installation, operating and service instructions eva series boiler

installation, operating and service instructions eva series boiler installation, operating and service instructions eva series boiler

boilers.water.heaters.thermalsolutions.com
from boilers.water.heaters.thermalsolutions.com More from this publisher
01.07.2015 Views

B. COMBUSTION AIR - See Figures 6 and 7. 1. The boiler may be operated with inside or outside air. 2. Refer to combustion air piping drawings in this section of this manual for proper outside air installation details. 3. Combustion air conduit can be galvanized smoke pipe, PVC, CPVC, or flexible aluminum conduit. 4. The maximum air inlet length is fifty (50) equivalent feet. Air inlet length is equal to the total length of straight pipe plus the equivalent length of fittings. Consult conduit manufacturer for equivalent length of fittings and pipe. Consult factory for inlet lengths in excess of 50 feet. 5. All joints and seams of the air intake pipe must be sealed using Silicone caulk, such as RTV 732 or equivalent. WARNING Do not reduce size of air intake pipe. Read, understand and follow combustion air instruction restrictions contained in the Pre-Installation instructions of this manual. 6. Air intake termination must be located at least twelve (12) inches above grade plus the expected snow accumulation. 7. Boiler may be installed with vertical venting and sidewall combustion air inlet or visa versa. 8. The air intake pipe must be adequately supported with straps or supports no less than five (5) feet apart. The completed air intake pipe system must be rigid and able to withstand impacts without collapse. CAUTION Dirty, contaminated or dusty air used for combustion will decrease the useful life of the boiler air filter. Use outside air if inside air quality is questionable. Use outside air if the boiler is installed in manufacturing plants, laundries, dry cleaners or other locations with heavy particulates in the air. WARNING Do not locate air intake where petroleum distillates, CFC's, detergents, volatile vapors or any other chemicals are present. Severe boiler corrosion and failure will result. Thermal Solutions does not warrant failures caused by contaminated air. Do not locate air intake termination where natural convection or wind conditions may cause the boiler exhaust gases to be drawn into the air intake. Figure 6: Horizontal Air Intake Piping 13

Figure 7: Vertical Air Intake Piping 14

B. COMBUSTION AIR - See Figures 6 <strong>and</strong> 7.<br />

1. The <strong>boiler</strong> may be operated with inside or outside<br />

air.<br />

2. Refer to combustion air piping drawings in this<br />

section of this manual for proper outside air<br />

<strong>installation</strong> details.<br />

3. Combustion air conduit can be galvanized smoke<br />

pipe, PVC, CPVC, or flexible aluminum conduit.<br />

4. The maximum air inlet length is fifty (50) equivalent<br />

feet. Air inlet length is equal to the total length of<br />

straight pipe plus the equivalent length of fittings.<br />

Consult conduit manufacturer for equivalent length<br />

of fittings <strong>and</strong> pipe.<br />

Consult factory for inlet lengths in excess of 50 feet.<br />

5. All joints <strong>and</strong> seams of the air intake pipe must be<br />

sealed using Silicone caulk, such as RTV 732 or<br />

equivalent.<br />

WARNING<br />

Do not reduce size of air intake pipe.<br />

Read, underst<strong>and</strong> <strong>and</strong> follow combustion<br />

air instruction restrictions contained in the<br />

Pre-Installation <strong>instructions</strong> of this manual.<br />

6. Air intake termination must be located at least<br />

twelve (12) inches above grade plus the expected<br />

snow accumulation.<br />

7. Boiler may be installed with vertical venting <strong>and</strong><br />

sidewall combustion air inlet or visa versa.<br />

8. The air intake pipe must be adequately supported<br />

with straps or supports no less than five (5) feet<br />

apart. The completed air intake pipe system must be<br />

rigid <strong>and</strong> able to withst<strong>and</strong> impacts without collapse.<br />

CAUTION<br />

Dirty, contaminated or dusty air used for<br />

combustion will decrease the useful life of<br />

the <strong>boiler</strong> air filter. Use outside air if inside<br />

air quality is questionable. Use outside air<br />

if the <strong>boiler</strong> is installed in manufacturing<br />

plants, laundries, dry cleaners or other<br />

locations with heavy particulates in the air.<br />

WARNING<br />

Do not locate air intake where<br />

petroleum distillates, CFC's,<br />

detergents, volatile vapors or any other<br />

chemicals are present. Severe <strong>boiler</strong><br />

corrosion <strong>and</strong> failure will result.<br />

Thermal Solutions does not warrant<br />

failures caused by contaminated air.<br />

Do not locate air intake termination<br />

where natural convection or wind<br />

conditions may cause the <strong>boiler</strong><br />

exhaust gases to be drawn into the air<br />

intake.<br />

Figure 6: Horizontal Air Intake Piping<br />

13

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!