />

All the control signals between the boiler and the <strong>ECCS</strong><br />

panel are transmitted over a 3 wire shielded cable using<br />

the Modbus protocol. This includes the enable/disable<br />

signal, the modulating signal, and the local/remote<br />

signal.<br />

<strong>System</strong> water temperature is continuously monitored<br />

through the header water temperature sensor. The<br />

system compares this temperature to the setpoint which<br />

is fixed or generated from the outdoor reset curve. If<br />

the system water temperature falls below the adjustable<br />

system ON POINT set on the screen (refer to Figure<br />

5.3) the lead boiler will turn on via a signal from the<br />

<strong>ECCS</strong> system. For a modulating boiler, The PID<br />

control will generate a signal and send it to the boilers<br />

via the MODBUS. If the firing rate goes above the<br />

START TRIGGER Point set on the screen for the<br />

amount of time set in the START DELAY, the first lag<br />

boiler will start. <strong>On</strong>ce the lag boiler starts it will drive<br />

to the same firing rate as the lead boiler. Both boilers<br />

will fire in tandem, at the same firing rate. Additional<br />

lag boilers will start by the same criteria in the order<br />

that set as the LEAD LAG SEQUENCE. Boilers will<br />

be shed in the reverse order of which they came on<br />

(AKA: First <strong>On</strong>, Last Off). As load is shed the boilers<br />

will use the STOP TRIGGER point and the STOP<br />

DELAY parameters set on the screen.<br />

For <strong>On</strong>/Off boilers, additional boilers will be added<br />

when the system water temperature drops below the<br />

system ON POINT for the time set in the boiler START<br />

DELAY. Boilers will be shed in reverse order using<br />

the OFF POINT and STOP DELAY parameters.<br />

The Lead Lag (LL) system will be capable of running a<br />

maximum number of 6 boilers. Parameters in the<br />

temperature controller and flame safeguard are<br />

transmitted via the Modbus connection to the PLC and<br />

Touch screen.<br />

2.2 LEAD LAG<br />

2.2.1. In a Lead Lag (LL) system (refer to Figure 5.4),<br />

one boiler is designated as a lead boiler. The lead<br />

boiler will always be the first boiler to come on and the<br />

last boiler to shut off. The lag boilers will always<br />

come on after the lead in order of their number. The<br />

first lag (lag#1) will always be the second boiler to<br />

come on, the second lag (lag#2) will always be the<br />

third to come on, etc. They will turn off in reverse<br />

order.<br />

6<br />

2.2.2. There is a sequence preprogrammed from the<br />

factory as a default of: Lead = boiler 1, Lag #1 =<br />

boiler 2, Lag #2 = boiler 3, etc., in sequential order.<br />

Sequence can be changed to any order that is<br />

desired. Numbers cannot be duplicated or out of<br />

range.<br />

2.2.3. To change the lead lag sequence go to the<br />

SEQUENCE AND ROTATION SCREEN<br />

(Figure 5.5). From the main screen press the system<br />

setup button, then the Enter Lead Lag Sequence<br />

button.<br />

2.2.4. The system will turn on the lead boiler when the<br />

temperature drops below the <strong>System</strong> ON POINT. The<br />

boiler will turn the lead off only if it is the only<br />

boiler running and the temperature is above the<br />

<strong>System</strong> OFF POINT.<br />

The <strong>ECCS</strong> system turns on additional boilers when the<br />

firing rate of the lead boiler rises above the START<br />

TRIGGER (See Figure 5.4: Lead Lag Trigger Setup<br />

Screen) point for the length of time in the BOILER<br />

START DELAY box. The START TRIGGER is the<br />

percentage of the firing rate that a modulating boiler<br />

must reach in order to start the delay timer. <strong>On</strong>ce the<br />

delay timer finishes timing, the next boiler in the<br />

sequence will start. If the firing rate drops below the<br />

START TRIGGER before the timer is complete, the<br />

timer will reset.<br />

ON/OFF boilers will sequence in accordance with the<br />

<strong>System</strong> ON and OFF POINTS. See Figure 5.4 under<br />

Setpoint differential.<br />

2.3. UNAVAILABLE BOILERS<br />

2.3.1. If a boiler is unavailable for any one of the<br />

following reasons the LL sequence will remove them<br />

and adjust the sequence until they become available<br />

again. The purpose of this is to save time between<br />

stages if there is an unavailable boiler. If the<br />

desired lead boiler is unavailable, Lag #1 will<br />

become the lead and other boilers will shift<br />

accordingly. The program will rotate based on the<br />

sequence that has been entered onto the screen.<br />

Flame fail – If the boiler has a flame failure the boiler<br />

will be removed from the LL sequence until the unit<br />

has been reset.<br />

Boiler in Local mode – If the Local/Remote switch is<br />

in Local the boiler will be removed from the LL<br />

sequence until the unit has been placed back in<br />

Remote.


