MV Vacuum circuit-breaker 24 KV - Schneider Electric
MV Vacuum circuit-breaker 24 KV - Schneider Electric MV Vacuum circuit-breaker 24 KV - Schneider Electric
Catalogue 2004 MV Vacuum circuit-breaker 24 KV
- Page 3 and 4: Evolis circuit-breaker A safe, easy
- Page 5 and 6: 200110 Merlin Gerin’s choices for
- Page 7 and 8: General contents Evolis presentatio
- Page 9 and 10: DV2 Ue Icu 20/ 40 1 0 525 1 0 690 8
- Page 11 and 12: MERLIN GERIN Sepam on ext 1 >51 1o
- Page 13 and 14: Contents Main characteristics prese
- Page 15 and 16: Function description MV connections
- Page 17 and 18: Function description opening circui
- Page 19 and 20: Function description indication and
- Page 21 and 22: Dimensions 3 sizes of width DE60060
- Page 23 and 24: Order form Only one box (ticked or
- Page 25 and 26: Services The following components c
- Page 27 and 28: Contents Main characteristics prese
- Page 29 and 30: Function description racking in DE6
- Page 31 and 32: Function description MV connections
- Page 33 and 34: Function description opening circui
- Page 35 and 36: Function description indication and
- Page 37 and 38: Dimensions 230 mm phase distance DE
- Page 39 and 40: DE60142 Circuit-breaker fitted opti
- Page 41 and 42: Order form Only one box (ticked or
- Page 43 and 44: The following components can be ord
- Page 45 and 46: Evolis Pilot monitoring device Cont
- Page 47 and 48: Local or remote data collection PE6
- Page 49 and 50: Note 47
Catalogue<br />
2004<br />
<strong>MV</strong> <strong>Vacuum</strong> <strong>circuit</strong>-<strong>breaker</strong><br />
<strong>24</strong> <strong>KV</strong>
Evolis <strong>circuit</strong>-<strong>breaker</strong><br />
A safe, easy to integrate<br />
and comprehensive range<br />
for demanding installations.<br />
b Evolis is a vacuum <strong>circuit</strong>-<strong>breaker</strong> that meets current and future standards in terms<br />
of electrical installation dependability, in compliance with standards and<br />
environmental protection.<br />
It is the quintessential expression of Merlin Gerin’s know-how.<br />
b Evolis is intended for all network applications, either new or renovation<br />
installations, for utilities companies, infrastructures, process industry and<br />
tertiary building.<br />
PE60040<br />
Evolis <strong>24</strong> kV frontal fixed<br />
PE60052<br />
Evolis <strong>24</strong> kV frontal withdrawable<br />
1
The very best of<br />
vacuum technology<br />
As a specialist in breaking technologies,<br />
Merlin Gerin took naturally an interest in<br />
vacuum breaking techniques.<br />
A major R&D investment was made to<br />
develop and engineer Evolis, providing<br />
customers with the very best of vacuum<br />
technology.<br />
Make-up of a vacuum interrupter<br />
b <strong>Vacuum</strong> interrupters basically have two electrical contacts, one fixed and the other<br />
mobile, and a sealed enclosure. The latter enables a high level of vacuum to be<br />
maintained inside the interrupter (less than 10 -2 Pa) to provide insulation between<br />
the open contacts.<br />
b The dielectric strength of the vacuum allows the contact-to-contact distance to be<br />
reduced. This short distance together with the low opening speed allow the use of a<br />
low energy control mechanism. A metal bellows provides the link between the mobile<br />
contact and the enclosure.<br />
DE60163<br />
Ceramic chamber<br />
Shield<br />
Fixed contact<br />
Mobile contact<br />
b In order to keep the vacuum level required for the correct operation of the<br />
interrupter for 30 years, the enclosure must be perfectly sealed, and the various<br />
components have to be fully degased. This is achieved by:<br />
v choosing materials that are specifically selected for this application<br />
(metals and ceramics),<br />
v choosing an appropriate assembly process (vacuum, high temperature brazing),<br />
v the use of a "getter" material to absorb the residual gas.<br />
Metal bellows<br />
Fig. 1: vacuum interrupter components<br />
Current breaking in a vacuum interrupter<br />
b In vacuum breaking, the electrical arc generated on separation of the contacts is<br />
made up of a plasma of metal vapors produced by the vaporization of the contact<br />
material.<br />
b At low values of current, these vapors very quickly condense on the shield and<br />
contacts when the arc disappears, thus allowing:<br />
v the vacuum to be re-established,<br />
v a contact-to-contact dielectric strength to be restored that is greater than<br />
the recovery voltage: breaking is then complete.<br />
DE60164<br />
Current<br />
Electrode<br />
AMF coil<br />
Contact disk<br />
Arc plasma<br />
Axial magnetic field<br />
b At high currents, the electrical arc in the vacuum switches to a concentrated mode<br />
which causes high, localized temperature rises on the contacts. The existence of<br />
these hot spots is detrimental to the quick restoring of the dielectric strength.<br />
Two techniques can be used in order to avoid this stagnation of the static<br />
concentrated arc:<br />
v the so called RMF (Radial Magnetic Field) technique, involves rotating the arc<br />
thanks to an electromagnetic effect generated by a radial magnetic field; this<br />
therefore limits contact erosion.<br />
v a more recent technique called AMF (Axial Magnetic Field) involves applying an<br />
axial magnetic field parallel to the axis of the two contacts (fig. 2) which allows a<br />
diffuse arc to be maintained (fig. 3) even at high current values. The arc energy is<br />
spread over the whole contact surface area, therefore causing very low levels of<br />
erosion.<br />
v Merlin Gerin has chosen this last technique for the Evolis range.<br />
Fig. 2: cross-section of AMF contact<br />
PE60042<br />
Fig. 3: diffuse vacuum arc AMF technology<br />
2
200110<br />
Merlin Gerin’s choices for Evolis<br />
combined with its industrial expertise<br />
provides customer with a highly reliable<br />
range of <strong>circuit</strong>-<strong>breaker</strong>s. These products<br />
are suitable for the most demanding<br />
conditions with the guarantee of full<br />
compliance with international standards.<br />
AMF technology<br />
b Evolis <strong>circuit</strong>-<strong>breaker</strong>s use AMF type vacuum interrupters.<br />
According to technical and economic optimization considerations, the axial magnetic<br />
field is generated:<br />
v either by a coil outside of the interrupter (fig. 4), for rated voltages up to 17.5 kV,<br />
v or by a coil integrated in the interrupter contact structure (fig. 5), for the <strong>24</strong> kV<br />
voltage level.<br />
b In both cases the AMF vacuum interrupters feature low arc voltages (Uarc of<br />
around 50 V) and maximum usage of the contact surface for very low contact erosion.<br />
The advantages provided<br />
b The above choices provide customers with the following advantages in<br />
<strong>MV</strong> <strong>circuit</strong>-<strong>breaker</strong> applications:<br />
v simple and compact vacuum interrupters,<br />
v high electrical endurance meaning that there is no need for contact wear<br />
inspection in normal network protection applications including highly disturbed<br />
overhead line feeders.<br />
Fig 4: 17.5 kV external coil type interrupter<br />
DE60162<br />
Fig 5: <strong>24</strong> kV internal coil type interrupter<br />
3
The very best of<br />
vacuum technology<br />
PE60062<br />
Systematic advanced control<br />
The main components of the <strong>circuit</strong>-<strong>breaker</strong>, such as vacuum interrupter and<br />
operating mechanism, are produced by <strong>Schneider</strong> <strong>Electric</strong>. The vacuum interrupters<br />
are manufactured in an ultra-modern production unit in France.<br />
During manufacture, each <strong>circuit</strong>-<strong>breaker</strong> is subjected to systematic advanced<br />
testing.<br />
<strong>Vacuum</strong> interrupter testing<br />
b The level of vacuum in each interrupter is tested using the "magnetron discharge<br />
method".<br />
<strong>Vacuum</strong> interrupter<br />
b Using this sophisticated procedure, measurement is very precise and does not<br />
require access to the inside of the interrupter, thus not affecting the airtight seal.<br />
PE60061<br />
Circuit-<strong>breaker</strong> testing<br />
b A rigorous set of tests and measurements is carried out on each <strong>circuit</strong>-<strong>breaker</strong>.<br />
b The results are reported and signed off by the quality control department on each<br />
