TABLE 6 - EQUIVALENT OF STANDARD PIPE FITTING & VALVES<br />

VALVES FULLY OPEN<br />

Pipe<br />

Size<br />

I.D.<br />

Inches<br />

Gate<br />

Globe<br />

Angle<br />

Swing<br />

Check<br />

90°<br />

Elbow<br />

45°<br />

Elbow<br />

90° Tee, Flow<br />

through Run<br />

90° Tee, Flow<br />

through<br />

Branch<br />

1/2"<br />

3/4"<br />

1"<br />

1-1/4"<br />

0.622<br />

0.824<br />

1.049<br />

1.380<br />

0.35<br />

0.44<br />

0.56<br />

0.74<br />

18.6<br />

23.1<br />

29.4<br />

38.6<br />

9.3<br />

11.5<br />

14.7<br />

19.3<br />

4.3<br />

5.3<br />

6.8<br />

8.9<br />

1.6<br />

2.1<br />

2.6<br />

3.5<br />

0.78<br />

0.97<br />

1.23<br />

1.6<br />

1.0<br />

1.4<br />

1.8<br />

2.3<br />

3.1<br />

4.1<br />

5.3<br />

6.9<br />

1-1/2"<br />

2"<br />

2-1/2"<br />

3"<br />

1.610<br />

2.067<br />

2.469<br />

3.068<br />

0.83<br />

1.10<br />

1.32<br />

1.60<br />

45.2<br />

58<br />

69<br />

86<br />

22.6<br />

29<br />

35<br />

43<br />

10.4<br />

13.4<br />

15.9<br />

19.8<br />

4.0<br />

5.2<br />

6.2<br />

7.7<br />

1.9<br />

2.4<br />

2.9<br />

3.6<br />

2.7<br />

3.5<br />

4.1<br />

5.1<br />

8.0<br />

10.4<br />

12.4<br />

15.3<br />

4"<br />

6"<br />

4.026<br />

6.065<br />

2.1<br />

2.6<br />

112<br />

140<br />

56<br />

70<br />

26.8<br />

40.4<br />

10.1<br />

15.2<br />

5.4<br />

8.1<br />

6.7<br />

10.1<br />

20.1<br />

30.3<br />

Equivalent lengths are for st<strong>and</strong>ard screwed fittings <strong>and</strong> for screwed, flanged, or welded valves<br />

relative to schedule 40 steel pipe.<br />

WARNING<br />

Table 7 lists gas inputs at sea level to 2000 feet altitude.<br />

additional 1000 feet above sea level.<br />

Reduce gas input four percent (4% ) for each<br />

Boiler Model<br />

TABLE 7: RATED INPUT<br />

Rated Capacity (CFH)<br />

Natural<br />

LP/Propane<br />

Gas Connection Size (inc dia.)<br />

EVA-250<br />

250<br />

100<br />

1<br />

EVA-500<br />

500<br />

200<br />

1-1/ 4<br />

EVA-750<br />

750<br />

300<br />

1-1/ 2<br />

EVA-1000<br />

1000<br />

400<br />

1-1/ 2<br />

EVA-1500<br />

1500<br />

600<br />

1-1/ 2<br />

EVA-2000<br />

2000<br />

800<br />

1-1/ 2<br />

EVA-2000S<br />

2000<br />

800<br />

1-1/ 2<br />

EVA-2500<br />

2500<br />

1000<br />

2<br />

EVA-3000<br />

3000<br />

1200<br />

2<br />

20