Catalogue<br />

2004<br />

<strong>MV</strong> <strong>Vacuum</strong> <strong>circuit</strong>-<strong>breaker</strong><br />

<strong>24</strong> <strong>KV</strong>


Evolis <strong>circuit</strong>-<strong>breaker</strong><br />

A safe, easy to integrate<br />

and comprehensive range<br />

for demanding installations.<br />

b Evolis is a vacuum <strong>circuit</strong>-<strong>breaker</strong> that meets current and future standards in terms<br />

of electrical installation dependability, in compliance with standards and<br />

environmental protection.<br />

It is the quintessential expression of Merlin Gerin’s know-how.<br />

b Evolis is intended for all network applications, either new or renovation<br />

installations, for utilities companies, infrastructures, process industry and<br />

tertiary building.<br />

PE60040<br />

Evolis <strong>24</strong> kV frontal fixed<br />

PE60052<br />

Evolis <strong>24</strong> kV frontal withdrawable<br />

1


The very best of<br />

vacuum technology<br />

As a specialist in breaking technologies,<br />

Merlin Gerin took naturally an interest in<br />

vacuum breaking techniques.<br />

A major R&D investment was made to<br />

develop and engineer Evolis, providing<br />

customers with the very best of vacuum<br />

technology.<br />

Make-up of a vacuum interrupter<br />

b <strong>Vacuum</strong> interrupters basically have two electrical contacts, one fixed and the other<br />

mobile, and a sealed enclosure. The latter enables a high level of vacuum to be<br />

maintained inside the interrupter (less than 10 -2 Pa) to provide insulation between<br />

the open contacts.<br />

b The dielectric strength of the vacuum allows the contact-to-contact distance to be<br />

reduced. This short distance together with the low opening speed allow the use of a<br />

low energy control mechanism. A metal bellows provides the link between the mobile<br />

contact and the enclosure.<br />

DE60163<br />

Ceramic chamber<br />

Shield<br />

Fixed contact<br />

Mobile contact<br />

b In order to keep the vacuum level required for the correct operation of the<br />

interrupter for 30 years, the enclosure must be perfectly sealed, and the various<br />

components have to be fully degased. This is achieved by:<br />

v choosing materials that are specifically selected for this application<br />

(metals and ceramics),<br />

v choosing an appropriate assembly process (vacuum, high temperature brazing),<br />

v the use of a "getter" material to absorb the residual gas.<br />

Metal bellows<br />

Fig. 1: vacuum interrupter components<br />

Current breaking in a vacuum interrupter<br />

b In vacuum breaking, the electrical arc generated on separation of the contacts is<br />

made up of a plasma of metal vapors produced by the vaporization of the contact<br />

material.<br />

b At low values of current, these vapors very quickly condense on the shield and<br />

contacts when the arc disappears, thus allowing:<br />

v the vacuum to be re-established,<br />

v a contact-to-contact dielectric strength to be restored that is greater than<br />

the recovery voltage: breaking is then complete.<br />

DE60164<br />

Current<br />

Electrode<br />

AMF coil<br />

Contact disk<br />

Arc plasma<br />

Axial magnetic field<br />

b At high currents, the electrical arc in the vacuum switches to a concentrated mode<br />

which causes high, localized temperature rises on the contacts. The existence of<br />

these hot spots is detrimental to the quick restoring of the dielectric strength.<br />

Two techniques can be used in order to avoid this stagnation of the static<br />

concentrated arc:<br />

v the so called RMF (Radial Magnetic Field) technique, involves rotating the arc<br />

thanks to an electromagnetic effect generated by a radial magnetic field; this<br />

therefore limits contact erosion.<br />

v a more recent technique called AMF (Axial Magnetic Field) involves applying an<br />

axial magnetic field parallel to the axis of the two contacts (fig. 2) which allows a<br />

diffuse arc to be maintained (fig. 3) even at high current values. The arc energy is<br />

spread over the whole contact surface area, therefore causing very low levels of<br />

erosion.<br />

v Merlin Gerin has chosen this last technique for the Evolis range.<br />

Fig. 2: cross-section of AMF contact<br />

PE60042<br />

Fig. 3: diffuse vacuum arc AMF technology<br />

2


200110<br />

Merlin Gerin’s choices for Evolis<br />

combined with its industrial expertise<br />

provides customer with a highly reliable<br />

range of <strong>circuit</strong>-<strong>breaker</strong>s. These products<br />

are suitable for the most demanding<br />

conditions with the guarantee of full<br />

compliance with international standards.<br />

AMF technology<br />

b Evolis <strong>circuit</strong>-<strong>breaker</strong>s use AMF type vacuum interrupters.<br />

According to technical and economic optimization considerations, the axial magnetic<br />

field is generated:<br />

v either by a coil outside of the interrupter (fig. 4), for rated voltages up to 17.5 kV,<br />

v or by a coil integrated in the interrupter contact structure (fig. 5), for the <strong>24</strong> kV<br />

voltage level.<br />

b In both cases the AMF vacuum interrupters feature low arc voltages (Uarc of<br />

around 50 V) and maximum usage of the contact surface for very low contact erosion.<br />

The advantages provided<br />

b The above choices provide customers with the following advantages in<br />

<strong>MV</strong> <strong>circuit</strong>-<strong>breaker</strong> applications:<br />

v simple and compact vacuum interrupters,<br />

v high electrical endurance meaning that there is no need for contact wear<br />

inspection in normal network protection applications including highly disturbed<br />

overhead line feeders.<br />

Fig 4: 17.5 kV external coil type interrupter<br />

DE60162<br />

Fig 5: <strong>24</strong> kV internal coil type interrupter<br />

3


The very best of<br />

vacuum technology<br />

PE60062<br />

Systematic advanced control<br />

The main components of the <strong>circuit</strong>-<strong>breaker</strong>, such as vacuum interrupter and<br />

operating mechanism, are produced by <strong>Schneider</strong> <strong>Electric</strong>. The vacuum interrupters<br />

are manufactured in an ultra-modern production unit in France.<br />

During manufacture, each <strong>circuit</strong>-<strong>breaker</strong> is subjected to systematic advanced<br />

testing.<br />

<strong>Vacuum</strong> interrupter testing<br />

b The level of vacuum in each interrupter is tested using the "magnetron discharge<br />

method".<br />

<strong>Vacuum</strong> interrupter<br />

b Using this sophisticated procedure, measurement is very precise and does not<br />

require access to the inside of the interrupter, thus not affecting the airtight seal.<br />