2.3.3. When a boiler becomes available again (fault<br />

cleared, switch from local to remote, etc.) the system<br />

will put it back in the sequence. If the desired lead<br />

becomes available it will start immediately and may<br />

shut down the last boiler running in the sequence<br />

depending on how many boilers are required.( EX: In a<br />

3 boiler system, if 2 boilers are running and only 2 are<br />

required when the lead comes back in service it will<br />

shut down the last lag boiler. If 2 are running and 3 are<br />

required it will not shut down the last lag boiler.)<br />

2.4 AUTO ROTATE<br />

When this function is selected by pressing the Auto<br />

Rotate button (refer to Figure 5.5) the sequence will<br />

automatically rotate based on how long the lead boiler<br />

runs. The rotation time will be set by the operator.<br />

After rotation time is reached, the Lead boiler will move<br />

to the end of the sequence and the second boiler will<br />

become the lead.<br />

When the rotation time is reached, the next boiler in the<br />

sequence will start. After the unit is running for a few<br />

minutes the sequence will rotate, dropping out the old<br />

lead boiler. This will insure the same amount of boilers<br />

are running before and after rotation occurs.<br />

If the sequence is changed manually, the rotation timer<br />

will start from the beginning.<br />

2.5 OUTDOOR RESET<br />

The outdoor reset function (refer to Figure 5.6)<br />

generates a setpoint based on a curve programmed on<br />

the screen and the outdoor air temperature. Two points<br />

are entered and a linear curve is generated.<br />

An RTD temperature sensor will send a signal to the<br />

RTD module for the PLC.<br />

If outdoor reset is enabled through a switch on the<br />

screen, the setpoint will be generated by the curve for<br />

outdoor reset programmed on the screen.<br />

2.6 WARM WEATHER SHUTDOWN/ENABLE<br />

DISABLE<br />

The Warm Weather Shutdown (WWSD) (refer to<br />

Figure 5.10) function will shutdown either the boilers,<br />

the system pumps or both depending on the selections<br />

on the WWSD screen. When the outdoor air<br />

temperature goes above the temperature set in the high<br />

outdoor air temperature box on the outdoor reset<br />

screen, shutdown will occur.<br />

The outputs for energizing a relay for controlling the<br />

system pumps, O:0.0 and O:0.1 (Refer to figure 3.5) will<br />

energize when the system goes into a WWSD<br />

condition. This is a fail-safe condition. If power is lost<br />

to the <strong>ECCS</strong> panel the pumps will still operate.<br />

7<br />

<strong>On</strong>ce the OAT>HAT setting, a 60 sec timer starts. If the<br />

condition is still true at the end of the 60 seconds the<br />

WWSD function will energize. If both the boilers and<br />

the pumps are selected to shut down, the boilers will<br />

shut down first and 30 seconds later the system pumps<br />

will shut down. This is done to minimize cycling around<br />

the HAT, which triggers the WWSD function.<br />

The WWSD function (or can be used as an Enable/<br />

Disable signal for all boilers) can also be activated with<br />

an external contact closure between terminals L+ and<br />

I:0.1 (Refer to figure 3.5). Ensure that the WWSD<br />

function is not enabled on the <strong>ECCS</strong> panel. This will<br />

function only when the boilers are in the remote mode<br />

and being controlled by the <strong>ECCS</strong> panel. If the boilers<br />

are in the local mode they will not be shut down<br />

by this function. There will be a 1 minute delay before<br />

shutdown once the contact is closed.<br />

2.7 MODBUS COMMUNICATION<br />

The <strong>ECCS</strong> Panel uses the Modbus protocol to<br />

communicate with all the boilers in the system. The<br />

Flame Safeguard and the temperature controller both<br />

have Modbus communication capability. Information<br />

such as faults, alarms, flame signal, cycles, hours,<br />

setpoint, and on/off points can all be communicated to<br />

the touch screen.<br />

2.8 TRENDING<br />

<strong>System</strong> water temperature and outdoor air temperature<br />

are trended for total of 8 hrs (refer to Figure 5.13). The<br />

standard screen shows one hour of time and that trend<br />

can be zoomed in or out from 7.5 minutes to 8 hours.<br />

Points on trend are recorded every 30 seconds.<br />

2.9 LOCAL/REMOTE OPERATION<br />

A Local/Remote switch is located on the Boiler<br />

Parameter screen on the touch screen (refer to Figure<br />

5.7). Some boilers may have an optional physical<br />

selector switch on the front of the boiler.<br />

The Local/Remote selector switch enables the boilers<br />

to be controlled from either the temperature sensor on<br />

the individual boiler (Local) or controlled from the<br />

<strong>System</strong> water temperature sensor (Remote). If the boiler<br />

is in the remote mode, the display on the individual<br />

boiler temperature control will flash Re F (Remote Firing<br />

Rate) and the remote setpoint. If in the local mode, the<br />

display will show the local setpoint without flashing.<br />

*Fail-safe Operation*<br />

If power is lost to the <strong>ECCS</strong> panel, the boilers will<br />

automatically revert back to the local mode.