device's test certificate to ensure product traceability.<br />
Compliance with standards<br />
b Evolis complies with IEC 62271-100.<br />
b Design and production are certified to ISO 9000 (version 2000).<br />
b Production sites are certified to ISO 14001 (environmental standard).<br />
Industrial process expertise<br />
Certification<br />
b The certificate of conformity provides guarantees that the <strong>circuit</strong>-<strong>breaker</strong>:<br />
v has been subject to type tests according to EN 45001 standards procedures in<br />
accredited laboratories by independent organizations,<br />
v is in conformity with recognized international standards<br />
b Evolis is currently being certified by external EN 45011 accredited organizations,<br />
members of the STL (Short <strong>circuit</strong> Testing Liaison)<br />
v EN 45001: general requirements for the competence of testing and calibration<br />
laboratories,<br />
v EN 45011: general requirements for bodies of operating product certification<br />
systems.<br />
Environmental care<br />
b Product design takes account of the environmental constraints described in a<br />
"Product Environment Profile" dossier (PEP).<br />
b An end-of-service-life manual details procedures for dismantling and processing<br />
components.<br />
4
General contents<br />
Evolis presentation p.6<br />
Panorama p.8<br />
Evolis <strong>24</strong> kV frontal fixed p.10<br />
Evolis <strong>24</strong> kV frontal withdrawable p.<strong>24</strong><br />
Evolis Pilot monitoring device p.43<br />
5
Evolis presentation<br />
6
DV2<br />
Ue Icu<br />
20/ 40 1 0<br />
525<br />
1 0<br />
690<br />
85<br />
cat.B Icw 85kA/1s<br />
Ics = 1 0% Icu<br />
IEC 947-2<br />
EN 60947-2<br />
(V) (kA)<br />
50/60Hz<br />
Extended products offer<br />
DE60129<br />
LV cubicle<br />
components<br />
b Mcb<br />
b protection relay<br />
b lamp<br />
b push button<br />
b terminal blocks<br />
connector<br />
Protection<br />
and control<br />
b UMI<br />
Circuit-<strong>breaker</strong><br />
b pilot<br />
b cradle<br />
Metering<br />
b VPIS<br />
b PM500<br />
UTE VDE BS CEI UNE AS NEMA<br />
Instrument<br />
transformer<br />
<strong>MV</strong> cubicle<br />
components<br />
b capacitor insulator<br />
b earthing switch<br />
b heating resistor<br />
b voltage presence<br />
indicator<br />
b crank<br />
b extraction table<br />
7
DV2<br />
(V) (kA)<br />
Ue Icu<br />
20/ 40<br />
525 1 0<br />
690 85<br />
cat.B Icw 85kA/1s<br />
Ics = 1 0% Icu<br />
IEC 947-2<br />
EN 60947-2<br />
50/60Hz<br />
UTE VDE BS CEI UNE AS NEMA<br />
DV2<br />
Ue Icu<br />
20/ 40 1 0<br />
525<br />
1 0<br />
690<br />
85<br />
cat.B Icw 85kA/1s<br />
Ics = 1 0% Icu<br />
IEC EN 60947-2<br />
(V) (kA)<br />
50/60Hz<br />
UTE VDE BS CEI UNE AS NEMA<br />
Panorama<br />
Evolis 7.2… 17.5 kV frontal<br />
Fixed<br />
Withdrawable<br />
RATED VOLTAGE<br />
kV<br />
kV<br />
kV<br />
PHASE DISTANCE<br />
from 145 to <strong>24</strong>0 mm<br />
RATED SHORT CIRCUIT CURRENT<br />
from 25 to 40 kA<br />
RATED CURRENT<br />
from 630 to 2500 A<br />
separate catalogue<br />
8
MERLIN GERIN<br />
Sepam<br />
on<br />
ext<br />
1 >51 1o >51 0 o f I on Trip<br />
1 > 51 1o > 51<br />
I1 = 165A RMS<br />
I2 = 166A RMS<br />
I3 = 167A RMS<br />
Evolis <strong>24</strong> kV frontal<br />
Protection<br />
and control<br />
Metering<br />
Instrument<br />
transformers<br />
Cubicle<br />
components<br />
Fixed Withdrawable v SEPAM series 20<br />
for common<br />
applications<br />
Pilot option checks that the<br />
<strong>circuit</strong>-<strong>breaker</strong> is in a good<br />
working order<br />
Pilot option checks that the<br />
<strong>circuit</strong>-<strong>breaker</strong> is in a good<br />
working order<br />
v PM450,<br />
PM500 for<br />
basic metering<br />
v LPCT<br />
compatible with<br />
Sepam relay<br />
v Earthing switch<br />
v Insulators<br />
v Potential tester<br />
v Bus section truck<br />
v SEPAM series 40 v PM800 Series v CT v Bus section<br />
for demanding for advanced compatible with v Circuit-<strong>breaker</strong><br />
applications metering Sepam relay extraction table<br />
v Crank<br />
Web accessible Web accessible v SEPAM series 80 v CM3000, v VT v Voltage<br />
RATED VOLTAGE for complete CM4000 Series compatible with indication<br />
kV<br />
applications for Sepam relay v Transparent<br />
comprehensive<br />
metering and<br />
power quality<br />
analysis<br />
screen<br />
v Insulator support<br />
PHASE DISTANCE<br />
from 230 to 250 mm<br />
RATED SHORT CIRCUIT CURRENT<br />
from 16 to 31.5 kA<br />
RATED CURRENT<br />
from 630 to 2500 A<br />
separate catalogues<br />
9
Evolis <strong>24</strong> kV frontal<br />
fixed<br />
10
Contents<br />
Main characteristics presentation p.12<br />
PE60040<br />
Function description p.13<br />
<strong>MV</strong> connections p.13<br />
LV connections p.14<br />
Opening <strong>circuit</strong> p.15<br />
Remote control p.16<br />
Indication and locking / interlocking p.17<br />
Auxiliary wiring diagram p.18<br />
Fixed version<br />
Dimensions p.19<br />
Offer structure p.20<br />
Order form p.21<br />
Separate components p.22<br />
Services p.23<br />
11
Evolis <strong>24</strong> kV frontal<br />
fixed<br />
Main characteristics presentation<br />
A fully assembled and tested unit<br />
b Evolis <strong>circuit</strong>-<strong>breaker</strong>s are actuated by a spring operated mechanism that ensures<br />
operating speeds independent of operator action and can be operated without any<br />
auxiliary supply.<br />
When the operating mechanism is motorized, the <strong>circuit</strong>-<strong>breaker</strong> can take on remote<br />
control functions and perform re-closing cycles.<br />
b This unit is easy to integrate in a cubicle environment. An Installation Guide<br />
explains the necessary operations in detail.<br />
DE60047<br />
D<br />
W<br />
H<br />
<strong>Electric</strong>al characteristics according to IEC 62271-100<br />
Phase distance (mm) 230 250 250<br />
Rated voltage <strong>24</strong> kV Isc In<br />
16 kA 630 A b v<br />
1250 A b v<br />
2000 A v<br />
2500 A v<br />
25 kA 630 A b v<br />
1250 A b v<br />
2000 A v<br />
2500 A v<br />
31.5 kA 630 A v<br />
1250 A v<br />
2000 A v<br />
2500 A v<br />
v available end of 2004<br />
Dimensions (mm)<br />
Weight (kg)<br />
D 593 593 593<br />
H 712.5 712.5 712.5<br />
W 655 730 745<br />
97 97 135<br />
Additional characteristics according to IEC 62271-100<br />
Rated values<br />
Voltage Ur kV rms <strong>24</strong><br />
Insulation voltage:<br />
power frequency withstand voltage Ud kV rms 50<br />
lightning impulse withstand voltage Up kV peak 125<br />
Frequency fr Hz 50-60<br />
Short time withstand current Ik/tk kA Isc/3s<br />
Peak withstand current Ip kA peak 2.5 & 2.6 Isc<br />
Short <strong>circuit</strong> making current kA peak 2.5 & 2.6 Isc<br />
Other characteristics<br />
Operating sequences<br />
O-3min-CO-3min-CO<br />
O-0.3s-CO-3min-CO<br />
O-0.3s-CO-15s-CO<br />
Mechanical endurance class M2<br />
number of operations 10 000<br />
<strong>Electric</strong>al endurance class E2<br />
Number of operations at full Isc value 16 kA 50<br />
25 kA 50<br />
31.5 kA 50<br />
Capacitive current breaking class C1-C2 (for some applications)<br />
Service conditions -25°C to 40°C<br />
Humidity:<br />
average relative humidity <strong>24</strong>-hours period < 95%<br />
1 month < 90%<br />
12
Function description<br />
<strong>MV</strong> connections<br />
Connection<br />
b The basic <strong>circuit</strong>-<strong>breaker</strong> is fitted with drilled copper terminal pads.<br />
Customer connection is easily achieved outside the <strong>circuit</strong>-<strong>breaker</strong> on these vertical<br />
terminal pads.<br />
DE60126<br />
Type tested configurations of connections are shown in the Installation Guide.<br />
13
Evolis <strong>24</strong> kV frontal<br />
fixed<br />
Function description<br />
LV connections<br />
Two solutions for connections<br />
DE60143<br />
without LV Plug<br />
with LV plug<br />
b The basic fixed <strong>circuit</strong>-<strong>breaker</strong> LV wiring can be connected directly to the terminal<br />
block of the operating mechanism, through a cable protection duct.<br />
b An LV plug can be fitted as an option. It includes:<br />
v the fixed part (male) fitted on the <strong>circuit</strong>-<strong>breaker</strong> and fully wired to the terminal<br />
block of the operating mechanism,<br />
v the mobile part (female) compatible with the male part.<br />
DE60149<br />
Low voltage connections<br />