PE60061<br />

Circuit-<strong>breaker</strong> testing<br />

b A rigorous set of tests and measurements is carried out on each <strong>circuit</strong>-<strong>breaker</strong>.<br />

b The results are reported and signed off by the quality control department on each<br />

device's test certificate to ensure product traceability.<br />

Compliance with standards<br />

b Evolis complies with IEC 62271-100.<br />

b Design and production are certified to ISO 9000 (version 2000).<br />

b Production sites are certified to ISO 14001 (environmental standard).<br />

Industrial process expertise<br />

Certification<br />

b The certificate of conformity provides guarantees that the <strong>circuit</strong>-<strong>breaker</strong>:<br />

v has been subject to type tests according to EN 45001 standards procedures in<br />

accredited laboratories by independent organizations,<br />

v is in conformity with recognized international standards<br />

b Evolis is currently being certified by external EN 45011 accredited organizations,<br />

members of the STL (Short <strong>circuit</strong> Testing Liaison)<br />

v EN 45001: general requirements for the competence of testing and calibration<br />

laboratories,<br />

v EN 45011: general requirements for bodies of operating product certification<br />

systems.<br />

Environmental care<br />

b Product design takes account of the environmental constraints described in a<br />

"Product Environment Profile" dossier (PEP).<br />

b An end-of-service-life manual details procedures for dismantling and processing<br />

components.<br />

4


General contents<br />

Evolis presentation p.6<br />

Panorama p.8<br />

Evolis <strong>24</strong> kV frontal fixed p.10<br />

Evolis <strong>24</strong> kV frontal withdrawable p.<strong>24</strong><br />

Evolis Pilot monitoring device p.43<br />

5


Evolis presentation<br />

6


DV2<br />

Ue Icu<br />

20/ 40 1 0<br />

525<br />

1 0<br />

690<br />

85<br />

cat.B Icw 85kA/1s<br />

Ics = 1 0% Icu<br />

IEC 947-2<br />

EN 60947-2<br />

(V) (kA)<br />

50/60Hz<br />

Extended products offer<br />

DE60129<br />

LV cubicle<br />

components<br />

b Mcb<br />

b protection relay<br />

b lamp<br />

b push button<br />

b terminal blocks<br />

connector<br />

Protection<br />

and control<br />

b UMI<br />

Circuit-<strong>breaker</strong><br />

b pilot<br />

b cradle<br />

Metering<br />

b VPIS<br />

b PM500<br />

UTE VDE BS CEI UNE AS NEMA<br />

Instrument<br />

transformer<br />

<strong>MV</strong> cubicle<br />

components<br />

b capacitor insulator<br />

b earthing switch<br />

b heating resistor<br />

b voltage presence<br />

indicator<br />

b crank<br />

b extraction table<br />

7


DV2<br />

(V) (kA)<br />

Ue Icu<br />

20/ 40<br />

525 1 0<br />

690 85<br />

cat.B Icw 85kA/1s<br />

Ics = 1 0% Icu<br />

IEC 947-2<br />

EN 60947-2<br />

50/60Hz<br />

UTE VDE BS CEI UNE AS NEMA<br />

DV2<br />

Ue Icu<br />

20/ 40 1 0<br />

525<br />

1 0<br />

690<br />

85<br />

cat.B Icw 85kA/1s<br />

Ics = 1 0% Icu<br />

IEC EN 60947-2<br />

(V) (kA)<br />

50/60Hz<br />

UTE VDE BS CEI UNE AS NEMA<br />

Panorama<br />

Evolis 7.2… 17.5 kV frontal<br />

Fixed<br />

Withdrawable<br />

RATED VOLTAGE<br />

kV<br />

kV<br />

kV<br />

PHASE DISTANCE<br />

from 145 to <strong>24</strong>0 mm<br />

RATED SHORT CIRCUIT CURRENT<br />

from 25 to 40 kA<br />

RATED CURRENT<br />

from 630 to 2500 A<br />

separate catalogue<br />

8


MERLIN GERIN<br />

Sepam<br />

on<br />

ext<br />

1 >51 1o >51 0 o f I on Trip<br />

1 > 51 1o > 51<br />

I1 = 165A RMS<br />

I2 = 166A RMS<br />

I3 = 167A RMS<br />

Evolis <strong>24</strong> kV frontal<br />

Protection<br />

and control<br />

Metering<br />

Instrument<br />

transformers<br />

Cubicle<br />

components<br />

Fixed Withdrawable v SEPAM series 20<br />

for common<br />

applications<br />

Pilot option checks that the<br />

<strong>circuit</strong>-<strong>breaker</strong> is in a good<br />

working order<br />

Pilot option checks that the<br />

<strong>circuit</strong>-<strong>breaker</strong> is in a good<br />

working order<br />

v PM450,<br />

PM500 for<br />

basic metering<br />

v LPCT<br />

compatible with<br />

Sepam relay<br />

v Earthing switch<br />

v Insulators<br />

v Potential tester<br />

v Bus section truck<br />

v SEPAM series 40 v PM800 Series v CT v Bus section<br />

for demanding for advanced compatible with v Circuit-<strong>breaker</strong><br />

applications metering Sepam relay extraction table<br />

v Crank<br />

Web accessible Web accessible v SEPAM series 80 v CM3000, v VT v Voltage<br />

RATED VOLTAGE for complete CM4000 Series compatible with indication<br />

kV<br />

applications for Sepam relay v Transparent<br />

comprehensive<br />

metering and<br />

power quality<br />

analysis<br />

screen<br />

v Insulator support<br />

PHASE DISTANCE<br />

from 230 to 250 mm<br />

RATED SHORT CIRCUIT CURRENT<br />

from 16 to 31.5 kA<br />

RATED CURRENT<br />

from 630 to 2500 A<br />

separate catalogues<br />

9


Evolis <strong>24</strong> kV frontal<br />

fixed<br />

10


Contents<br />

Main characteristics presentation p.12<br />

PE60040<br />

Function description p.13<br />

<strong>MV</strong> connections p.13<br />

LV connections p.14<br />

Opening <strong>circuit</strong> p.15<br />

Remote control p.16<br />

Indication and locking / interlocking p.17<br />

Auxiliary wiring diagram p.18<br />

Fixed version<br />

Dimensions p.19<br />

Offer structure p.20<br />

Order form p.21<br />

Separate components p.22<br />

Services p.23<br />

11


Evolis <strong>24</strong> kV frontal<br />

fixed<br />

Main characteristics presentation<br />

A fully assembled and tested unit<br />

b Evolis <strong>circuit</strong>-<strong>breaker</strong>s are actuated by a spring operated mechanism that ensures<br />

operating speeds independent of operator action and can be operated without any<br />

auxiliary supply.<br />

When the operating mechanism is motorized, the <strong>circuit</strong>-<strong>breaker</strong> can take on remote<br />

control functions and perform re-closing cycles.<br />

b This unit is easy to integrate in a cubicle environment. An Installation Guide<br />