2.10 DOMESTIC HOT WATER (DHW) PRIORITY<br />

Domestic hot water priority is accomplished by<br />

providing a contact closure to the <strong>ECCS</strong> panel from a<br />

domestic hot water tank. The <strong>ECCS</strong> panel sends out<br />

24V on terminal L+ and receives voltage back on<br />

terminal I0:0 when DHW priority is called for. When<br />

I0:0 receives a signal the following sequence occurs:<br />

1.) The control compares the DHW setpoint (which is<br />

set on the <strong>System</strong> Setup Screen, See Figure: 5.3.) to the<br />

system generated by Outdoor reset curve or fixed<br />

setpoint. If the DHW setpoint is higher, the DHW<br />

setpoint will become the new setpoint. If the DHW<br />

setpoint is lower than the existing setpoint it will not<br />

change the setpoint.<br />

2.) If the system is in the WWSD mode, the system<br />

will be taken out of the WWSD mode and start<br />

boilers until the system water temperature is brought<br />

up to the DHW setpoint.<br />

NOTICE<br />

The <strong>ECCS</strong> <strong>System</strong> WILL NOT start any<br />

pumps or open valves in the DHW piping.<br />

This must be provided by others.<br />

2.11 ALARMS<br />

a. The ECCs will annunciate and record alarms on the<br />

screen that come from the individual boilers. Any of<br />

the faults from the flamesafeguard are annunciated<br />

through Modbus communication to the <strong>ECCS</strong> panel.<br />

The format for the alarms can be viewed in Fig 5.9.<br />

The alarm will indicate which boiler is in alarm, the<br />

fault code #, and a description of the 7 most common<br />

faults. This includes Main Flame Failure, Main Flame<br />

Ignition Failure, Pilot flame failure, Air flow failure,<br />

lockout interlock, Running interlock and Flame<br />

detected. If it is one of the other 100+ possible<br />

alarms it will just display the fault code for the Flame<br />

safeguard. In addition there are alarms for High water<br />

temperature(above 230F), Low water temperature<br />

(below 120F), and communication failure.<br />

A communication failure occurs when the<br />

communication over the Modbus is interrupted by<br />

either losing power to the boiler or there is a break in<br />

the wiring.<br />

b. The <strong>ECCS</strong> stores 100+ alarms in the history<br />

screen. Every alarm is time and date stamped when it<br />

Occurs, when it was Acknowledged, and when it was<br />

Cleared. See Fig 5.8. The screen does not have any<br />

permanent memory so if the power is turned off to the<br />

panel the alarm history is lost.<br />

c. As long as an alarm is active, there will be a small<br />

box with an exclamation point in it at the bottom of<br />

the screen. This will also have the # of active<br />

alarms at the bottom of the box.<br />

d. External alarm indication – A 24vdc relay(supplied<br />

by others) can be power by the <strong>ECCS</strong> between<br />

terminals O:0.7 and M for an alarm indication. Refer<br />

to Fig 3.4.<br />

2.12 EXTERNAL ENABLE/DISABLE<br />

See 2.6 Warm Weather Shut Down on page 7.<br />

8


Section 3: Installation<br />

3.1 UNPACKING<br />

3.1.1. Inspection<br />

CAUTION<br />

Do not lay panel down on touch screen.<br />

Panel weighs approximately 25 lbs.<br />

Use proper lifting techniques when handling.<br />

a. Inspect the shipment carefully for any signs of<br />

damage. All equipment is carefully manufactured,<br />

inspected and packed before shipment. Our<br />

responsibility ceases upon delivery of the <strong>ECCS</strong><br />

panel to the carrier in good condition. The<br />

consignee must file any claims for damage or<br />

shortage in shipment immediately against the<br />

carrier. <strong>Thermal</strong> Solutions Products, LLC will<br />

allow noclaims for variances or shortages unless<br />

presented within thirty (30) days after receipt of<br />

equipment.<br />

b. The <strong>ECCS</strong> system will include:<br />

(1) Panel with touch screen mounted in front door.<br />

PLC inside with terminal strips and breaker.<br />

(1) <strong>System</strong> water temperature sensor and<br />

thermowell.<br />

(1) Outdoor air temperature sensor.<br />

WARNING<br />

Carefully read all instructions before<br />

installing panel. Failure to follow all<br />

instructions in proper order can cause<br />

personal injury or death.<br />

3.2 MOUNTING<br />

3.2.1. Panel<br />

a. The <strong>ECCS</strong> system must be installed to conform<br />

with the requirements of the local and state<br />

authority having jurisdiction, or in the absence of<br />

such requirements, to the latest release of the<br />

National Electric Code, ANSI/NFPA 70.<br />

b. Provide clearance around panel for wiring conduit<br />

and access to panel.<br />

Allow 26" in front of panel to allow door to be<br />

opened and personnel access to touch screen.<br />

Allow 4” on bottom, top and sides to allow<br />

clearance for conduit.<br />

c. Mount in the vertical position. Door hinges on left<br />

side with touch screen facing out. See Figure 3.1<br />

for physical size and details on mounting holes.<br />

d. Panel is rated for NEMA 12 service. When<br />

attaching conduit, enter from bottom of panel to<br />

prevent water from gravitating down the conduit<br />

into the box.<br />

3.2.2. <strong>System</strong> Water Temperature Sensor<br />

a. Mount the thermowell and sensor in a 3/4"<br />

coupling in the common header downstream of all<br />

boiler connections. Maintain a minimum distance<br />

of 10 pipe diameters for connections. See Figure<br />

3.3 <strong>System</strong> Wiring.<br />

3.2.3. Outdoor Air Temperature Sensor<br />

a. Mount the temperature sensor on an outside wall<br />

out of direct sunlight, preferably a north facing<br />

wall.<br />

b. Do not mount sensor near exhausts of any kind,<br />

this may affect readings.<br />

WARNING<br />

Installation of this panel should be<br />

undertaken only by trained and skilled<br />

personnel from a qualified service agency.<br />

9


Figure 3.1: Panel Mounting Layout<br />

10


3.3.ELECTRICAL<br />

NOTICE<br />

3.3.1. General<br />

DANGER<br />

Always positively assure electrical power<br />

is disconnected before attempting work<br />

on or near electrical components or<br />

systems. Electrical shock will/can cause<br />

death or serious injury.<br />