Two versions of LV plug are available<br />
b A 21-pin LV plug, allowing connection of:<br />
v a shunt opening release YO1,<br />
v a remote control mechanism (electrical motor, shunt closing release YF,<br />
antipumping relay),<br />
v the monitoring device Pilot,<br />
v maximum number of auxiliary contacts: 3 NC - 3 NO - 1 CHG,<br />
(see details in chapter "Open/closed auxiliary contacts").<br />
b A 42-pin LV plug, allowing connection of:<br />
v an opening release (shunt opening release or undervoltage release),<br />
v a second opening release (shunt opening release YO2 or undervoltage release YN<br />
or low energy release MITOP),<br />
v a remote control mechanism (electrical motor, shunt closing release, antipumping<br />
relay),<br />
v the monitoring device Pilot,<br />
v maximum number of auxiliary contacts: 5 NC - 6 NO - 1 CHG,<br />
(see details in chapter "Open/closed auxiliary contacts").<br />
LV plug connections<br />
LV wiring kit<br />
A kit including 21 wires (2 meters long) fitted with pin suitable for the plug can be<br />
supplied for connection to the LV compartment of the cubicle.<br />
Interlocking kit<br />
For withdrawble applications, an interlocking kit is available. This kit facilitates<br />
the interlocking between the LV plug (connected/disconnected) and the open/closed<br />
position of the <strong>circuit</strong>-<strong>breaker</strong> (as required by the IEC standard 62271-200).<br />
This arrangement provides an auxiliary supply connection with a high level of<br />
electrical safety.<br />
14
Function description<br />
opening <strong>circuit</strong><br />
DE60161<br />
Composition<br />
b The opening <strong>circuit</strong> can be produced using the followings units:<br />
v shunt opening release (YO1),<br />
v second shunt opening release (YO2),<br />
v undervoltage release (YN),<br />
v low energy release (MITOP).<br />
(2)<br />
(1) or (3)<br />
Please check in the combination table the right associations of different releases.<br />
Note: this table is present in order form at the end of this catalogue.<br />
Shunt opening release (YO1 and YO2)<br />
b This causes instant opening of the <strong>circuit</strong>-<strong>breaker</strong> when energised.<br />
Characteristics<br />
Supply<br />
see order form<br />
Threshold VAC 0.7 to 1.1 Un<br />
VDC<br />
0.85 to 1.1 Un<br />
Consumption VAC 160 VA<br />
VDC<br />
50 W<br />
DE60094<br />
(1) Shunt opening release<br />
Undervoltage release (YN)<br />
b An Undervoltage release operates to open the <strong>circuit</strong>-<strong>breaker</strong> when the voltage at<br />
the terminals of the release falls below 35% of its rated voltage, even if the fall is slow<br />
and gradual.<br />
On the other hand, it does not operate the <strong>circuit</strong>-<strong>breaker</strong> when the voltage at its<br />
terminals exceeds 70% of its rated supply voltages.<br />
Circuit-<strong>breaker</strong> closing is possible when the values of the voltage at the terminals of<br />
the release are greater than or equal to 85% of its rated voltage.<br />
Closing is impossible when the voltage at the terminals is lower than 35% of its<br />
rated supply voltage.<br />
DE60089<br />
(2) Undervoltage release<br />
Characteristics<br />
Supply<br />
see order form<br />
Threshold opening 0.35 to 0.7 Un<br />
closing 0.85 Un<br />
Consumption pick-up VAC 400 VA<br />
VDC<br />
100 W<br />
hold VAC 100 VA<br />
VDC<br />
10 W<br />
DE60091<br />
Low energy release (MITOP)<br />
b This specific release comprises a low energy consumption unit and is used<br />
specifically with self-powered relay SEPAM 100LA ("REFLEX MODULE"), or VIP<br />
relay.<br />
(3) Low energy release<br />
Characteristics<br />
Supply<br />
Threshold<br />
direct current<br />
0.6 A < I < 3 A<br />
Any tripping caused by the Mitop release is indicated momentarily by an SDE type<br />
changeover contact.<br />
15
Evolis <strong>24</strong> kV frontal<br />
fixed<br />
Function description<br />
remote control<br />
Function<br />
DE60160<br />
(6)<br />
(5)<br />
b The remote control enables remote opening and closing of the <strong>circuit</strong>-<strong>breaker</strong>.<br />
(8)<br />
Composition<br />
b The remote control comprises:<br />
v electrical motor and gear reducer,<br />
v a shunt closing release (YF),<br />
v an antipumping relay,<br />
v an operation counter.<br />
(7)<br />
(9)<br />
(4)<br />
DE60093<br />
Operating mechanism<br />
Ì<br />
<strong>Electric</strong> motor and gear reducer<br />
b The electrical motor arms and rearms the energy storage springs as soon as the<br />
<strong>circuit</strong>-<strong>breaker</strong> is closed. This enables instant reclosing of the device after opening.<br />
The arming lever is only used as back up control in the absence of an auxiliary<br />
voltage.<br />
M3 contact indicates end of charging.<br />
(4) <strong>Electric</strong> motor and gear reducer<br />
Characteristics<br />
Supply VAC 50/60 see order form<br />
VDC<br />
see order form<br />
Consumption VAC 380 VA<br />
VDC 380 W<br />
DE60094<br />
Shunt closing release (YF)<br />
b This causes the remote closing of the <strong>circuit</strong>-<strong>breaker</strong> when the operating<br />
mechanism is armed.<br />
(5) Shunt closing release<br />
Characteristics<br />
YF<br />
Supply VAC 50/60 Hz see order form<br />
VDC<br />
see order form<br />
Threshold<br />
0.85 to 1.1 Un<br />
Consumption VAC 160 VA<br />
VDC<br />
50 W<br />
DE60095<br />
Antipumping relay<br />
b The antipumping relay avoids unwanted closing and tripping within a short interval.<br />
This function gives absolute priority to the opening order and blocks closing.<br />
This prevents the device from being locked in an indefinite opening-closing cycle.<br />
(6) Antipumping relay<br />
16
Function description<br />
indication and locking / interlocking<br />
DE60087<br />
Operation counter<br />
b The operation counter is visible from the front face.<br />
It displays the number of operating cycles that the device has performed.<br />
(7) Operation counter<br />
DE60152<br />
Open/closed auxiliary contacts<br />
b The number of available contacts depends on the fitted options on the operating<br />
mechanism.<br />
(8) Auxiliary contacts<br />
b In its basic configuration, the operating mechanism of the <strong>circuit</strong>-<strong>breaker</strong><br />
comprises a total of:<br />
v 5 normally closed contacts (NC),<br />
v 6 normally open contacts (NO),<br />
v 1 changeover contact (CHG).<br />
b Use of auxiliary contacts is given in the following table:<br />
Option NC contact NO contact<br />
Remote control 1 1<br />
Shunt opening release (each) 0 1<br />
Undervoltage release 0 0<br />
Low energy release MITOP 0 0<br />
Trip <strong>circuit</strong> supervision 1 0<br />
To find out the final number of contacts available, the above quantity must be<br />
deducted from the total quantity (5 NC + 6 NO + 1 CHG) included in the <strong>circuit</strong><strong>breaker</strong>.<br />
(Example: a <strong>circuit</strong>-<strong>breaker</strong> equipped with a remote control and a shunt opening release<br />
has 4 NC + 4 NO + 1 CHG available contacts. With an undervoltage release instead of<br />
a shunt release, this <strong>circuit</strong>-<strong>breaker</strong> has 4 NC + 5 NO + 1CHG available contacts).<br />
b When the 21-pin LV plug is used (for withdrawable applications), the maximum<br />
number of available contacts is:<br />
v 3 NC,<br />
v 3 NO,<br />
v 1 changeover.<br />
(Instead of 5NC-6NO-1CHG with the 42-pin LV plug).<br />
Contact characteristics<br />
Rated current<br />
10 A<br />
Breaking capacity AC 220 V (cos ϕ ≥ 0.3) 1 A<br />
DC 110/220 V (L/R ≤ 0.02 s) 0.3 A<br />
DE601<strong>24</strong><br />
Locking of the <strong>circuit</strong>-<strong>breaker</strong><br />
in the open position<br />
b This key lock allows the locking of the <strong>circuit</strong>-<strong>breaker</strong> in the "open" position by the<br />
means of a key.<br />
b The <strong>circuit</strong>-<strong>breaker</strong> is locked in the "open" position by blocking the opening<br />
pushbutton in the "pushed-in position".<br />
b The key lock is of Profalux or Ronis captive key type.<br />
(9) Locking kit<br />
17
Evolis <strong>24</strong> kV frontal<br />
fixed<br />
Function description<br />
auxiliary wiring diagram<br />
Auxiliary wiring diagram (principle)<br />
DE60123<br />
CLOSE CB<br />
OPEN CB<br />
M<br />
YF +<br />
anti-pumping<br />
PILOT<br />
YO1<br />
or<br />
YO2<br />
YM<br />
MITOP<br />
motor<br />
shunt closing<br />