explains the necessary operations in detail.<br />

DE60047<br />

D<br />

W<br />

H<br />

<strong>Electric</strong>al characteristics according to IEC 62271-100<br />

Phase distance (mm) 230 250 250<br />

Rated voltage <strong>24</strong> kV Isc In<br />

16 kA 630 A b v<br />

1250 A b v<br />

2000 A v<br />

2500 A v<br />

25 kA 630 A b v<br />

1250 A b v<br />

2000 A v<br />

2500 A v<br />

31.5 kA 630 A v<br />

1250 A v<br />

2000 A v<br />

2500 A v<br />

v available end of 2004<br />

Dimensions (mm)<br />

Weight (kg)<br />

D 593 593 593<br />

H 712.5 712.5 712.5<br />

W 655 730 745<br />

97 97 135<br />

Additional characteristics according to IEC 62271-100<br />

Rated values<br />

Voltage Ur kV rms <strong>24</strong><br />

Insulation voltage:<br />

power frequency withstand voltage Ud kV rms 50<br />

lightning impulse withstand voltage Up kV peak 125<br />

Frequency fr Hz 50-60<br />

Short time withstand current Ik/tk kA Isc/3s<br />

Peak withstand current Ip kA peak 2.5 & 2.6 Isc<br />

Short <strong>circuit</strong> making current kA peak 2.5 & 2.6 Isc<br />

Other characteristics<br />

Operating sequences<br />

O-3min-CO-3min-CO<br />

O-0.3s-CO-3min-CO<br />

O-0.3s-CO-15s-CO<br />

Mechanical endurance class M2<br />

number of operations 10 000<br />

<strong>Electric</strong>al endurance class E2<br />

Number of operations at full Isc value 16 kA 50<br />

25 kA 50<br />

31.5 kA 50<br />

Capacitive current breaking class C1-C2 (for some applications)<br />

Service conditions -25°C to 40°C<br />

Humidity:<br />

average relative humidity <strong>24</strong>-hours period < 95%<br />

1 month < 90%<br />

12


Function description<br />

<strong>MV</strong> connections<br />

Connection<br />

b The basic <strong>circuit</strong>-<strong>breaker</strong> is fitted with drilled copper terminal pads.<br />

Customer connection is easily achieved outside the <strong>circuit</strong>-<strong>breaker</strong> on these vertical<br />

terminal pads.<br />

DE60126<br />

Type tested configurations of connections are shown in the Installation Guide.<br />

13


Evolis <strong>24</strong> kV frontal<br />

fixed<br />

Function description<br />

LV connections<br />

Two solutions for connections<br />

DE60143<br />

without LV Plug<br />

with LV plug<br />

b The basic fixed <strong>circuit</strong>-<strong>breaker</strong> LV wiring can be connected directly to the terminal<br />

block of the operating mechanism, through a cable protection duct.<br />

b An LV plug can be fitted as an option. It includes:<br />

v the fixed part (male) fitted on the <strong>circuit</strong>-<strong>breaker</strong> and fully wired to the terminal<br />

block of the operating mechanism,<br />

v the mobile part (female) compatible with the male part.<br />

DE60149<br />

Low voltage connections<br />

Two versions of LV plug are available<br />

b A 21-pin LV plug, allowing connection of:<br />

v a shunt opening release YO1,<br />

v a remote control mechanism (electrical motor, shunt closing release YF,<br />

antipumping relay),<br />

v the monitoring device Pilot,<br />

v maximum number of auxiliary contacts: 3 NC - 3 NO - 1 CHG,<br />

(see details in chapter "Open/closed auxiliary contacts").<br />

b A 42-pin LV plug, allowing connection of:<br />

v an opening release (shunt opening release or undervoltage release),<br />

v a second opening release (shunt opening release YO2 or undervoltage release YN<br />

or low energy release MITOP),<br />

v a remote control mechanism (electrical motor, shunt closing release, antipumping<br />

relay),<br />

v the monitoring device Pilot,<br />

v maximum number of auxiliary contacts: 5 NC - 6 NO - 1 CHG,<br />

(see details in chapter "Open/closed auxiliary contacts").<br />

LV plug connections<br />

LV wiring kit<br />

A kit including 21 wires (2 meters long) fitted with pin suitable for the plug can be<br />

supplied for connection to the LV compartment of the cubicle.<br />

Interlocking kit<br />

For withdrawble applications, an interlocking kit is available. This kit facilitates<br />

the interlocking between the LV plug (connected/disconnected) and the open/closed<br />

position of the <strong>circuit</strong>-<strong>breaker</strong> (as required by the IEC standard 62271-200).<br />

This arrangement provides an auxiliary supply connection with a high level of<br />

electrical safety.<br />

14


Function description<br />

opening <strong>circuit</strong><br />

DE60161<br />

Composition<br />

b The opening <strong>circuit</strong> can be produced using the followings units:<br />

v shunt opening release (YO1),<br />

v second shunt opening release (YO2),<br />

v undervoltage release (YN),<br />

v low energy release (MITOP).<br />

(2)<br />

(1) or (3)<br />

Please check in the combination table the right associations of different releases.<br />

Note: this table is present in order form at the end of this catalogue.<br />

Shunt opening release (YO1 and YO2)<br />

b This causes instant opening of the <strong>circuit</strong>-<strong>breaker</strong> when energised.<br />

Characteristics<br />

Supply<br />

see order form<br />

Threshold VAC 0.7 to 1.1 Un<br />

VDC<br />

0.85 to 1.1 Un<br />

Consumption VAC 160 VA<br />

VDC<br />

50 W<br />

DE60094<br />

(1) Shunt opening release<br />

Undervoltage release (YN)<br />

b An Undervoltage release operates to open the <strong>circuit</strong>-<strong>breaker</strong> when the voltage at<br />

the terminals of the release falls below 35% of its rated voltage, even if the fall is slow<br />

and gradual.<br />

On the other hand, it does not operate the <strong>circuit</strong>-<strong>breaker</strong> when the voltage at its<br />

terminals exceeds 70% of its rated supply voltages.<br />

Circuit-<strong>breaker</strong> closing is possible when the values of the voltage at the terminals of<br />

the release are greater than or equal to 85% of its rated voltage.<br />

Closing is impossible when the voltage at the terminals is lower than 35% of its<br />

rated supply voltage.<br />

DE60089<br />

(2) Undervoltage release<br />

Characteristics<br />

Supply<br />

see order form<br />

Threshold opening 0.35 to 0.7 Un<br />

closing 0.85 Un<br />

Consumption pick-up VAC 400 VA<br />

VDC<br />

100 W<br />

hold VAC 100 VA<br />

VDC<br />

10 W<br />

DE60091<br />

Low energy release (MITOP)<br />

b This specific release comprises a low energy consumption unit and is used<br />

specifically with self-powered relay SEPAM 100LA ("REFLEX MODULE"), or VIP<br />

relay.<br />

(3) Low energy release<br />

Characteristics<br />

Supply<br />

Threshold<br />

direct current<br />

0.6 A < I < 3 A<br />

Any tripping caused by the Mitop release is indicated momentarily by an SDE type<br />

changeover contact.<br />

15


Evolis <strong>24</strong> kV frontal<br />

fixed<br />

Function description<br />

remote control<br />

Function<br />

DE60160<br />

(6)<br />

(5)<br />

b The remote control enables remote opening and closing of the <strong>circuit</strong>-<strong>breaker</strong>.<br />

(8)<br />

Composition<br />

b The remote control comprises:<br />

v electrical motor and gear reducer,<br />

v a shunt closing release (YF),<br />

v an antipumping relay,<br />

v an operation counter.<br />

(7)<br />

(9)<br />

(4)<br />

DE60093<br />

Operating mechanism<br />

Ì<br />

<strong>Electric</strong> motor and gear reducer<br />

b The electrical motor arms and rearms the energy storage springs as soon as the<br />