Never work on or near electrical<br />

components when the possibility of<br />

water contact exists. Electrical shocks<br />

will/can result.<br />

Power may need to be disconnected at<br />

more than one location on one or more<br />

voltage supplies.<br />

Electrical work must be performed by<br />

licensed, skilled and experienced<br />

personnel.<br />

Always follow the electrical diagrams<br />

provided with the <strong>ECCS</strong> system. Consult<br />

manufacturer if problems or questions<br />

arise.<br />

Always positively assure electrical work<br />

is performed correctly according to the<br />

authority having jurisdiction before<br />

connecting the power supply.<br />

a. The <strong>ECCS</strong> system must be installed to conform<br />

with the requirements of the local and state<br />

authority having jurisdiction, or in the absence of<br />

such requirements, to the latest release of the<br />

National Electric Code, ANSI/NFPA 70.<br />

b. Panel is built and labeled to UL508A standards.<br />

c. Refer to the wiring diagram supplied with the<br />

panel, the wiring diagram for the boiler, the<br />

system wiring diagram, and the Panel layout<br />

diagram for wiring information.<br />

d. Do not route the communication cable in conduit<br />

with line voltage circuits.<br />

e. Maximum wire length:<br />

Communication bus, 4000 ft.<br />

Low voltage conductors are not to be routed<br />

with line voltage conductors.<br />

3.3.2. Wiring Power Supply to Panel<br />

a. The <strong>ECCS</strong> panel requires 120Vac brought into<br />

the panel. Connect the 120V leg directly to the 4-<br />

amp breaker on the terminal strip. The Neutral<br />

wire connects to the N terminal. The ground wire<br />

connects to the green/yellow terminal.<br />

b. 120Vac supply to the panel must be protected by<br />

a fused disconnect, maximum 20A (by others).<br />

3.3.3. Wiring Panel to Boilers<br />

a. All the wiring going from the <strong>ECCS</strong> panel to the<br />

boilers is low voltage DC, 24V or less. Use<br />

minimum 22ga., 3 wire shielded cable. Belden<br />

Part# 8771 or equivalent.<br />

b. Modbus Signal - 3 wire, 22ga. shielded cable run<br />

from terminals A, B, C in the panel to terminals A,<br />

B, C in THE CLOSEST BOILER. The wire must<br />

be wired from the closest boiler to the next boiler<br />

and repeated until the last boiler is reached. In<br />

other words this must be a continuous chain (daisy<br />

chain configuration). A 120-ohm resistor must be<br />

added to the last device. (See Figure 3.3 <strong>System</strong><br />

Wiring). The resistor is taped to the inside of the<br />

panel for shipping.<br />

3.3.4. Wiring Panel to Sensors<br />

a. <strong>System</strong> water temperature sensor - Run a 2 wire,<br />

22 ga. shielded cable from terminals a+ and a- in<br />

the <strong>ECCS</strong> panel to the wire leads on the<br />

temperature sensor. Attach shield at panel to<br />

terminal marked shield. See Figure 3.4 <strong>ECCS</strong><br />

Panel Wiring Diagrams.<br />

b. Outdoor air temperature sensor - Run a 2 wire, 22<br />

ga. shielded cable from terminals b+ and b- in the<br />

<strong>ECCS</strong> panel to the wire leads on the outdoor<br />

temperature sensor. Attach shield at panel to<br />

terminal marked shield. See Figure 3.4 <strong>ECCS</strong><br />

Panel Wiring Diagram.<br />

NOTICE<br />

Sensor wiring is susceptible to electrical<br />

interference. Insure the shield on cable is<br />

grounded on one end only.<br />

11


12<br />

Figure 3.2: Panel Layout


13<br />

Figure 3.3: <strong>System</strong> Wiring


Figure 3.4: <strong>ECCS</strong> Panel Wiring Diagram<br />

14


15<br />

Figure 3.5: Boiler Wiring Diagram


Section 4: Setting the Modbus Addresses<br />

4.1 COMMUNICATION SETUP FOR BOILERS<br />

Each Modbus device in each boiler must be addressed to<br />

properly communicate with the <strong>ECCS</strong> system. The<br />

Temperature <strong>Control</strong>ler must be addressed through the<br />

configuration level and the flame safeguard will be<br />

addressed according to the following instructions. Refer to<br />

Appendix A, system wiring, or individual component<br />

manuals.<br />

4.2 SETTING THE ADDRESS OF THE HONEYWELL<br />

MODBUS MODULE<br />

Addressing for the HW Modbus Module correlates to the<br />

Temp <strong>Control</strong>lers Modbus addressing on the same unit.<br />

There are 2 dials on the bottom of the module that need to<br />

be set and a jumper that needs to be removed. Refer to<br />

Figure 4.1: Honeywell S7810M Modbus Module Mounting<br />

and 4.2: S7810M Address Switches and Baud Rate Jumper.<br />

4.3 SETTING THE MODBUS ADDRESS OF THE<br />

FIREYE MICRO M<br />

Addressing for the Fireye correlates to the Temperature<br />

<strong>Control</strong>lers Modbus addressing on the same unit. Refer to<br />

MicroM manual for instructions.<br />

Fireye MicroM<br />

Fireye<br />

Temperature Parameter<br />

<strong>Control</strong>ler Baud Rate @<br />

(C113)<br />

19,200<br />

Unit Address<br />

Boiler<br />

1 0160<br />

11<br />

Boiler<br />

2 0260<br />

12<br />

Boiler<br />

3 0360<br />

13<br />

Boiler<br />

4 0460<br />

14<br />

Boiler<br />

5 0560<br />

15<br />

Boiler<br />

6 0660<br />

16<br />

Honeywell<br />

Temperature<br />

<strong>Control</strong>ler<br />

(C113)<br />

S7810M<br />

Modbus<br />

Module<br />

Baud Rate @<br />

19,200<br />

remove<br />

jumper<br />

10"s<br />

Dial<br />

1"s<br />

Dial<br />

Boiler<br />

1<br />

0160<br />

1 1<br />

Boiler<br />

2<br />

0260<br />

1 2<br />

Boiler<br />

3<br />

0360<br />

1 3<br />

Boiler<br />

4<br />

0460<br />

1 4<br />

Boiler<br />

5<br />

0560<br />

1 5<br />

Boiler<br />

6<br />

0660<br />

1 6<br />

16


Figure 4.1: Honeywell S7810M Modbus TM Module Mounting<br />

17


Note: View from bottom of module<br />

Figure 4.2: S7810M Address Switches and Baud Rate Jumper<br />

18


Section 5: Touch Screen Programming<br />

5.1. SCREEN DESCRIPTION<br />

The touch screen is 116x87mm or (5.7"). The display uses<br />

CCFL(cold cathode Florescence Lamps) back lighting with<br />

320x240 pixels. Resistive/analog touch screen technology.<br />

5.2. GENERAL GUIDLENES FOR USING THE<br />

TOUCH SCREEN<br />

1) Touching the screen with the nail of the finger, an<br />