+ anti-pumping<br />
system<br />
monitoring<br />
device pilot<br />
shunt<br />
opening<br />
release<br />
undervoltage<br />
release<br />
low energy<br />
release<br />
(MITOP)<br />
changeover<br />
contact<br />
NO<br />
contacts<br />
NC<br />
contacts<br />
remote control<br />
18
Dimensions<br />
3 sizes of width<br />
DE60060<br />
D<br />
D<br />
97.5<br />
DE60062<br />
712.5<br />
W<br />
593<br />
Dimensions (mm)<br />
Phase distance 230 250 250<br />
D W D W D W<br />
16 kA 630 A b 655 b 734<br />
1250 A b 655 b 734<br />
2000 A b 745<br />
2500 A b 745<br />
25 kA 630 A b 655 b 734<br />
1250 A b 655 b 734<br />
2000 A b 745<br />
2500 A b 745<br />
31.5 kA 630 A b 745<br />
1250 A b 745<br />
2000 A b 745<br />
2500 A b 745<br />
19
Evolis <strong>24</strong> kV frontal<br />
fixed<br />
Offer structure<br />
DE60080<br />
DE60132<br />
Basic frontal fixed <strong>circuit</strong>-<strong>breaker</strong><br />
The basic frontal fixed <strong>circuit</strong>-<strong>breaker</strong> includes:<br />
b a manual operating mechanism (spring type),<br />
b closing and opening pushbuttons,<br />
b a mechanical "open/closed" position indicator,<br />
b a mechanical "charged/discharged" closing spring indicator,<br />
b a shunt opening release,<br />
b an "end of charging" contact,<br />
b a block of auxiliary contacts.<br />
Phase distance (mm) 230 250<br />
<strong>24</strong> kV<br />
16 kA 630 A<br />
1250 A<br />
2000 A -<br />
2500 A -<br />
25 kA 630 A<br />
1250 A<br />
2000 A -<br />
2500 A -<br />
31.5 kA 630 A -<br />
1250 A -<br />
2000 A -<br />
2500 A -<br />
Extra value for:<br />
undervoltage release (instead of shunt opening release)<br />
DE60153<br />
Circuit-<strong>breaker</strong> fitted options<br />
LV connection<br />
21-pin LV plug<br />
42-pin LV plug<br />
DE60135<br />
Monitoring device<br />
Pilot module<br />
diagnosis by <strong>Schneider</strong> <strong>Electric</strong> expert<br />
DE60101<br />
Remote control<br />
remote control<br />
(electrical motor, gear reducer, shunt closing release, antipumping relay, operation counter)<br />
DE60102<br />
Second opening release<br />
DE60132<br />
DE60081<br />
shunt opening release (YO2) (fig. 1)<br />
undervoltage release (YN) (fig. 2)<br />
low energy release (MITOP) (fig. 3)<br />
Fig. 1 Fig. 2 Fig. 3<br />
DE60136<br />
Locking / interlocking<br />
open position <strong>circuit</strong>-<strong>breaker</strong> locking without lock<br />
Ronis or Profalux lock<br />
DE60092<br />
Indication<br />
operation counter<br />
20
Order form<br />
Only one box (ticked or filled in by<br />
the needed value) have to be considered between<br />
each horizontal line.<br />
A blue box corresponds to a non priced function.<br />
Basic frontal fixed <strong>circuit</strong>-<strong>breaker</strong><br />
Quantity<br />
Rated voltage Ur<br />
<strong>24</strong> kV<br />
Rated short-<strong>circuit</strong> breaking current Isc<br />
kA<br />
Rated normal current Ir<br />
A<br />
Phase distance (mm) 230 250<br />
Indicators<br />
IEC standard labels and push button colours red-black red-green<br />
ANSI standard red-black red-green<br />
1st opening release (see possible choice in combination table below)<br />
shunt opening <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />
release (YO1) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />
220 Vdc<br />
undervoltage <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />
release (YN) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />
220 Vdc<br />
Circuit-<strong>breaker</strong> fitted options<br />
LV connection<br />
21 pin LV plug 42 pin LV plug<br />
Pilot monitoring device<br />
Pilot with connecting kit with LV plug without LV plug<br />
diagnosis by <strong>Schneider</strong> <strong>Electric</strong> expert (separate order)<br />
Remote control<br />
<strong>Electric</strong>al motor <strong>24</strong>… 32 Vdc 110… 127 Vdc/ac<br />
48… 60 Vdc/ac 220… 250 Vdc/ac<br />
Shunt closing release<br />
(YF)<br />
<strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />
48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />
220 Vdc<br />
2nd opening release (see possible choice in combination table below)<br />
shunt opening <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />
release (YO2) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />
220 Vdc<br />
undervoltage <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />
release (YN) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />
220 Vdc<br />
low energy release (MITOP)<br />
Locking / interlocking<br />
open position CB locking<br />
Ronis<br />
Profalux<br />
Indication<br />
operation counter (already included if remote control supplied)<br />
Combination table<br />
No LV plug or<br />
21-pin<br />
42-pin LV plug<br />
LV plug<br />
Shunt opening release YO1 1 1 1 1 1<br />
Shunt opening release YO2 1<br />
undervoltage YN 1 1 1<br />
Mitop 1 1<br />
21
Evolis <strong>24</strong> kV frontal<br />
fixed<br />
Separate components<br />
DE60102<br />
DE60154<br />
DE60132<br />
DE60133<br />
DE60101<br />
The following components can be<br />
ordered separately and can be adapted<br />
or replaced by the customer<br />
Accessories incorporated in the operating mechanism<br />
Shunt opening release<br />
Shunt closing release<br />
Undervoltage release<br />
<strong>Electric</strong>al motor<br />
Other accessories of the operating mechanism<br />
DE60136<br />
<strong>24</strong> Vdc AAA10 115<br />
48 Vdc AAA10 116<br />
110 Vdc AAA10 117<br />
125-127 Vdc AAA10 118<br />
220 Vdc AAA10 119<br />
110 Vac 50 Hz AAA10 120<br />
220-230 Vac 50 Hz AAA10 121<br />
120 Vac 60 Hz AAA10 122<br />
<strong>24</strong> Vdc AAA10 106<br />
48 Vdc AAA10 107<br />
110 Vdc AAA10 108<br />
125-127 Vdc AAA10 109<br />
220 Vdc AAA10 110<br />
110 Vac 50 Hz AAA10 111<br />
220-230 Vac 50 Hz AAA10 112<br />
120 Vac 60 Hz AAA10 113<br />
<strong>24</strong> Vdc AAA10 1<strong>24</strong><br />
48 Vdc AAA10 125<br />
110 Vdc AAA10 126<br />
125-127 Vdc AAA10 127<br />
220 Vdc AAA10 128<br />
110 Vac 50 Hz AAA10 129<br />
220-230 Vac 50 Hz AAA10 130<br />
120 Vac 60 Hz AAA10 131<br />
<strong>24</strong>… 32 Vdc AAA10 027<br />
48… 60 Vac/dc AAA10 028<br />
100… 127 Vac/dc AAA10 029<br />
220… 250 Vac/dc AAA10 030<br />
gear reducer AAA10 065<br />
open position <strong>circuit</strong>-<strong>breaker</strong> locking AAA10 092<br />
DE60153<br />
200188<br />
<strong>MV</strong> and LV connection accessories<br />
<strong>MV</strong> connection accessories<br />
LV connection<br />
200190<br />
clusters set (including fingers) 630-1250 A AAA10 025<br />
2500 A AAA10 026<br />
arms set 630-1250 A AAA10 022<br />
2500 A AAA10 023<br />
21-pin LV plug AAA10 031<br />
42-pin LV plug AAA10 032<br />
LV connection kit (21 wires) 59117<br />
22
Services<br />
The following components can only be adapted or replaced on<br />
site by personnel trained by <strong>Schneider</strong> <strong>Electric</strong>:<br />
b Pilot monitoring device,<br />
b remote control (incl.: motor, gear train, shunt closing release, antipumping relay,<br />
operation counter),<br />
b operation counter,<br />
b low energy release (MITOP),<br />
b interlocking kit between <strong>circuit</strong>-<strong>breaker</strong> position and LV plug,<br />
b racking device,<br />
b operating mechanism auto-discharge,<br />
b frontal <strong>circuit</strong>-<strong>breaker</strong> front cover.<br />
23
Evolis <strong>24</strong> kV frontal<br />
withdrawable<br />
<strong>24</strong>
Contents<br />
Main characteristics presentation p.26<br />
PE60041<br />
Function description p.27<br />
Racking in p.27<br />
LPCT sensors p.28<br />
<strong>MV</strong> connections p.29<br />
LV connections p.30<br />
Opening <strong>circuit</strong> p.31<br />
Remote control p.32<br />
Indication and locking / interlocking p.33<br />
Auxiliary wiring diagram p.34<br />
Dimensions p.35<br />
Offer structure p.36<br />
Withdrawable version<br />
Order form p.39<br />
Separate components p.40<br />
Services p.42<br />
25
Evolis <strong>24</strong> kV frontal<br />
withdrawable<br />
Main characteristics presentation<br />
A fully assembled and tested unit<br />
b Evolis <strong>circuit</strong>-<strong>breaker</strong>s are actuated by a spring operated mechanism that ensures<br />
operating speed independent of operator action and can be operated without any<br />
auxiliary supply.<br />
When the operating mechanism is motorized, the <strong>circuit</strong>-<strong>breaker</strong> can take on remote<br />
control functions and perform re-closing cycles.<br />
