4. Install drain valve in fitting provided at bottom rear<br />

of the <strong>boiler</strong>.<br />

5. If this <strong>boiler</strong> is used in connection with refrigeration<br />

systems, the <strong>boiler</strong> must be installed so that the<br />

chilled medium is piped in parallel with the <strong>boiler</strong><br />

using appropriate valves to prevent the chilled<br />

medium from entering the <strong>boiler</strong>. Also consult<br />

I=B=R Installation <strong>and</strong> Piping Guides. If this <strong>boiler</strong><br />

is connected to heating coils located in air h<strong>and</strong>ling<br />

units where they may be exposed to refrigerated air,<br />

the <strong>boiler</strong> piping must be equipped with flow control<br />

valves to prevent gravity circulation of <strong>boiler</strong> water<br />

during operation of the cooling system.<br />

6. Install optional low water cut-off such as McDonnell<br />

& Miller Model PS851-M-120 or equal in system<br />

WARNING<br />

Do not install valves, plugs or caps in<br />

safety relief valve piping.<br />

Safety relief valve piping must be<br />

terminated such that in the event the<br />

safety relief valve opens, the discharge<br />

will not cause personal injury or<br />

damage.<br />

7. There must be a minimum of five pipe diameters<br />

of straight horizontal run downstream of the flow<br />

switch. Otherwise, premature failure of flow switch<br />

paddle may occur. See flow switch instruction<br />

manual (MM-601) included with <strong>boiler</strong>.<br />

WARNING<br />

Failure to operate the unit with the proper water<br />

flow rate can lead to appliance failure. Always<br />

verify proper water flow switch operation so that<br />

the unit stops <strong>operating</strong> if improper water flow is<br />

present.<br />

WARNING<br />

Failure to operate the unit with the proper water<br />

flow rate can lead to appliane failure. Always<br />

install water flow switch so that the unit stops<br />

<strong>operating</strong> if improper water flow is present.<br />

Safety relief valve discharge piping must be piped<br />

such that the potential of severe burns is eliminated.<br />

DO NOT pipe in any area where freezing<br />

could occur. DO NOT install any shut-off valves,<br />

plugs or caps. Consult Local Codes for proper<br />

discharge piping arrangement.<br />

Do not operate <strong>boiler</strong> with flow rates in excess of<br />

the maximum flow rates listed in Table 3. Boiler<br />

tube erosion <strong>and</strong> pitting will occur. Thermal Solutions<br />

St<strong>and</strong>ard Warranty does not cover problems<br />

cause by excessive water flow rates.<br />

If a high head system pump is installed, assure<br />

that the <strong>boiler</strong> relief valve <strong>and</strong> system piping are<br />

capable of <strong>operating</strong> properly at the combined<br />

pressure of the system fill pressure plus the pump<br />

static head pressure.<br />