<strong>circuit</strong>-<strong>breaker</strong> is closed. This enables instant reclosing of the device after opening.<br />

The arming lever is only used as back up control in the absence of an auxiliary<br />

voltage.<br />

M3 contact indicates end of charging.<br />

(4) <strong>Electric</strong> motor and gear reducer<br />

Characteristics<br />

Supply VAC 50/60 see order form<br />

VDC<br />

see order form<br />

Consumption VAC 380 VA<br />

VDC 380 W<br />

DE60094<br />

Shunt closing release (YF)<br />

b This causes the remote closing of the <strong>circuit</strong>-<strong>breaker</strong> when the operating<br />

mechanism is armed.<br />

(5) Shunt closing release<br />

Characteristics<br />

YF<br />

Supply VAC 50/60 Hz see order form<br />

VDC<br />

see order form<br />

Threshold<br />

0.85 to 1.1 Un<br />

Consumption VAC 160 VA<br />

VDC<br />

50 W<br />

DE60095<br />

Antipumping relay<br />

b The antipumping relay avoids unwanted closing and tripping within a short interval.<br />

This function gives absolute priority to the opening order and blocks closing.<br />

This prevents the device from being locked in an indefinite opening-closing cycle.<br />

(6) Antipumping relay<br />

16


Function description<br />

indication and locking / interlocking<br />

DE60087<br />

Operation counter<br />

b The operation counter is visible from the front face.<br />

It displays the number of operating cycles that the device has performed.<br />

(7) Operation counter<br />

DE60152<br />

Open/closed auxiliary contacts<br />

b The number of available contacts depends on the fitted options on the operating<br />

mechanism.<br />

(8) Auxiliary contacts<br />

b In its basic configuration, the operating mechanism of the <strong>circuit</strong>-<strong>breaker</strong><br />

comprises a total of:<br />

v 5 normally closed contacts (NC),<br />

v 6 normally open contacts (NO),<br />

v 1 changeover contact (CHG).<br />

b Use of auxiliary contacts is given in the following table:<br />

Option NC contact NO contact<br />

Remote control 1 1<br />

Shunt opening release (each) 0 1<br />

Undervoltage release 0 0<br />

Low energy release MITOP 0 0<br />

Trip <strong>circuit</strong> supervision 1 0<br />

To find out the final number of contacts available, the above quantity must be<br />

deducted from the total quantity (5 NC + 6 NO + 1 CHG) included in the <strong>circuit</strong><strong>breaker</strong>.<br />

(Example: a <strong>circuit</strong>-<strong>breaker</strong> equipped with a remote control and a shunt opening release<br />

has 4 NC + 4 NO + 1 CHG available contacts. With an undervoltage release instead of<br />

a shunt release, this <strong>circuit</strong>-<strong>breaker</strong> has 4 NC + 5 NO + 1CHG available contacts).<br />

b When the 21-pin LV plug is used (for withdrawable applications), the maximum<br />

number of available contacts is:<br />

v 3 NC,<br />

v 3 NO,<br />

v 1 changeover.<br />

(Instead of 5NC-6NO-1CHG with the 42-pin LV plug).<br />

Contact characteristics<br />

Rated current<br />

10 A<br />

Breaking capacity AC 220 V (cos ϕ ≥ 0.3) 1 A<br />

DC 110/220 V (L/R ≤ 0.02 s) 0.3 A<br />

DE601<strong>24</strong><br />

Locking of the <strong>circuit</strong>-<strong>breaker</strong><br />

in the open position<br />

b This key lock allows the locking of the <strong>circuit</strong>-<strong>breaker</strong> in the "open" position by the<br />

means of a key.<br />

b The <strong>circuit</strong>-<strong>breaker</strong> is locked in the "open" position by blocking the opening<br />

pushbutton in the "pushed-in position".<br />

b The key lock is of Profalux or Ronis captive key type.<br />

(9) Locking kit<br />

17


Evolis <strong>24</strong> kV frontal<br />

fixed<br />

Function description<br />

auxiliary wiring diagram<br />

Auxiliary wiring diagram (principle)<br />

DE60123<br />

CLOSE CB<br />

OPEN CB<br />

M<br />

YF +<br />

anti-pumping<br />

PILOT<br />

YO1<br />

or<br />

YO2<br />

YM<br />

MITOP<br />

motor<br />

shunt closing<br />

+ anti-pumping<br />

system<br />

monitoring<br />

device pilot<br />

shunt<br />

opening<br />

release<br />

undervoltage<br />

release<br />

low energy<br />

release<br />

(MITOP)<br />

changeover<br />

contact<br />

NO<br />

contacts<br />

NC<br />

contacts<br />

remote control<br />

18


Dimensions<br />

3 sizes of width<br />

DE60060<br />

D<br />

D<br />

97.5<br />

DE60062<br />

712.5<br />

W<br />

593<br />

Dimensions (mm)<br />

Phase distance 230 250 250<br />

D W D W D W<br />

16 kA 630 A b 655 b 734<br />

1250 A b 655 b 734<br />

2000 A b 745<br />

2500 A b 745<br />

25 kA 630 A b 655 b 734<br />

1250 A b 655 b 734<br />

2000 A b 745<br />

2500 A b 745<br />

31.5 kA 630 A b 745<br />

1250 A b 745<br />

2000 A b 745<br />

2500 A b 745<br />

19


Evolis <strong>24</strong> kV frontal<br />

fixed<br />

Offer structure<br />

DE60080<br />

DE60132<br />

Basic frontal fixed <strong>circuit</strong>-<strong>breaker</strong><br />

The basic frontal fixed <strong>circuit</strong>-<strong>breaker</strong> includes:<br />

b a manual operating mechanism (spring type),<br />

b closing and opening pushbuttons,<br />

b a mechanical "open/closed" position indicator,<br />

b a mechanical "charged/discharged" closing spring indicator,<br />

b a shunt opening release,<br />

b an "end of charging" contact,<br />

b a block of auxiliary contacts.<br />

Phase distance (mm) 230 250<br />

<strong>24</strong> kV<br />

16 kA 630 A<br />

1250 A<br />

2000 A -<br />

2500 A -<br />

25 kA 630 A<br />

1250 A<br />

2000 A -<br />

2500 A -<br />

31.5 kA 630 A -<br />

1250 A -<br />

2000 A -<br />

2500 A -<br />

Extra value for:<br />

undervoltage release (instead of shunt opening release)<br />

DE60153<br />

Circuit-<strong>breaker</strong> fitted options<br />

LV connection<br />

21-pin LV plug<br />

42-pin LV plug<br />

DE60135<br />

Monitoring device<br />

Pilot module<br />

diagnosis by <strong>Schneider</strong> <strong>Electric</strong> expert<br />

DE60101<br />

Remote control<br />

remote control<br />

(electrical motor, gear reducer, shunt closing release, antipumping relay, operation counter)<br />