b This unit is easy to integrate in a cubicle environment. An Installation Guide<br />
explains the necessary operations in detail.<br />
b This withdrawable unit comprises the <strong>circuit</strong>-<strong>breaker</strong>, arms and clusters, racking<br />
truck and its cradle. The cradle and the <strong>circuit</strong>-<strong>breaker</strong> can be ordered and delivered<br />
separately.<br />
DE60049<br />
D<br />
W<br />
H<br />
<strong>Electric</strong>al characteristics according to IEC 62271-100<br />
Phase distance (mm) 230 250<br />
Rated voltage <strong>24</strong> kV Isc In<br />
16 kA 630 A b<br />
1250 A b<br />
2000 A v<br />
2500 A v<br />
25 kA 630 A b<br />
1250 A b<br />
2000 A v<br />
2500 A v<br />
31.5 kA 630 A v<br />
1250 A v<br />
2000 A v<br />
2500 A v<br />
v available end of 2004<br />
Dimensions (mm)<br />
D 1309 1309<br />
H 1188 1188<br />
W 786 886<br />
Weight (Kg)<br />
Circuit-<strong>breaker</strong> 145 206<br />
Cradle 136 148<br />
Additional characteristics according to IEC 62271-100<br />
Rated values<br />
Voltage Ur kV rms <strong>24</strong><br />
Insulation voltage:<br />
power frequency withstand voltage Ud kV rms 50<br />
lightning impulse withstand voltage Up kV peak 125<br />
Frequency fr Hz 50-60<br />
Short time withstand current Ik/tk kA Isc/3s<br />
Peak withstand current Ip kA peak 2.5 & 2.6 Isc<br />
Short <strong>circuit</strong> making current kA peak 2.5 & 2.6 Isc<br />
Other characteristics<br />
Operating sequences<br />
O-3min-CO-3min-CO<br />
O-0.3s-CO-3min-CO<br />
O-0.3s-CO-15s-CO<br />
Mechanical endurance class M2<br />
number of operations 10 000<br />
<strong>Electric</strong>al endurance class E2<br />
Number of operations at full Isc value 16 kA 50<br />
25 kA 50<br />
31.5 kA 50<br />
Capacitive current breaking class C1-C2 (for some applications)<br />
Service conditions -25°C to 40°C<br />
Humidity:<br />
average relative humidity <strong>24</strong>-hours period < 95%<br />
1 month < 90%<br />
26
Function description<br />
racking in<br />
DE60114<br />
2000148<br />
200149<br />
200128<br />
Service position<br />
Test position<br />
Extracted position<br />
Composition<br />
b The "racking in" function is provided by:<br />
v the racking truck supporting the <strong>circuit</strong>-<strong>breaker</strong> (mobile part),<br />
v the cradle including the bushings (fixed part),<br />
v the LV plug.<br />
Operating procedure<br />
b The <strong>circuit</strong>-<strong>breaker</strong> moves through 3 stable positions:<br />
v service position:<br />
<strong>circuit</strong>-<strong>breaker</strong> racked in and locked in place; low voltage plug connected,<br />
v test position:<br />
<strong>circuit</strong>-<strong>breaker</strong> racked out and locked in place; low voltage plug connected,<br />
v extracted position:<br />
the <strong>circuit</strong>-<strong>breaker</strong> can be unlocked and extracted from the cubicle,<br />
with no interlocking.<br />
Safety functions<br />
A propulsive system combined with a screw-shaft makes racking in and racking out<br />
easier.<br />
b Interlocking<br />
In accordance with IEC standards 62271-100 and 62271-200, the following<br />
interlockings are provided:<br />
v racking in or out are impossible unless the <strong>circuit</strong>-<strong>breaker</strong> is in the open position,<br />
v racking in the <strong>circuit</strong>-<strong>breaker</strong> is impossible unless the LV plug is connected,<br />
v disconnecting the LV plug is impossible unless the <strong>circuit</strong>-<strong>breaker</strong> is racked out.<br />
In addition the truck is equipped with a device that allows <strong>circuit</strong>-<strong>breaker</strong> racking in<br />
to be interlocked with the cubicle door (which must be specially designed):<br />
v It is only possible to rack in the <strong>circuit</strong>-<strong>breaker</strong> if the door is closed,<br />
v the door can only be opened with the <strong>circuit</strong>-<strong>breaker</strong> racked out.<br />
b Earthing is achieved throughout the whole racking in operation by the mean of the<br />
wheels of the racking truck. Additional earthing device can be supplied as an option.<br />
b Protective shutters on the cradle prevent access to the racking fingers when the<br />
device is extracted (protection index: IP2X).<br />
b For maintenance or test purposes, it is possible to:<br />
v padlock the shutters in the closed position,<br />
v unlock the shutters mechanism to access the fixed contacts, and insert a screen<br />
to prevent the lived set of fixed contacts being exposed.<br />
DE60138<br />
b A fool-proof protection enables cradle and <strong>circuit</strong>-<strong>breaker</strong> to be matched up.<br />
This system is mounted on the <strong>circuit</strong>-<strong>breaker</strong>. Part of it has to be assembled by<br />
the panel builder on the cradle side.<br />
b Earthing switch<br />
It can be fixed on the cradle, allowing proper interlocking between the <strong>circuit</strong>-<strong>breaker</strong><br />
and the earthing switch, (see detailed description in "Earthing switch and cubicle<br />
components" catalogue).<br />
DE55137<br />
Auto-discharge function<br />
Racked in/out position<br />
MT66049<br />
Earthing sliding device<br />
b Anti-drop function<br />
This function ensures the safety of the operator during the extraction of the<br />
<strong>circuit</strong>-<strong>breaker</strong>.<br />
Accessories<br />
b 4 racked in/racked out position contacts.<br />
b Additional earthing device (copper brush).<br />
b Core sensors LPCT type, directly fitted on the bushings of the cradle.<br />
b Auto-discharge function:<br />
the spring of the <strong>circuit</strong>-<strong>breaker</strong> operating mechanism is automatically discharged<br />
when the <strong>circuit</strong>-<strong>breaker</strong> is extracted from the cubicle. This feature avoids<br />
unexpected closing of the <strong>circuit</strong>-<strong>breaker</strong>.<br />
27
Evolis <strong>24</strong> kV frontal<br />
withdrawable<br />
Function description<br />
LPCT sensors<br />
The LPCT’s are the best way to increase<br />
the effectiveness of the protection chain<br />
and simplify the selection.<br />
Function<br />
b These Low Power Current Transducers (LPCT) provide accurate current<br />
measurement to the protection function when an Evolis <strong>circuit</strong>-<strong>breaker</strong> is associated<br />
with the Sepam relay range.<br />
DE60099<br />
LPCT for bushings (TLP Type)<br />
b They comply with IEC 60044-8 standard.<br />
Composition<br />
b Two types of LPCT are available:<br />
v LPCT for bushings,<br />
v LPCT for cubicles.<br />
b The sensor is delivered with 5m of cable and connector that allows direct<br />
connection to the Sepam unit.<br />
DE60097<br />
LPCT for cubicle (CLP Type)<br />
Mechanical characteristics<br />
(LPCT for bushings)<br />
b Mounted directly on the Evolis withdrawable <strong>circuit</strong>-<strong>breaker</strong> cradle.<br />
The sensors are simply located on the bushings and fixed using three screws.<br />
Each sensor covers the full operating range of the corresponding <strong>circuit</strong>-<strong>breaker</strong>.<br />
b Connection to the Sepam is achieved using an shielded cable which is attached to<br />
each sensor.<br />
<strong>Electric</strong>al characteristics<br />
b In compliance with IEC 60044-8 standard, defining Low Power current Transducer<br />
with voltage output.<br />
b Usable for nominal currents of 25 A to 2500 A.<br />
b Class 0.5 throughout the range.<br />
b Current sensors deliver a voltage output at a ratio of 100 A/22.5 mV.<br />
Common features<br />
Rated primary current<br />
100 A<br />
Rated secondary output (at 100A)<br />
22.5 mV<br />
Accuracy class for measuring 0.5<br />
Accuracy class for protection<br />
5P<br />
Burden<br />
2 kΩ<br />
Frequency<br />
50 / 60 Hz<br />
Specific features CLP2 CLP3 TLP160 TLP190<br />
Assembly In the cubicle In the cubicle On the bushings On the bushings<br />
DE60097<br />
DE60098<br />
DE60099<br />
DE60100<br />
Rated extended primary current 1250 A 2500 A 1250 A 2500 A<br />
Accuracy limit factor 250 315 250 315<br />
Rated short time thermal current 25 kA / 3s 31.5 kA / 3s 25 kA / 3s 31.5 kA / 3s<br />
Highest voltage for equipment <strong>24</strong> kV <strong>24</strong> kV 0.72 kV 0.72 kV<br />
Rated power frequency withstand volt. 50 kV 50 kV 3 kV 3 kV<br />
Rated lighting inpulse withstand voltage 125 kV 125 kV<br />
28
Function description<br />
<strong>MV</strong> connections<br />