eraser on a pencil, or a pen cap is more effective<br />

than the skin on the tip of the finger.<br />

2) All inputs will have boxes around the value. A value<br />

without a box around it is for display only and<br />

cannot be changed.<br />

3) When you touch an input box, a keypad will be<br />

displayed for entering the desired value.<br />

4) Some inputs are password protected. If an input<br />

box is pressed and a Login box is displayed asking<br />

for a password, press the area where the password<br />

should be. A keypad will be displayed to enter the<br />

password. (See below.)<br />

5) When the correct password is entered the box<br />

will disapear and the desired value can now be<br />

entered into the input box by pressing it again and<br />

using the keypad that is displayed.<br />

6) Entering the password once will disable the need<br />

to enter it again on that security level and lower<br />

for 5 minutes.<br />

Press this area to<br />

enter password<br />

Figure 5.1: Touch Screen Login<br />

19


B1 = Boiler #1<br />

Bar graph shows<br />

firing rate as % of<br />

modulation<br />

Shows Firing rate<br />

as a numerical %<br />

of modulation.<br />

100% - Highfire<br />

1% - Low fire<br />

0% - Off<br />

Indicates if the boiler<br />

is the lead boiler, has<br />

a fault, or is operating<br />

in manual<br />

Boiler water outlet<br />

temperature<br />

Press button to access alarm history<br />

Figure 5.2: Main Screen<br />

Press input box to enter Setpoint<br />

Press button to enter a<br />

curve for outdoor reset<br />

<strong>On</strong>/off points set by<br />

the differential on<br />

the trigger points<br />

Press button to go to<br />

the trigger points<br />

screen<br />

Domestic Hot Water<br />

Setpoint<br />

Press button to<br />

enter a Lead<br />

Lag sequence<br />

Figure 5.3: <strong>System</strong> Setup Screen<br />

20


SETTING THE TRIGGERS AND THE START /STOP TIME DELAYS FOR THE LEAD LAG SYSTEM<br />

The value entered in this box will be subtracted from the setpoint to create<br />

the boiler <strong>On</strong> point. This <strong>On</strong> point has two separate functions–<br />

1)If the system has ON/OFF boilers, it will use the ON POINT as a trigger<br />

to turn on the next boiler.<br />

2)If the system is using modulating boilers only the lead boiler will use<br />

the on point to turn on.<br />

0% of firing rate =<br />

low fire<br />

100% of firing rate<br />

= high fire<br />

Input box. Firing rate of<br />

the running boiler<br />

which when reached<br />

will start the timer to<br />

start the next boiler in<br />

sequence. The limits of<br />

this value are between<br />

50 and 100.<br />

Input box. Firing<br />

rate of the running<br />

boiler which when<br />

reached will start<br />

the timer to stop the<br />

last boiler in the<br />

sequence. The<br />

limits of this value<br />

are 0 - 50.<br />

Adjustable start time<br />

delay which delays<br />

the starting of the next<br />

boiler in the sequence<br />

once the start trigger<br />

is made. The limits of<br />

this value are 90-900.<br />

Adjustable stop time<br />

delay which delays<br />

the stopping of the last<br />

running boiler in the<br />

sequence once the stop<br />

trigger is made. The<br />

limits of this value are<br />

0-1200.<br />

Figure 5.4: Lead Lag Trigger Setup Screen<br />

The value entered in this<br />

box will be added to the<br />

setpoint to create the<br />

boiler Off point. This<br />

Offpoint has two separate<br />

functions–<br />

1)If the system has<br />

ON/OFF boilers, it<br />

will use the Off point<br />

as a trigger to turn<br />

off the last running<br />

boiler.<br />

2)If the system is using<br />

modulating boilers<br />

only the lead boiler<br />

will use the the Off<br />

point to turn off.<br />

Example, using the values above (Modulating boilers) :<br />

Boiler 1 is on and reaches 90% of firing rate. The firing rate<br />

will have to stay above 90% for 120 sec for the next boiler<br />

in the sequence to start. If it drops below 90% before the 120<br />

second time delay is complete, the timer will reset.<br />

Example (<strong>On</strong>/Off boilers) : Assume a setpoint of 180 °F.<br />

The <strong>On</strong> and Off points are programmed on the screen at 5<br />

and 5. Therefore the boilers will turn on a 175 °F and off at<br />

185 °F. The boilers have a differential of 10°F.<br />

Boiler 1 is on and the temp at the system water temperature<br />

sensor drops below 175 °F for 120 sec., the next boiler in the<br />

sequence will start. If the system water temperature rises to<br />

175 °F before the time is complete, the timer will reset.<br />

21


ENTERING THE LEAD LAG SEQUENCE AND ROTATION TIME<br />

NOTICE<br />

Some boilers may shut down depending<br />

on the new sequence entered.<br />

The input boxes must<br />

be pressed and a<br />

keypad will be displayed<br />

on the screen to enter<br />

a new value.<br />

When the CHANGE SEQUENCE button is pressed,<br />

the input boxes and the sequence enter button will be<br />

displayed.<br />

Press and drag the<br />

AUTO ROTATE<br />

switch to turn on/off<br />

the automatic<br />

rotation of the<br />

sequence.<br />

Press the input box to<br />

set rotation time. Range<br />

is between 8 hours and<br />

720 hours. When in the<br />

auto rotate mode the<br />

sequence will<br />

automatically rotate as<br />

follows:<br />

Before rotation 1 (lead),<br />

2, 3, 4, 5.<br />

After rotation 2 (lead), 3,<br />

4, 5, 1.<br />

Figure 5.5: Sequence and Rotation Screen<br />

22


Outdoor Reset Switch.<br />

Press and drag toggle<br />

switch from OFF to ON.<br />

The setpoint will now<br />

be generated by the<br />

curve entered above.<br />

Entering temperatures in these 4 input<br />

boxes will generate a linear curve in<br />

which a setpoint based on outdoor air<br />

temperature will be generated.<br />

This is the setpoint which<br />

is generated based on the<br />

outdoor air curve entered<br />

and the outdoor air<br />

temperature.<br />

Pressing this button will<br />

go to the screen to set<br />

up the Warm Weather<br />

Shutdown Options.<br />

CAUTION<br />

This system cannot protect the boiler from cold water returning back to the boiler as is the case<br />