DE60102<br />

Second opening release<br />

DE60132<br />

DE60081<br />

shunt opening release (YO2) (fig. 1)<br />

undervoltage release (YN) (fig. 2)<br />

low energy release (MITOP) (fig. 3)<br />

Fig. 1 Fig. 2 Fig. 3<br />

DE60136<br />

Locking / interlocking<br />

open position <strong>circuit</strong>-<strong>breaker</strong> locking without lock<br />

Ronis or Profalux lock<br />

DE60092<br />

Indication<br />

operation counter<br />

20


Order form<br />

Only one box (ticked or filled in by<br />

the needed value) have to be considered between<br />

each horizontal line.<br />

A blue box corresponds to a non priced function.<br />

Basic frontal fixed <strong>circuit</strong>-<strong>breaker</strong><br />

Quantity<br />

Rated voltage Ur<br />

<strong>24</strong> kV<br />

Rated short-<strong>circuit</strong> breaking current Isc<br />

kA<br />

Rated normal current Ir<br />

A<br />

Phase distance (mm) 230 250<br />

Indicators<br />

IEC standard labels and push button colours red-black red-green<br />

ANSI standard red-black red-green<br />

1st opening release (see possible choice in combination table below)<br />

shunt opening <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />

release (YO1) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />

220 Vdc<br />

undervoltage <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />

release (YN) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />

220 Vdc<br />

Circuit-<strong>breaker</strong> fitted options<br />

LV connection<br />

21 pin LV plug 42 pin LV plug<br />

Pilot monitoring device<br />

Pilot with connecting kit with LV plug without LV plug<br />

diagnosis by <strong>Schneider</strong> <strong>Electric</strong> expert (separate order)<br />

Remote control<br />

<strong>Electric</strong>al motor <strong>24</strong>… 32 Vdc 110… 127 Vdc/ac<br />

48… 60 Vdc/ac 220… 250 Vdc/ac<br />

Shunt closing release<br />

(YF)<br />

<strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />

48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />

220 Vdc<br />

2nd opening release (see possible choice in combination table below)<br />

shunt opening <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />

release (YO2) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />

220 Vdc<br />

undervoltage <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />

release (YN) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />

220 Vdc<br />

low energy release (MITOP)<br />

Locking / interlocking<br />

open position CB locking<br />

Ronis<br />

Profalux<br />

Indication<br />

operation counter (already included if remote control supplied)<br />

Combination table<br />

No LV plug or<br />

21-pin<br />

42-pin LV plug<br />

LV plug<br />

Shunt opening release YO1 1 1 1 1 1<br />

Shunt opening release YO2 1<br />

undervoltage YN 1 1 1<br />

Mitop 1 1<br />

21


Evolis <strong>24</strong> kV frontal<br />

fixed<br />

Separate components<br />

DE60102<br />

DE60154<br />

DE60132<br />

DE60133<br />

DE60101<br />

The following components can be<br />

ordered separately and can be adapted<br />

or replaced by the customer<br />

Accessories incorporated in the operating mechanism<br />

Shunt opening release<br />

Shunt closing release<br />

Undervoltage release<br />

<strong>Electric</strong>al motor<br />

Other accessories of the operating mechanism<br />

DE60136<br />

<strong>24</strong> Vdc AAA10 115<br />

48 Vdc AAA10 116<br />

110 Vdc AAA10 117<br />

125-127 Vdc AAA10 118<br />

220 Vdc AAA10 119<br />

110 Vac 50 Hz AAA10 120<br />

220-230 Vac 50 Hz AAA10 121<br />

120 Vac 60 Hz AAA10 122<br />

<strong>24</strong> Vdc AAA10 106<br />

48 Vdc AAA10 107<br />

110 Vdc AAA10 108<br />

125-127 Vdc AAA10 109<br />

220 Vdc AAA10 110<br />

110 Vac 50 Hz AAA10 111<br />

220-230 Vac 50 Hz AAA10 112<br />

120 Vac 60 Hz AAA10 113<br />

<strong>24</strong> Vdc AAA10 1<strong>24</strong><br />

48 Vdc AAA10 125<br />

110 Vdc AAA10 126<br />

125-127 Vdc AAA10 127<br />

220 Vdc AAA10 128<br />

110 Vac 50 Hz AAA10 129<br />

220-230 Vac 50 Hz AAA10 130<br />

120 Vac 60 Hz AAA10 131<br />

<strong>24</strong>… 32 Vdc AAA10 027<br />

48… 60 Vac/dc AAA10 028<br />

100… 127 Vac/dc AAA10 029<br />

220… 250 Vac/dc AAA10 030<br />

gear reducer AAA10 065<br />

open position <strong>circuit</strong>-<strong>breaker</strong> locking AAA10 092<br />

DE60153<br />

200188<br />

<strong>MV</strong> and LV connection accessories<br />

<strong>MV</strong> connection accessories<br />

LV connection<br />

200190<br />

clusters set (including fingers) 630-1250 A AAA10 025<br />

2500 A AAA10 026<br />

arms set 630-1250 A AAA10 022<br />

2500 A AAA10 023<br />

21-pin LV plug AAA10 031<br />

42-pin LV plug AAA10 032<br />

LV connection kit (21 wires) 59117<br />

22


Services<br />

The following components can only be adapted or replaced on<br />

site by personnel trained by <strong>Schneider</strong> <strong>Electric</strong>:<br />

b Pilot monitoring device,<br />

b remote control (incl.: motor, gear train, shunt closing release, antipumping relay,<br />

operation counter),<br />

b operation counter,<br />

b low energy release (MITOP),<br />

b interlocking kit between <strong>circuit</strong>-<strong>breaker</strong> position and LV plug,<br />

b racking device,<br />

b operating mechanism auto-discharge,<br />

b frontal <strong>circuit</strong>-<strong>breaker</strong> front cover.<br />

23


Evolis <strong>24</strong> kV frontal<br />

withdrawable<br />

<strong>24</strong>


Contents<br />

Main characteristics presentation p.26<br />

PE60041<br />

Function description p.27<br />

Racking in p.27<br />

LPCT sensors p.28<br />

<strong>MV</strong> connections p.29<br />

LV connections p.30<br />

Opening <strong>circuit</strong> p.31<br />

Remote control p.32<br />

Indication and locking / interlocking p.33<br />

Auxiliary wiring diagram p.34<br />

Dimensions p.35<br />

Offer structure p.36<br />

Withdrawable version<br />

Order form p.39<br />

Separate components p.40<br />

Services p.42<br />

25


Evolis <strong>24</strong> kV frontal<br />

withdrawable<br />

Main characteristics presentation<br />

A fully assembled and tested unit<br />

b Evolis <strong>circuit</strong>-<strong>breaker</strong>s are actuated by a spring operated mechanism that ensures<br />

operating speed independent of operator action and can be operated without any<br />

auxiliary supply.<br />

When the operating mechanism is motorized, the <strong>circuit</strong>-<strong>breaker</strong> can take on remote<br />

control functions and perform re-closing cycles.<br />

b This unit is easy to integrate in a cubicle environment. An Installation Guide<br />