Connection<br />
b Customer connection is easily achieved outside the cradle:<br />
v on vertical copper terminals integrated in the bushing.<br />
DE60134<br />
Type tested connection configuration are shown in the Installation Guide.<br />
DE60158<br />
Field deflectors<br />
The field deflectors are to be fitted at the end of the bushings. They are necessary in<br />
case of installation of the cradle within a compartmented cubicle.<br />
For other applications, tested configurations are described in the Installation Guide.<br />
29
Evolis <strong>24</strong> kV frontal<br />
withdrawable<br />
Function description<br />
LV connections<br />
DE60155<br />
Main functions<br />
b With the basic withdrawable <strong>circuit</strong>-<strong>breaker</strong>, LV wiring is produced via an<br />
LV plug.<br />
b The LV plug includes:<br />
v the fixed part (male) fitted on the <strong>circuit</strong>-<strong>breaker</strong> and fully wired to the terminal<br />
block of the operating mechanism,<br />
v the mobile part (female) compatible with the male part.<br />
Two versions of LV plug are available<br />
b A 21-pin LV plug, allowing to connection of<br />
v a shunt opening release YO1,<br />
v a remote control mechanism (electrical motor, shunt closing release YF,<br />
antipumping relay),<br />
v the Pilot monitoring device,<br />
v maximum number of auxiliary contacts: 3 NC - 3 NO - 1 CHG<br />
(see details in chapter "Open/closed auxiliary contacts").<br />
b A 42-pin LV plug, allowing to connect<br />
v an opening release (shunt opening release or under-voltage release),<br />
v a second opening release (shunt opening release YO2, under-voltage release YN<br />
or low energy release MITOP),<br />
v a remote control mechanism (electrical motor, shunt closing release,<br />
antipumping relay)<br />
v the Pilot monitoring device,<br />
v maximum number of auxiliary contacts: 5 NC - 6 NO - 1 CHG<br />
(see details in chapter "Open/closed auxiliary contacts").<br />
b Interlocking function<br />
In order to comply with IEC standard 62271-200, an interlocking feature prevents:<br />
v racking in when the LV plug is not connected.<br />
v disconnection of the LV plug when the <strong>circuit</strong>-<strong>breaker</strong> is in racking in position.<br />
LV wiring kit<br />
b A kit including 21 wires (2 meters long) fitted with pin suitable for the plug can be<br />
supplied for connection to the LV compartment of the cubicle.<br />
This arrangement provides an auxiliary supply connection with a high level of<br />
electrical safety.<br />
30
Function description<br />
opening <strong>circuit</strong><br />
DE60161<br />
Composition<br />
b The opening <strong>circuit</strong> can be achieved by the followings units:<br />
v shunt opening release (YO1),<br />
v second shunt opening release (YO2),<br />
v under voltage release (YN),<br />
v low energy release (MITOP).<br />
(2)<br />
(1) or (3)<br />
Please check in the combination table the right associations of different releases.<br />
Note: this table is present in order form at the end of this catalogue.<br />
Shunt opening release (YO1 et YO2)<br />
b This causes the instant opening of the <strong>circuit</strong>-<strong>breaker</strong> when energised.<br />
Operating mechanism<br />
Characteristics<br />
Supply<br />
see order form<br />
Threshold VAC 0.7 to 1.1 Un<br />
VDC<br />
0.85 to 1.1 Un<br />
Consumption VAC 160 VA<br />
VDC<br />
50 W<br />
DE60094<br />
(1) Shunt opening release<br />
Under voltage release (YN)<br />
b An under voltage release operates to open the <strong>circuit</strong>-<strong>breaker</strong> when the voltage at<br />
the terminals of the release falls below 35% of its rated voltage, even if the fall is slow<br />
and gradual.<br />
On the other hand, it does not operate the <strong>circuit</strong>-<strong>breaker</strong> when the voltage at its<br />
terminals exceeds 70% of its rated supply voltage.<br />
Circuit-<strong>breaker</strong> closing is possible when the values of the voltage at the terminals of<br />
the release are greater than or equal to 85% of its rated voltage.<br />
Closing is impossible when the voltage at the terminals is lower than 35% of its<br />
rated supply voltage.<br />
DE60089<br />
(2) Under voltage release<br />
Characteristics<br />
Supply<br />
see order form<br />
Threshold opening 0.35 to 0.7 Un<br />
closing 0.85 Un<br />
Consumption pick-up VAC 400 VA<br />
VDC<br />
100 W<br />
hold VAC 100 VA<br />
VDC<br />
10 W<br />
DE60091<br />
Low energy release (MITOP)<br />
b This specific release comprises a low energy consumption unit and is used<br />
specifically with self-powered relay SEPAM 100LA ("REFLEX MODULE"), or VIP<br />
relay.<br />
(3) Low energy release<br />
Characteristics<br />
Supply<br />
Threshold<br />
direct current<br />
0.6 A < I < 3 A<br />
Any tripping caused by the Mitop release is indicated momentarily by an SDE type<br />
changeover contact.<br />
31
Evolis <strong>24</strong> kV frontal<br />
withdrawable<br />
Function description<br />
remote control<br />
Function<br />
DE60160<br />
(6)<br />
(5)<br />
b The remote control enables remote opening and closing of the <strong>circuit</strong>-<strong>breaker</strong>.<br />
(8)<br />
Composition<br />
b The remote control comprises:<br />
v electrical motor and gear reducer,<br />
v a shunt closing release (YF),<br />
v an antipumping relay,<br />
v an operation counter.<br />
(7)<br />
(9)<br />
(4)<br />
DE60093<br />
Operating mechanism<br />
(4) <strong>Electric</strong> motor and gear reducer<br />
<strong>Electric</strong> motor and gear reducer<br />
b The electrical motor arms and rearms the energy storage springs as soon as the<br />
<strong>circuit</strong>-<strong>breaker</strong> is closed. This enables instant reclosing of the device after opening.<br />
The arming lever is only used as back up control in the absence of an auxiliary<br />
voltage.<br />
M3 contact indicates end of charging.<br />
Characteristics<br />
Supply V AC 50/60 see order form<br />
V DC<br />
see order form<br />
Consumption V AC 380 VA<br />
V DC 380 W<br />
DE60151<br />
(5) Shunt closing release<br />
Shunt closing release (YF)<br />
b This causes the remote closing of the <strong>circuit</strong>-<strong>breaker</strong> when the operating<br />
mechanism is armed.<br />
Characteristics<br />
YF<br />
Supply VAC 50/60 Hz see order form<br />
VDC<br />
see order form<br />
Threshold<br />
0.85 to 1.1 Un<br />
Consumption VAC 160 VA<br />
VDC<br />
50 W<br />
DE60095<br />
Antipumping relay<br />
b The antipumping relay avoids unwanted closing and tripping within a short interval.<br />
This function gives absolute priority to the opening order and blocks closing.<br />
This prevents the device from being locked in an indefinite opening-closing cycle.<br />
(6) Antipumping relay<br />
32
Function description<br />
indication and locking / interlocking<br />
DE60087<br />
Operation counter<br />
b The operation counter is visible from the front face.<br />
It displays the number of operating cycles that the device has performed.<br />
(7) Operation counter<br />
DE60152<br />
Open/closed auxiliary contacts<br />
b The number of available contacts depends on the fitted options on the operating<br />
mechanism.<br />
(8) Auxiliary contacts<br />
b In its basic configuration, the operating mechanism of the <strong>circuit</strong>-<strong>breaker</strong><br />
comprises a total of:<br />
v 5 normally closed contacts (NC),<br />
v 6 normally open contacts (NO),<br />
v 1 changeover contact (CHG).<br />
b Use of auxiliary contacts is given in the following table:<br />
Option NC contact NO contact<br />
Remote control 1 1<br />
Shunt opening release (each) 0 1<br />
Undervoltage release 0 0<br />
Low energy release MITOP 0 0<br />
Trip <strong>circuit</strong> supervision 1 0<br />
To find out the final number of contacts available, the above quantity<br />
must be deducted from the total quantity (5 NC + 6 NO + 1 CHG) included in the<br />
<strong>circuit</strong>-<strong>breaker</strong>.<br />
(Example: a <strong>circuit</strong>-<strong>breaker</strong> equipped with a remote control and a shunt opening release<br />
has 4 NC + 4 NO + 1 CHG available contacts. With an under-voltage release instead of<br />
a shunt release, this <strong>circuit</strong>-<strong>breaker</strong> has 4 NC + 5 NO + 1CHG available contacts).<br />
b When the 21-pin LV plug is used, the maximum number of available contacts is:<br />
v 3 NC,<br />
v 3 NO,<br />
v 1 changeover.<br />
(Instead of 5NC-6NO-1CHG with the 42-pin LV plug).<br />