when coming out of a warm weather shutdown scenario. In order to protect the boiler from<br />

condensing, a primary/secondary piping arrangement or mixing valve must be installed in the<br />

piping.<br />

Figure 5.6: Outdoor Reset Setup Screen<br />

This is the setpoint of the boiler water at the outlet of<br />

the boiler. When in local the boiler will use this as its<br />

operating setpoint.<br />

The values for Setpoint,<br />

<strong>On</strong> point and Off point are<br />

for display only and come<br />

directly from the boiler<br />

temperature controller via<br />

a Modbus connection.<br />

These values come<br />

directly from the Flame<br />

Safeguard via a Modbus<br />

connection.<br />

Pressing and dragging this<br />

switch with your finger will<br />

change control from local to<br />

remote operation.<br />

Figure 5.7: Boiler Parameters Screen<br />

23


Pressing the Alarm History button<br />

on the main screen will get you to<br />

this screen<br />

Records Date and time the fault<br />

occurs(O), was Acknowledged(A),<br />

and cleared(C).<br />

Buffer can hold<br />

up to 110 fault<br />

messages.<br />

Figure 5.8: Alarm History Screen<br />

THIS BOX WILL AUTOMATICALLY APPEAR OVER ANY SCREEN WHEN A FAULT OCCURS<br />

Boiler # fault occured on<br />

Description<br />

fault<br />

of<br />

Fault code<br />

The Alarm Indicator will stay at the bottom of all<br />

screens until all faults have been cleared. The # at<br />

the bottom of the box indicates how many faults are<br />

active. Pressing this button will bring up a screen<br />

showing all the active alarms.<br />

Pressing the ACK button<br />

Acknowledges the alarm and<br />

makes the box disappear.<br />

Figure 5.9: Alarm Pop-up Screen<br />

24


Figure 5.10: Warm Weather Shutdown Screen<br />

Figure 5.11: Initial Setup Screen<br />

25


Figure 5.12: Trend Screen<br />

This trend will record header temperature and outdoor air temperature for up to 8 hours. Screen normally shows a one hour<br />

snapshot. Using the – and the + keys will zoom out to 8 hours or zoom in to 7.5 minutes (refer to Figure 5.13 Trend Screen Zoom<br />

<strong>Control</strong>). Each time a button is pressed, the graph will double or half (depending on button pressed) the time increment. Data is<br />

recorded every 30 seconds.<br />

Figure 5.13: Trend Screen Zoom <strong>Control</strong><br />

26


Figure 5.14 Time/Date Screen<br />

In order to access the time/date screen, press an invisible button in the<br />

upper right hand corner of the Boiler 1 Parameter Screen (figure 5.7)<br />

27


Section 6: Trouble Shooting Guide<br />

PROBLEM<br />

No boilers running<br />

Temperature<br />

OFF POINT.<br />

POSSIBLE CAUSE<br />

of water higher than the<br />

Boilers in local mode and boiler water<br />

temperature is above OFF POINT.<br />

POSSIBLE REMEDY<br />

Boilers will come on automatically when system<br />

water temperature drops below ON POINT.<br />

Switch to remote or wait for temperature to drop<br />

below ON POINT.<br />

B reaker in <strong>ECCS</strong> Panel in OFF or tripped. Turn on breaker in <strong>ECCS</strong> Panel.<br />

Touch Screen is not lit<br />

Power feeding <strong>ECCS</strong> Panel is OFF or<br />

tripped.<br />

Improper power supply to panel.<br />

Power<br />

to screen is not connected.<br />

Improper power supply to screen.<br />

Turn on breaker feeding <strong>ECCS</strong> Panel.<br />

Check power voltage and correct as needed.<br />

Panel requires 120VAC wired to 4 amp circuit<br />

breaker inside panel.<br />

Check wiring and correct as needed, 24VDC<br />

Screen uses 24VDC from PLC. Check voltage<br />

and correct if needed.<br />

B ad touch screen.<br />

Replace screen.<br />

No data being<br />

displayed on screen<br />

and no communication<br />

error or data on<br />

screen is not updating<br />

Modbus communication wires shorted<br />

together on any temperature controller or<br />

flame safeguard.<br />

Check Modbus wires A & B on all controllers for<br />

location where wires are touching each other<br />

and separate.<br />

P LC not in run mode.<br />

Flip switch on front of PLC to run position.<br />

P ower off to boiler.<br />

Turn power on to boiler.<br />

Alarm "Boiler #<br />

Communication<br />

Failure"<br />

Alarm "Boiler # Main<br />

Flame Failure"<br />

Modbus wiring disconnected on boiler<br />

showing alarm.<br />

Shield on wire not grounded properly.<br />

Baud rate setting on Fireye or Honeywell<br />

controller is wrong.<br />

Incorrect baud rate set on temperature<br />

controller.<br />

Modbus wiring A, B, C is not consistent<br />

throughout boiler devices.<br />

Boiler address not correct on flame<br />

safeguard or temperature controller.<br />

Boiler has faulted on a flame failure while<br />

in run mode.<br />

Connect Modbus wiring (3 wire shielded cable)<br />

to terminals A, B, C on devices.<br />

Shield should be grounded on one end of<br />

daisy chain only (panel end). Shields at wire<br />

junctions should be tied together.<br />

Set baud rate to 19,200.<br />

Configuration parameter check C113. Second<br />

value from right shall be a 6. Adjust as needed.<br />

Insure same wire is daisy chained to all A<br />

terminals, B to B terminals, and C to C<br />

terminals.<br />

Check appendix for correct setting on Modbus<br />

devices. See Section 4.<br />

Check controller manual. Reset flame<br />

safeguard controller.<br />

Alarm "Boiler # Pilot<br />

Flame Failure"<br />

Alarm "Boiler #<br />

Airflow Switch"<br />

B oiler has faulted while lighting pilot. Refer to boiler manual troubleshooting guide.<br />