explains the necessary operations in detail.<br />

b This withdrawable unit comprises the <strong>circuit</strong>-<strong>breaker</strong>, arms and clusters, racking<br />

truck and its cradle. The cradle and the <strong>circuit</strong>-<strong>breaker</strong> can be ordered and delivered<br />

separately.<br />

DE60049<br />

D<br />

W<br />

H<br />

<strong>Electric</strong>al characteristics according to IEC 62271-100<br />

Phase distance (mm) 230 250<br />

Rated voltage <strong>24</strong> kV Isc In<br />

16 kA 630 A b<br />

1250 A b<br />

2000 A v<br />

2500 A v<br />

25 kA 630 A b<br />

1250 A b<br />

2000 A v<br />

2500 A v<br />

31.5 kA 630 A v<br />

1250 A v<br />

2000 A v<br />

2500 A v<br />

v available end of 2004<br />

Dimensions (mm)<br />

D 1309 1309<br />

H 1188 1188<br />

W 786 886<br />

Weight (Kg)<br />

Circuit-<strong>breaker</strong> 145 206<br />

Cradle 136 148<br />

Additional characteristics according to IEC 62271-100<br />

Rated values<br />

Voltage Ur kV rms <strong>24</strong><br />

Insulation voltage:<br />

power frequency withstand voltage Ud kV rms 50<br />

lightning impulse withstand voltage Up kV peak 125<br />

Frequency fr Hz 50-60<br />

Short time withstand current Ik/tk kA Isc/3s<br />

Peak withstand current Ip kA peak 2.5 & 2.6 Isc<br />

Short <strong>circuit</strong> making current kA peak 2.5 & 2.6 Isc<br />

Other characteristics<br />

Operating sequences<br />

O-3min-CO-3min-CO<br />

O-0.3s-CO-3min-CO<br />

O-0.3s-CO-15s-CO<br />

Mechanical endurance class M2<br />

number of operations 10 000<br />

<strong>Electric</strong>al endurance class E2<br />

Number of operations at full Isc value 16 kA 50<br />

25 kA 50<br />

31.5 kA 50<br />

Capacitive current breaking class C1-C2 (for some applications)<br />

Service conditions -25°C to 40°C<br />

Humidity:<br />

average relative humidity <strong>24</strong>-hours period < 95%<br />

1 month < 90%<br />

26


Function description<br />

racking in<br />

DE60114<br />

2000148<br />

200149<br />

200128<br />

Service position<br />

Test position<br />

Extracted position<br />

Composition<br />

b The "racking in" function is provided by:<br />

v the racking truck supporting the <strong>circuit</strong>-<strong>breaker</strong> (mobile part),<br />

v the cradle including the bushings (fixed part),<br />

v the LV plug.<br />

Operating procedure<br />

b The <strong>circuit</strong>-<strong>breaker</strong> moves through 3 stable positions:<br />

v service position:<br />

<strong>circuit</strong>-<strong>breaker</strong> racked in and locked in place; low voltage plug connected,<br />

v test position:<br />

<strong>circuit</strong>-<strong>breaker</strong> racked out and locked in place; low voltage plug connected,<br />

v extracted position:<br />

the <strong>circuit</strong>-<strong>breaker</strong> can be unlocked and extracted from the cubicle,<br />

with no interlocking.<br />

Safety functions<br />

A propulsive system combined with a screw-shaft makes racking in and racking out<br />

easier.<br />

b Interlocking<br />

In accordance with IEC standards 62271-100 and 62271-200, the following<br />

interlockings are provided:<br />

v racking in or out are impossible unless the <strong>circuit</strong>-<strong>breaker</strong> is in the open position,<br />

v racking in the <strong>circuit</strong>-<strong>breaker</strong> is impossible unless the LV plug is connected,<br />

v disconnecting the LV plug is impossible unless the <strong>circuit</strong>-<strong>breaker</strong> is racked out.<br />

In addition the truck is equipped with a device that allows <strong>circuit</strong>-<strong>breaker</strong> racking in<br />

to be interlocked with the cubicle door (which must be specially designed):<br />

v It is only possible to rack in the <strong>circuit</strong>-<strong>breaker</strong> if the door is closed,<br />

v the door can only be opened with the <strong>circuit</strong>-<strong>breaker</strong> racked out.<br />

b Earthing is achieved throughout the whole racking in operation by the mean of the<br />

wheels of the racking truck. Additional earthing device can be supplied as an option.<br />

b Protective shutters on the cradle prevent access to the racking fingers when the<br />

device is extracted (protection index: IP2X).<br />

b For maintenance or test purposes, it is possible to:<br />

v padlock the shutters in the closed position,<br />

v unlock the shutters mechanism to access the fixed contacts, and insert a screen<br />

to prevent the lived set of fixed contacts being exposed.<br />

DE60138<br />

b A fool-proof protection enables cradle and <strong>circuit</strong>-<strong>breaker</strong> to be matched up.<br />

This system is mounted on the <strong>circuit</strong>-<strong>breaker</strong>. Part of it has to be assembled by<br />

the panel builder on the cradle side.<br />

b Earthing switch<br />

It can be fixed on the cradle, allowing proper interlocking between the <strong>circuit</strong>-<strong>breaker</strong><br />

and the earthing switch, (see detailed description in "Earthing switch and cubicle<br />

components" catalogue).<br />

DE55137<br />

Auto-discharge function<br />

Racked in/out position<br />

MT66049<br />

Earthing sliding device<br />

b Anti-drop function<br />

This function ensures the safety of the operator during the extraction of the<br />

<strong>circuit</strong>-<strong>breaker</strong>.<br />

Accessories<br />

b 4 racked in/racked out position contacts.<br />

b Additional earthing device (copper brush).<br />

b Core sensors LPCT type, directly fitted on the bushings of the cradle.<br />

b Auto-discharge function:<br />

the spring of the <strong>circuit</strong>-<strong>breaker</strong> operating mechanism is automatically discharged<br />

when the <strong>circuit</strong>-<strong>breaker</strong> is extracted from the cubicle. This feature avoids<br />

unexpected closing of the <strong>circuit</strong>-<strong>breaker</strong>.<br />

27


Evolis <strong>24</strong> kV frontal<br />

withdrawable<br />

Function description<br />

LPCT sensors<br />

The LPCT’s are the best way to increase<br />

the effectiveness of the protection chain<br />

and simplify the selection.<br />

Function<br />

b These Low Power Current Transducers (LPCT) provide accurate current<br />

measurement to the protection function when an Evolis <strong>circuit</strong>-<strong>breaker</strong> is associated<br />

with the Sepam relay range.<br />

DE60099<br />

LPCT for bushings (TLP Type)<br />

b They comply with IEC 60044-8 standard.<br />

Composition<br />

b Two types of LPCT are available:<br />

v LPCT for bushings,<br />

v LPCT for cubicles.<br />

b The sensor is delivered with 5m of cable and connector that allows direct<br />

connection to the Sepam unit.<br />

DE60097<br />

LPCT for cubicle (CLP Type)<br />

Mechanical characteristics<br />

(LPCT for bushings)<br />

b Mounted directly on the Evolis withdrawable <strong>circuit</strong>-<strong>breaker</strong> cradle.<br />