Contact characteristics<br />
Rated current<br />
10 A<br />
Breaking capacity AC 220 V (cos ϕ ≥ 0.3) 1 A<br />
DC 110/220 V (L/R ≤ 0.02 s) 0.3 A<br />
DE601<strong>24</strong><br />
Locking of the <strong>circuit</strong>-<strong>breaker</strong><br />
in the open position<br />
b This key lock allows the locking of the <strong>circuit</strong>-<strong>breaker</strong> in the "open" position by<br />
the means of a key.<br />
b The <strong>circuit</strong>-<strong>breaker</strong> is locked in the "open" position by blocking the opening<br />
pushbutton in the "pushed-in position".<br />
b The key lock is of Profalux or Ronis captive key type.<br />
(9) Locking kit<br />
33
Evolis <strong>24</strong> kV frontal<br />
withdrawable<br />
Function description<br />
auxiliary wiring diagram<br />
Auxiliary wiring diagram (principle)<br />
DE60123<br />
CLOSE CB<br />
OPEN CB<br />
M<br />
YF +<br />
anti-pumping<br />
PILOT<br />
YO1<br />
or<br />
YO2<br />
YM<br />
MITOP<br />
motor<br />
shunt closing<br />
+ anti-pumping<br />
system<br />
monitoring<br />
device pilot<br />
shunt<br />
opening<br />
release<br />
undervoltage<br />
release<br />
low energy<br />
release<br />
(MITOP)<br />
changeover<br />
contact<br />
NO<br />
contacts<br />
NC<br />
contacts<br />
remote control<br />
34
Dimensions<br />
230 mm phase distance<br />
DE60063<br />
230 230 163<br />
DE60065<br />
1188<br />
400<br />
473.5<br />
786<br />
288<br />
1309<br />
1400<br />
250 mm phase distance<br />
DE60064<br />
250 250 193<br />
DE60065<br />
1188<br />
400<br />
473.5<br />
886<br />
288<br />
1309<br />
1400<br />
35
Evolis <strong>24</strong> kV frontal<br />
withdrawable<br />
Offer structure<br />
DE60165<br />
DE60132<br />
Basic frontal withdrawable <strong>circuit</strong>-<strong>breaker</strong><br />
The basic frontal withdrawable <strong>circuit</strong>-<strong>breaker</strong> includes:<br />
b 6 power connections including arms and clusters<br />
b a racking truck<br />
b a manual operating mechanism (spring type)<br />
b closing and opening pushbuttons<br />
b a mechanical "open/closed" position indicator<br />
b a mechanical "charged/discharged" closing spring indicator<br />
b a shunt opening release<br />
b an "end of charging" contact<br />
b a block of auxiliary contacts<br />
b a 21-pin LV plug<br />
b an interlocking kit between the LV plug and the <strong>circuit</strong>-<strong>breaker</strong> position<br />
b antidrop function.<br />
Phase distance (mm) 230 250<br />
<strong>24</strong> kV<br />
16 kA 630 A -<br />
1250 A -<br />
2000 A -<br />
2500 A -<br />
25 kA 630 A -<br />
1250 A -<br />
2000 A -<br />
2500 A -<br />
31.5 kA 630 A -<br />
1250 A -<br />
2000 A -<br />
2500 A -<br />
Extra value for:<br />
undervoltage release (fig. 1) (instead of shunt opening release)<br />
DE60153<br />
LV plug 42-pin (fig. 2) (instead of 21 pin)<br />
Fig. 1<br />
DE60135<br />
Circuit-<strong>breaker</strong> fitted options<br />
Monitoring device<br />
Pilot module<br />
diagnosis by <strong>Schneider</strong> <strong>Electric</strong> expert<br />
DE60101<br />
Remote control<br />
remote control<br />
(electrical motor, gear reducer, shunt closing release, antipumping relay, operation counter)<br />
DE60102<br />
Second opening release<br />
DE60132<br />
DE60081<br />
shunt opening release (YO2) (fig. 1)<br />
undervoltage release (YN) (fig. 2)<br />
low energy release (MITOP) (fig. 3)<br />
Fig. 1 Fig. 2 Fig. 3<br />
DE60136<br />
Locking / interlocking<br />
open position <strong>circuit</strong>-<strong>breaker</strong> locking without lock<br />
Ronis or Profalux lock<br />
DE60092<br />
Indication<br />
operation counter<br />
36
DE60142<br />
Circuit-<strong>breaker</strong> fitted options (cond’t)<br />
Safety device<br />
operating mechanism auto discharge *<br />
230 mm phase distance <strong>circuit</strong>-<strong>breaker</strong><br />
250 mm phase distance <strong>circuit</strong>-<strong>breaker</strong><br />
* available end of 2004<br />
200295<br />
Rack-in / rack-out operation<br />
operating crank<br />
DE60084<br />
Cradle<br />
Phase distance<br />
phase distance<br />
230 mm<br />
250 mm<br />
DE55137<br />
Cradle accessories<br />
MT66049<br />
racked in/out position contacts (fig. 1)<br />
earthing sliding device (fig. 2)<br />
DE60107<br />
Fig. 1 Fig. 2<br />
DE60108<br />
LPCT tore sensor for 230 mm phase distance cradle (TLP 160)<br />
LPCT tore sensor for 250 mm phase distance cradle (TLP 190)<br />
TLP 160 TLP 190<br />
37
Evolis <strong>24</strong> kV frontal<br />
withdrawable<br />
38
Order form<br />
Only one box (ticked or filled in by<br />
the needed value) have to be considered between<br />
each horizontal line.<br />
A blue box corresponds to a non priced function.<br />
Basic frontal withdrawable <strong>circuit</strong>-<strong>breaker</strong><br />
Quantity<br />
Rated voltage Ur<br />
<strong>24</strong> kV<br />
Rated short-<strong>circuit</strong> breaking current Isc<br />
kA<br />
Rated normal current Ir<br />
A<br />
Indicators<br />
IEC standard labels and push button colours red-green red-black<br />
ANSI standard red-black red-green<br />
1st opening release (see possible choice in combination table below, 21-pin or 42-pin)<br />
shunt opening <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />
release (YO1) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />
220 Vdc<br />
undervoltage <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />
release (YN) 48 Vdc 125 Vdc 220-230 Vac (50 Hz)<br />
220 Vdc<br />
Circuit-<strong>breaker</strong> fitted options<br />
LV connection<br />
42 pin LV plug (instead of 21)<br />
Pilot monitoring device<br />
Pilot with connecting kit with LV plug without LV plug<br />
diagnosis by <strong>Schneider</strong> <strong>Electric</strong> expert (separate order)<br />
Remote control<br />
<strong>Electric</strong>al motor <strong>24</strong>… 32 Vdc 110… 127 Vdc/ac<br />
48… 60 Vdc/ac 220… 250 Vdc/ac<br />
Shunt closing release<br />
(YF) <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />
48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />
220 Vdc<br />
2nd opening release (see possible choice in combination table below)<br />
shunt opening <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />
release (YO2) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />
220 Vdc<br />
undervoltage <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />
release (YN) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />
220 Vdc<br />
low energy release (MITOP)<br />
Locking / interlocking<br />
open position CB locking<br />
Ronis<br />
Profalux<br />
Indication<br />
operation counter (already included if remote control supplied)<br />
Safety device function<br />
auto discharge (available end of 2004)<br />
Earthing<br />
earth sliding device<br />
Operation<br />
operating crank<br />
Cradle<br />
Quantity<br />
Rated current up to 1250 A above<br />
and 25 kA<br />
Cradle accessories<br />
Rack in/rack out position contact<br />
LPCT-TLP up to 1250 A above<br />
and 25 kA<br />
Combination table<br />
No LV plug or<br />
21-pin<br />
42-pin LV plug<br />
LV plug<br />
Shunt opening release YO1 1 1 1 1 1<br />
Shunt opening release YO2 1<br />
undervoltage YN 1 1 1<br />
Mitop 1 1<br />
39
Evolis <strong>24</strong> kV frontal<br />
withdrawable<br />
Separate components<br />
The following components can be<br />
ordered separately and can<br />
be adapted or replaced<br />
by the customer<br />
<strong>MV</strong> and LV connection accessories<br />
<strong>MV</strong> connection accessories<br />
200190<br />
200188<br />
clusers set (including fingers) 630-1250 A AAA10 025<br />
2500 A AAA10 026<br />
arms set 630-1250 A AAA10 022<br />
2500 A AAA10 023<br />
DE60153<br />
LV connection<br />
21 pin LV plug 630-1250 A AAA10 031<br />
42 pin LV plug 2500 A AAA10 032<br />
MT66055<br />
200354<br />
Other <strong>circuit</strong>-<strong>breaker</strong> accessories<br />
200295<br />
Accessories fitted on the cradle<br />
DE60145<br />
DE55137<br />
Fig. 1 Fig. 2 Fig. 3<br />
bus section truck 1250 A / 230 mm AAA10 061<br />
2500 A / 250 mm AAA10 062<br />
busbar earthing truck 230 mm AAA10 063<br />
250 mm AAA10 064<br />
<strong>circuit</strong>-<strong>breaker</strong> insertion slope AAA10 089<br />
operating crank for racking in/out 59449<br />
1 bushing kit for cradle (fig.1) 630 - 1250 A AAA10 016<br />
2500 A AAA10 018<br />
6 field deflectors for cradle bushings 630-1250 A AAA10 020<br />
(fig.2) 2500 A AAA10 021<br />