F an did not energize.<br />

Refer to boiler manual troubleshooting guide.<br />

A ir flow switch set wrong or not working. Adjust or replace switch.<br />

F an running too slow.<br />

Check VFD to determine cause and correct.<br />

28


Section 7: Appendix A – Temperature <strong>Control</strong>ler Operation for Modulating<br />

Boilers (Modbus)<br />

7.1. DESCRIPTION<br />

The microprocessor based temperature<br />

controller is utilized for all modulating<br />

<strong>Thermal</strong> Solutions water boilers. The basic<br />

function of the controller is to modulate the<br />

firing rate of the burner in response to the<br />

boiler heat load. The controller monitors the<br />

boiler water temperature through the use of<br />

a sensor located in the boiler pressure<br />

vessel. The controller compares the boiler<br />

water temperature to the controller’s user<br />

defined operating set-point temperature.<br />

An output signal from the microprocessor<br />

varies the blower speed through the use of a<br />

variable frequency drive (VFD). The gas<br />

valve regulates an appropriate amount of<br />

gas flow for a given air flow or blower<br />

speed. The user may adjust the operating<br />

set-point temperature for a given<br />

application. In addition, the controller has the ability to<br />

change to an alternate set-point through an external signal<br />

for low load conditions (i.e. weekend use, night setback).<br />

Outdoor reset is another standard feature, allowing the<br />

boiler operating temperature to vary based on the outdoor<br />

ambient temperature. The typical result is a higher seasonal<br />

efficiency.<br />

7.2. SET-UP<br />

All of the control parameters have been set at the<br />

factory. There are a few parameters called “Process<br />

Parameters” that must be defined by a qualified<br />

operator. The table below will help serve as a<br />

reference and record when making adjustments.<br />

To alter any of these process parameters follow the<br />

following steps:<br />

• To obtain access into the programming mode<br />

of the controller, briefly press the button<br />

“PGM”.<br />

• You will see “SP1” displayed on the second<br />

line in green LEDs. The previously set<br />

operating temperature will be displayed on the<br />

first line in red LEDs. To increase or decrease<br />

the setpoint 1 value (SP1) use the up and<br />

down arrow keys respectively (st).<br />

• To set the value for “SP2”, briefly press the<br />

“PGM” key and follow the same instructions<br />

above.<br />

• To return to the operating mode press<br />

“EXIT”, otherwise the unit will automatically<br />

return to the operating mode after 30 seconds<br />

of no activity.<br />

To make other adjustments, contact your local<br />

representative or consult the factory.<br />

7.3. MODBUS VERSION USED ON BOILERS CONTROLLED BY THE <strong>ECCS</strong> SYSTEM<br />

The <strong>ECCS</strong> control system communicates with the temperature controller using a Modbus communication system. A three wire<br />

shielded cable is connected in a daisy chain configuration to each temperature controller at the CA,CB,CG terminals. This<br />

controller accepts modulating, enable/disable, and local/remote commands from a remote source. Information such as setpoint,<br />

water temperature, frequency feedback, on/off points, etc can also be transmitted back to the control panel.<br />

Parameter<br />

Display<br />

Value<br />

Range<br />

Factory<br />

Setting<br />

User Setting<br />

Setpoint<br />

1<br />

SP1<br />

125-200<br />

180<br />

Setpoint<br />

2<br />

SP2<br />

125-200<br />

0<br />

Digital Setpoint Shift<br />

(optional)<br />

dSP<br />

125-200<br />

0<br />

Outside Temperature<br />

(optional)<br />

Pre-definition of External<br />

Setpoint (optional)<br />

TA<br />

SP.E<br />

C onsult Factory<br />

—<br />

C onsult Factory<br />

—<br />

Figure 7.1 Process Data<br />

30


Actual Boiler Water<br />

Temperature (red display)<br />

Setpoint value (green display)<br />

Solid–local mode<br />

Flashing Ref–(Remote firing rate)<br />

Burner <strong>On</strong><br />

Call for Heat<br />

Decrease Value<br />

Indicates <strong>Manual</strong><br />

Operation<br />

Limit Comparator<br />

Increase Value<br />

Programming Key<br />

EXIT Key<br />

7.4 ADJUSTMENTS<br />

Often during troubleshooting conditions it may become<br />

necessary to manually adjust the firing rate. Follow the<br />

instructions below to make manual firing rate adjustments.<br />

• Press “EXIT” button and hold for 5 -10<br />

seconds.<br />

• The red light above manual operation (hand)<br />

symbol illuminates.<br />

• Press s button to raise firing rate. Press t<br />

button to lower firing rate.<br />

• 0 = 50% of Maximum firing rate and 100 =<br />

100% of Maximum firing rate<br />

• Press “EXIT” button and hold for 5 –10<br />

seconds to return to automatic firing rate<br />

control.<br />

• Automatic mode has been re-activated once<br />

the red light above the manual operation<br />

symbol goes out.<br />

7.5 SYSTEM SPECIFICATIONS<br />

Input voltage ....................................... 100-240vac 48/63hz<br />

Operating temperature ........................................... 0-120° F<br />

Environmental ........................................ NEMA 4 external,<br />

Internal 95%rh noncondensing<br />

Transducer supply ........................................ 24VDC, 30ma<br />

Analog Input 1 ..................Pt100,Ni100, PT1000, Ni 1000,<br />

... Thermocouple (J, K, T or N),4-20ma and Analog 0-10v<br />

Analog Input 2 ........... 1k pot,4-20ma, 0-1VDC, 0-10 VDC<br />

Analog Input 3 ............................................. Pt1000,Ni1000<br />

Output 1 release to modulate...... 24-240VAC 2Amps max<br />

Output 2 and 3 open/close .......... 24-240VAC 2Amps max<br />

Output 4 programmable ............. 24-240VAC 2Amps max<br />

Output 5 analog output ..... 0-10 VDC (500 ohm load min),<br />

....................................0-20 or 4-20ma (500ohm load max)<br />

Modbus RTU port ... 4800 Baud, 9600 Baud, 19,200 Baud<br />

................................................................ unit Address 1-99<br />