The sensors are simply located on the bushings and fixed using three screws.<br />

Each sensor covers the full operating range of the corresponding <strong>circuit</strong>-<strong>breaker</strong>.<br />

b Connection to the Sepam is achieved using an shielded cable which is attached to<br />

each sensor.<br />

<strong>Electric</strong>al characteristics<br />

b In compliance with IEC 60044-8 standard, defining Low Power current Transducer<br />

with voltage output.<br />

b Usable for nominal currents of 25 A to 2500 A.<br />

b Class 0.5 throughout the range.<br />

b Current sensors deliver a voltage output at a ratio of 100 A/22.5 mV.<br />

Common features<br />

Rated primary current<br />

100 A<br />

Rated secondary output (at 100A)<br />

22.5 mV<br />

Accuracy class for measuring 0.5<br />

Accuracy class for protection<br />

5P<br />

Burden<br />

2 kΩ<br />

Frequency<br />

50 / 60 Hz<br />

Specific features CLP2 CLP3 TLP160 TLP190<br />

Assembly In the cubicle In the cubicle On the bushings On the bushings<br />

DE60097<br />

DE60098<br />

DE60099<br />

DE60100<br />

Rated extended primary current 1250 A 2500 A 1250 A 2500 A<br />

Accuracy limit factor 250 315 250 315<br />

Rated short time thermal current 25 kA / 3s 31.5 kA / 3s 25 kA / 3s 31.5 kA / 3s<br />

Highest voltage for equipment <strong>24</strong> kV <strong>24</strong> kV 0.72 kV 0.72 kV<br />

Rated power frequency withstand volt. 50 kV 50 kV 3 kV 3 kV<br />

Rated lighting inpulse withstand voltage 125 kV 125 kV<br />

28


Function description<br />

<strong>MV</strong> connections<br />

Connection<br />

b Customer connection is easily achieved outside the cradle:<br />

v on vertical copper terminals integrated in the bushing.<br />

DE60134<br />

Type tested connection configuration are shown in the Installation Guide.<br />

DE60158<br />

Field deflectors<br />

The field deflectors are to be fitted at the end of the bushings. They are necessary in<br />

case of installation of the cradle within a compartmented cubicle.<br />

For other applications, tested configurations are described in the Installation Guide.<br />

29


Evolis <strong>24</strong> kV frontal<br />

withdrawable<br />

Function description<br />

LV connections<br />

DE60155<br />

Main functions<br />

b With the basic withdrawable <strong>circuit</strong>-<strong>breaker</strong>, LV wiring is produced via an<br />

LV plug.<br />

b The LV plug includes:<br />

v the fixed part (male) fitted on the <strong>circuit</strong>-<strong>breaker</strong> and fully wired to the terminal<br />

block of the operating mechanism,<br />

v the mobile part (female) compatible with the male part.<br />

Two versions of LV plug are available<br />

b A 21-pin LV plug, allowing to connection of<br />

v a shunt opening release YO1,<br />

v a remote control mechanism (electrical motor, shunt closing release YF,<br />

antipumping relay),<br />

v the Pilot monitoring device,<br />

v maximum number of auxiliary contacts: 3 NC - 3 NO - 1 CHG<br />

(see details in chapter "Open/closed auxiliary contacts").<br />

b A 42-pin LV plug, allowing to connect<br />

v an opening release (shunt opening release or under-voltage release),<br />

v a second opening release (shunt opening release YO2, under-voltage release YN<br />

or low energy release MITOP),<br />

v a remote control mechanism (electrical motor, shunt closing release,<br />

antipumping relay)<br />

v the Pilot monitoring device,<br />

v maximum number of auxiliary contacts: 5 NC - 6 NO - 1 CHG<br />

(see details in chapter "Open/closed auxiliary contacts").<br />

b Interlocking function<br />

In order to comply with IEC standard 62271-200, an interlocking feature prevents:<br />

v racking in when the LV plug is not connected.<br />

v disconnection of the LV plug when the <strong>circuit</strong>-<strong>breaker</strong> is in racking in position.<br />

LV wiring kit<br />

b A kit including 21 wires (2 meters long) fitted with pin suitable for the plug can be<br />

supplied for connection to the LV compartment of the cubicle.<br />

This arrangement provides an auxiliary supply connection with a high level of<br />

electrical safety.<br />

30


Function description<br />

opening <strong>circuit</strong><br />

DE60161<br />

Composition<br />

b The opening <strong>circuit</strong> can be achieved by the followings units:<br />

v shunt opening release (YO1),<br />

v second shunt opening release (YO2),<br />

v under voltage release (YN),<br />

v low energy release (MITOP).<br />

(2)<br />

(1) or (3)<br />

Please check in the combination table the right associations of different releases.<br />

Note: this table is present in order form at the end of this catalogue.<br />

Shunt opening release (YO1 et YO2)<br />

b This causes the instant opening of the <strong>circuit</strong>-<strong>breaker</strong> when energised.<br />

Operating mechanism<br />

Characteristics<br />

Supply<br />

see order form<br />

Threshold VAC 0.7 to 1.1 Un<br />

VDC<br />

0.85 to 1.1 Un<br />

Consumption VAC 160 VA<br />

VDC<br />

50 W<br />

DE60094<br />

(1) Shunt opening release<br />

Under voltage release (YN)<br />

b An under voltage release operates to open the <strong>circuit</strong>-<strong>breaker</strong> when the voltage at<br />

the terminals of the release falls below 35% of its rated voltage, even if the fall is slow<br />

and gradual.<br />

On the other hand, it does not operate the <strong>circuit</strong>-<strong>breaker</strong> when the voltage at its<br />

terminals exceeds 70% of its rated supply voltage.<br />

Circuit-<strong>breaker</strong> closing is possible when the values of the voltage at the terminals of<br />

the release are greater than or equal to 85% of its rated voltage.<br />

Closing is impossible when the voltage at the terminals is lower than 35% of its<br />

rated supply voltage.<br />

DE60089<br />

(2) Under voltage release<br />

Characteristics<br />

Supply<br />

see order form<br />

Threshold opening 0.35 to 0.7 Un<br />

closing 0.85 Un<br />

Consumption pick-up VAC 400 VA<br />

VDC<br />

100 W<br />

hold VAC 100 VA<br />

VDC<br />

10 W<br />

DE60091<br />

Low energy release (MITOP)<br />

b This specific release comprises a low energy consumption unit and is used<br />

specifically with self-powered relay SEPAM 100LA ("REFLEX MODULE"), or VIP<br />

relay.<br />

(3) Low energy release<br />

Characteristics<br />

Supply<br />

Threshold<br />

direct current<br />

0.6 A < I < 3 A<br />

Any tripping caused by the Mitop release is indicated momentarily by an SDE type<br />

changeover contact.<br />

31


Evolis <strong>24</strong> kV frontal<br />

withdrawable<br />

Function description<br />

remote control<br />

Function<br />

DE60160<br />

(6)<br />

(5)<br />

b The remote control enables remote opening and closing of the <strong>circuit</strong>-<strong>breaker</strong>.<br />