4 racked in/out position contacts (fig.3) 59173<br />
(to be installed in the cradle)<br />
DE60107<br />
DE60108<br />
LPCT toroidal sensor TLP 160 (up to 1250 A) AAA10 094<br />
TLP 190 (above) AAA10 095<br />
TLP 160 TLP 190<br />
DE60141<br />
Cradle without bushings<br />
phase distance 230 mm AAA10 015<br />
250 mm AAA10 017<br />
40
The following components can be<br />
ordered separately and can<br />
be adapted or replaced<br />
by the customer<br />
DE60102<br />
DE60154<br />
DE60132<br />
DE60133<br />
DE60101<br />
Accessories incorporated in the operating mechanism<br />
Shunt opening release<br />
Shunt closing release<br />
Undervoltage release<br />
<strong>Electric</strong>al motor<br />
Other accessories of the operating mechanism<br />
<strong>24</strong> Vdc AAA10 115<br />
48 Vdc AAA10 116<br />
110 Vdc AAA10 117<br />
125-127 Vdc AAA10 118<br />
220 Vdc AAA10 119<br />
110 Vac 50 Hz AAA10 120<br />
220-230 Vac 50 Hz AAA10 121<br />
120 Vac 60 Hz AAA10 122<br />
<strong>24</strong> Vdc AAA10 106<br />
48 Vdc AAA10 107<br />
110 Vdc AAA10 108<br />
125-127 Vdc AAA10 109<br />
220 Vdc AAA10 110<br />
110 Vac 50 Hz AAA10 111<br />
220-230 Vac 50 Hz AAA10 112<br />
120 Vac 60 Hz AAA10 113<br />
<strong>24</strong> Vdc AAA10 1<strong>24</strong><br />
48 Vdc AAA10 125<br />
110 Vdc AAA10 126<br />
125-127 Vdc AAA10 127<br />
220 Vdc AAA10 128<br />
110 Vac 50 Hz AAA10 129<br />
220-230 Vac 50 Hz AAA10 130<br />
120 Vac 60 Hz AAA10 131<br />
<strong>24</strong>… 32 Vdc AAA10 027<br />
48… 60 Vac/dc AAA10 028<br />
100… 127 Vac/dc AAA10 029<br />
220… 250 Vac/dc AAA10 030<br />
gear reducer AAA10 065<br />
open position <strong>circuit</strong>-<strong>breaker</strong> locking AAA10 092<br />
41
Evolis <strong>24</strong> kV frontal<br />
withdrawable<br />
Services<br />
The following components can only be adapted or replaced on<br />
site by personnel trained by <strong>Schneider</strong> <strong>Electric</strong>:<br />
b Pilot monitoring device,<br />
b remote control (incl.: motor, gear reducer, shunt closing release, antipumping<br />
relay, operation counter),<br />
b operation counter,<br />
b low energy release (MITOP),<br />
b interlocking kit between <strong>circuit</strong>-<strong>breaker</strong> position and LV plug,<br />
b racking device,<br />
b operating mechanism auto-discharge,<br />
b frontal <strong>circuit</strong>-<strong>breaker</strong> front cover.<br />
42
Evolis Pilot monitoring<br />
device<br />
Contents<br />
Function description p.44<br />
PE60053<br />
Two specific features p.44<br />
Pilot main characteristics p.44<br />
Detailed features p.44<br />
Local or remote data collection p.45<br />
Easy to install module p.45<br />
Added at any time p.45<br />
Operation and service p.45<br />
Pilot<br />
43
Evolis Pilot monitoring<br />
device<br />
Function description<br />
DE60053<br />
Fitted on the <strong>circuit</strong>-<strong>breaker</strong>,<br />
the Pilot monitors its operating<br />
conditions.<br />
The Pilot <strong>circuit</strong>-<strong>breaker</strong> monitoring device<br />
has two specific features<br />
Monitoring operating conditions<br />
The device monitors external conditions and provides alarms if they are out of the<br />
specified range.<br />
Recording <strong>circuit</strong>-<strong>breaker</strong> operating data<br />
Similarly to an aircraft black box the monitor device logs the <strong>circuit</strong>-<strong>breaker</strong>’s key data<br />
over time, allowing a diagnosis on its mechanical conditions.<br />
Pilot main characteristics<br />
DE60058<br />
YL<br />
YM<br />
Energy<br />
supply<br />
Characteristics<br />
Supply V AC 50/60 Hz 100/250 -15% to +10%<br />
V DC <strong>24</strong>/250 -30% to +10%<br />
Service temperature °C -25°C to +70°C<br />
Consumption VA or W > 3<br />
Measurement inputs V AC 50/60 Hz 100/250 -15% to +10%<br />
V DC <strong>24</strong>/250 -30% to +10%<br />
Events recording capacity 1000<br />
Conditions record capability 1000<br />
Maintenance notes record capacity<br />
256 (x 256 characters)<br />
M<br />
Communication<br />
Detailed features<br />
DE60055<br />
Aux. voltage<br />
45°C 50°C<br />
θ °C<br />
40°C 55°C<br />
N > 20000<br />
Operating<br />
I > 360j<br />
Pilot<br />
ON OK<br />
Reset alarm<br />
Monitoring operating conditions<br />
b The module continuously monitors<br />
v opening auxiliary voltage,<br />
v <strong>circuit</strong>-<strong>breaker</strong> ambient temperature,<br />
v number of operations,<br />
v time between operations,<br />
v and sends alarms if the set points are exceeded.<br />
b Alarms are visible on the front of the device and can also be transferred to<br />
the LV compartment, or supervision system.<br />
b Operating conditions are recorded: minimum and maximum values of auxiliary<br />
voltage and ambient temperature are time-tagged and stored every <strong>24</strong>h.<br />
Recording <strong>circuit</strong>-<strong>breaker</strong> data<br />
b All <strong>circuit</strong>-<strong>breaker</strong> events are time-tagged and stored (opening, closing, motor<br />
charging, energizing, voltage set point, temperature set point, number of operations,<br />
time between operations).<br />
b A <strong>circuit</strong>-<strong>breaker</strong> expert can analyse the stored data in order to check the correct<br />
mechanical functioning of the <strong>circuit</strong>-<strong>breaker</strong>, 1000 events are stored in the<br />
module.<br />
Servicing note-pad<br />
b The device incorporates this useful feature to record any information related to<br />
servicing the <strong>circuit</strong>-<strong>breaker</strong> (250x250 - character note-pad).<br />
44
Local or remote data collection<br />
PE60037<br />
DE60056<br />
RS485<br />
Ethernet network<br />
Web server<br />
Local use<br />
Alarms are displayed on the device itself.<br />
A dry contact relay collates the faults and can be wired to the low voltage<br />
compartment.<br />
A laptop user-machine Interface can be used to set parameters and to display<br />
and upload data.<br />
Aux. voltage<br />
45°C 50°C<br />
θ °C<br />
40°C 55°C<br />
N > 20000<br />
Operating<br />
I > 360j<br />
Pilot<br />
ON OK<br />
Reset alarm<br />
Remote use<br />
The monitoring device can be connected to a supervisor or concentrator<br />
for connection to the Web via a local RS485 Modbus network.<br />
The supervisor can display, process and acknowledge alarms.<br />
Data is then either processed in the supervision system or in the remote<br />
web-enabled system.<br />
Easy to install module<br />
DE60057<br />
b The module is inserted in the special housing reserved for it on the front of the<br />
<strong>circuit</strong>-<strong>breaker</strong>.<br />
This module may be added at any time<br />
during the <strong>circuit</strong>-<strong>breaker</strong>'s service life<br />
b The module may be factory-mounted within the <strong>circuit</strong>-<strong>breaker</strong>: connection and<br />
parameter setting, are done by <strong>Schneider</strong> <strong>Electric</strong>.<br />
b The module may be added after <strong>circuit</strong>-<strong>breaker</strong> commissioning: connection,<br />
parameter setting and testing, are done by a specialized service provider (<strong>Schneider</strong><br />
<strong>Electric</strong> or other).<br />
The customer is provided with the product manual and the CDrom containing the<br />
computerized manual and UMI PC software.<br />
Operation and service<br />
The "Pilot" monitoring device can be used on two levels:<br />
b Information on operating conditions.<br />
b Diagnosis of mechanical <strong>circuit</strong>-<strong>breaker</strong> conditions: performed by a <strong>circuit</strong>-<strong>breaker</strong><br />
expert (from <strong>Schneider</strong> <strong>Electric</strong>), by analyzing the recorded data.<br />
45
Note<br />
46
Note<br />
47
Note<br />
48
<strong>Schneider</strong> <strong>Electric</strong> Industries SAS<br />
Postal address<br />
<strong>MV</strong> department<br />
F-38050 Grenoble cedex 9<br />
Tel: +33 (0)4 76 57 60 60<br />
http://www.schneider-electric.com<br />
RSC Nanterre B 954 503 439<br />
As standards, specifications and designs change from time to time, please ask for confirmation of<br />
the information given in this publication.<br />
Publishing: <strong>Schneider</strong> <strong>Electric</strong> SA<br />
Technical writing: P. Andréani<br />
Design, production: HeadLines<br />
Printing: Imprimerie du Pont de Claix<br />
AMTED302014EN © 2004 <strong>Schneider</strong> <strong>Electric</strong> - All rights reserved<br />