Size ................................... 1/8 din, 130mm mounting depth<br />

Data storage ......................................................... EEPROM<br />

Approvals ...................................................... UL, CSA, CE<br />

31


NOTES


NOTES


THERMAL SOLUTIONS PRODUCTS, LLC.<br />

(“Seller”)<br />

LIMITED WARRANTY<br />

LIMITED WARRANTY<br />

Subject to the terms and conditions herein and except as provided<br />

below with respect to products or parts not manufactured by<br />

<strong>Thermal</strong> Solutions Products, LLC, Seller warrants to the original<br />

owner at the original installation site that products manufactured<br />

by Seller (“Products”) comply, at the time of manufacture, with<br />

recognized hydronics industry regulatory agency standards and<br />

requirements then in effect and will be free from defects in<br />

materials and workmanship for a period of 3 years from date of<br />

shipment (the “Warranty Period”) SPECIAL NOTE: The<br />

warranty of any boiler found to be operating as a “Water Heater”<br />

shall revert back to <strong>Thermal</strong> Solution’s standard water heater<br />

warranty.<br />

For products or parts not manufactured by <strong>Thermal</strong> Solutions,<br />

the warranty obligations of <strong>Thermal</strong> Solutions shall, in all<br />

respects, be limited to one year.<br />

REMEDY<br />

A. The sole remedy for breach of this warranty is expressly<br />

limited to the repair or replacement of any part found to be<br />

defective under conditions of normal use within the<br />

Warranty Period. Labor for removal and/or installation is<br />

not included.<br />

B. Warranty - The owner must notify the original installer of<br />

the Product and Seller (Attention: <strong>Thermal</strong> Solutions<br />

Products, LLC, P.O. Box 3244, Lancaster, PA 17604-<br />

3244), in writing, within the Warranty Period, providing a<br />

detailed description of all claimed defects. Transportation to<br />

a factory or other designated facility for repairs of any<br />

products or items alleged defective shall, in all events, be the<br />

responsibility and at the cost of the owner.<br />

EXCLUSIONS<br />

Seller shall have no liability for and this warranty does not cover:<br />

A. Incidental, special or consequential damages, such as loss of<br />

the use of products, facilities or production, inconvenience,<br />

loss of time or labor expense involved in repairing or<br />

replacing the alleged defective Product.<br />

B. The performance of any Product under conditions varying<br />

materially from those under which such Product is usually<br />

tested under industry standards as of the time of shipment.<br />

C. Any damage to the Product due to abrasion, erosion,<br />

corrosion, deterioration, abnormal temperatures or the<br />

influence of foreign matter or energy.<br />

D. The design or operation of owner’s plant or equipment or of<br />

any facility or system of which any Product may be made a<br />

part.<br />

E. The suitability of any Product for any particular application.<br />

F. Any failure resulting from misuse, modification not<br />

authorized by Seller in writing, improper installation or lack<br />

of or improper maintenance.<br />

G. Equipment furnished by the owner, either mounted or<br />

unmounted, or when contracted for by the owner to be<br />

installed or handled.<br />

H. Leakage or other malfunction caused by:<br />

1. Defective installations in general and specifically, any<br />

installation which is made:<br />

a. in violation of applicable state or local plumbing<br />

housing or building codes,<br />

b. without a certified ASME, pressure relief valve, or<br />

c. contrary to the written instructions furnished with the<br />

unit<br />

2. Adverse local conditions in general and, specifically,<br />

sediment or lime precipitation in the tubes and/or headers<br />

or corrosive elements in the atmosphere.<br />

3. Misuse in general and, specifically, operation and<br />

maintenance contrary to the written instructions<br />

furnished with the unit, disconnection, alteration or<br />

addition of components or apparatus, not approved by<br />

seller, operation with fuels or settings other than those<br />

set forth on the rating plate or accidental or exterior<br />

damage.<br />

I. Production of noise, odors, discoloration or rusty water.<br />

J. Damage to surrounding area or property caused by leakage<br />

or malfunction.<br />

K. Costs associated with the replacement and/or repair of the<br />

unit including: any freight, shipping or delivery charges, any<br />

removal, installation or reinstallation charges, any material<br />

and/or permits required for installation reinstallation or<br />

repair, charges to return the boiler and or components.<br />

Seller’s liability under this warranty shall not in any case exceed<br />

the amount paid for the Product found to be defective.<br />

THIRD-PARTY WARRANTIES<br />

For goods or components not manufactured by Seller, the<br />

warranty obligations of Seller shall, in all respects, conform and<br />

be limited to one year from the date of shipment<br />

SEVERABILITY<br />

To the extent that any provision of this warranty would be void or<br />

prohibited under applicable law, such provisions shall be limited<br />

in effect to the minimum extent necessary to render the remaining<br />

provisions hereof enforceable.<br />

NO OTHER WARRANTIES<br />

Seller makes no implied warranty of merchantability or<br />

fitness for a particular purpose, or other warranties with<br />

respect to any products or services except as expressly set<br />

forth in this limited warranty.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!