(8)<br />

Composition<br />

b The remote control comprises:<br />

v electrical motor and gear reducer,<br />

v a shunt closing release (YF),<br />

v an antipumping relay,<br />

v an operation counter.<br />

(7)<br />

(9)<br />

(4)<br />

DE60093<br />

Operating mechanism<br />

(4) <strong>Electric</strong> motor and gear reducer<br />

<strong>Electric</strong> motor and gear reducer<br />

b The electrical motor arms and rearms the energy storage springs as soon as the<br />

<strong>circuit</strong>-<strong>breaker</strong> is closed. This enables instant reclosing of the device after opening.<br />

The arming lever is only used as back up control in the absence of an auxiliary<br />

voltage.<br />

M3 contact indicates end of charging.<br />

Characteristics<br />

Supply V AC 50/60 see order form<br />

V DC<br />

see order form<br />

Consumption V AC 380 VA<br />

V DC 380 W<br />

DE60151<br />

(5) Shunt closing release<br />

Shunt closing release (YF)<br />

b This causes the remote closing of the <strong>circuit</strong>-<strong>breaker</strong> when the operating<br />

mechanism is armed.<br />

Characteristics<br />

YF<br />

Supply VAC 50/60 Hz see order form<br />

VDC<br />

see order form<br />

Threshold<br />

0.85 to 1.1 Un<br />

Consumption VAC 160 VA<br />

VDC<br />

50 W<br />

DE60095<br />

Antipumping relay<br />

b The antipumping relay avoids unwanted closing and tripping within a short interval.<br />

This function gives absolute priority to the opening order and blocks closing.<br />

This prevents the device from being locked in an indefinite opening-closing cycle.<br />

(6) Antipumping relay<br />

32


Function description<br />

indication and locking / interlocking<br />

DE60087<br />

Operation counter<br />

b The operation counter is visible from the front face.<br />

It displays the number of operating cycles that the device has performed.<br />

(7) Operation counter<br />

DE60152<br />

Open/closed auxiliary contacts<br />

b The number of available contacts depends on the fitted options on the operating<br />

mechanism.<br />

(8) Auxiliary contacts<br />

b In its basic configuration, the operating mechanism of the <strong>circuit</strong>-<strong>breaker</strong><br />

comprises a total of:<br />

v 5 normally closed contacts (NC),<br />

v 6 normally open contacts (NO),<br />

v 1 changeover contact (CHG).<br />

b Use of auxiliary contacts is given in the following table:<br />

Option NC contact NO contact<br />

Remote control 1 1<br />

Shunt opening release (each) 0 1<br />

Undervoltage release 0 0<br />

Low energy release MITOP 0 0<br />

Trip <strong>circuit</strong> supervision 1 0<br />

To find out the final number of contacts available, the above quantity<br />

must be deducted from the total quantity (5 NC + 6 NO + 1 CHG) included in the<br />

<strong>circuit</strong>-<strong>breaker</strong>.<br />

(Example: a <strong>circuit</strong>-<strong>breaker</strong> equipped with a remote control and a shunt opening release<br />

has 4 NC + 4 NO + 1 CHG available contacts. With an under-voltage release instead of<br />

a shunt release, this <strong>circuit</strong>-<strong>breaker</strong> has 4 NC + 5 NO + 1CHG available contacts).<br />

b When the 21-pin LV plug is used, the maximum number of available contacts is:<br />

v 3 NC,<br />

v 3 NO,<br />

v 1 changeover.<br />

(Instead of 5NC-6NO-1CHG with the 42-pin LV plug).<br />

Contact characteristics<br />

Rated current<br />

10 A<br />

Breaking capacity AC 220 V (cos ϕ ≥ 0.3) 1 A<br />

DC 110/220 V (L/R ≤ 0.02 s) 0.3 A<br />

DE601<strong>24</strong><br />

Locking of the <strong>circuit</strong>-<strong>breaker</strong><br />

in the open position<br />

b This key lock allows the locking of the <strong>circuit</strong>-<strong>breaker</strong> in the "open" position by<br />

the means of a key.<br />

b The <strong>circuit</strong>-<strong>breaker</strong> is locked in the "open" position by blocking the opening<br />

pushbutton in the "pushed-in position".<br />

b The key lock is of Profalux or Ronis captive key type.<br />

(9) Locking kit<br />

33


Evolis <strong>24</strong> kV frontal<br />

withdrawable<br />

Function description<br />

auxiliary wiring diagram<br />

Auxiliary wiring diagram (principle)<br />

DE60123<br />

CLOSE CB<br />

OPEN CB<br />

M<br />

YF +<br />

anti-pumping<br />

PILOT<br />

YO1<br />

or<br />

YO2<br />

YM<br />

MITOP<br />

motor<br />

shunt closing<br />

+ anti-pumping<br />

system<br />

monitoring<br />

device pilot<br />

shunt<br />

opening<br />

release<br />

undervoltage<br />

release<br />

low energy<br />

release<br />

(MITOP)<br />

changeover<br />

contact<br />

NO<br />

contacts<br />

NC<br />

contacts<br />

remote control<br />

34


Dimensions<br />

230 mm phase distance<br />

DE60063<br />

230 230 163<br />

DE60065<br />

1188<br />

400<br />

473.5<br />

786<br />

288<br />

1309<br />

1400<br />

250 mm phase distance<br />

DE60064<br />

250 250 193<br />

DE60065<br />

1188<br />

400<br />

473.5<br />

886<br />

288<br />

1309<br />

1400<br />

35


Evolis <strong>24</strong> kV frontal<br />

withdrawable<br />

Offer structure<br />

DE60165<br />

DE60132<br />

Basic frontal withdrawable <strong>circuit</strong>-<strong>breaker</strong><br />

The basic frontal withdrawable <strong>circuit</strong>-<strong>breaker</strong> includes:<br />

b 6 power connections including arms and clusters<br />

b a racking truck<br />

b a manual operating mechanism (spring type)<br />

b closing and opening pushbuttons<br />

b a mechanical "open/closed" position indicator<br />

b a mechanical "charged/discharged" closing spring indicator<br />

b a shunt opening release<br />

b an "end of charging" contact<br />

b a block of auxiliary contacts<br />

b a 21-pin LV plug<br />

b an interlocking kit between the LV plug and the <strong>circuit</strong>-<strong>breaker</strong> position<br />

b antidrop function.<br />

Phase distance (mm) 230 250<br />

<strong>24</strong> kV<br />

16 kA 630 A -<br />

1250 A -<br />

2000 A -<br />

2500 A -<br />

25 kA 630 A -<br />

1250 A -<br />

2000 A -<br />

2500 A -<br />

31.5 kA 630 A -<br />

1250 A -<br />

2000 A -<br />

2500 A -<br />

Extra value for:<br />

undervoltage release (fig. 1) (instead of shunt opening release)<br />

DE60153<br />

LV plug 42-pin (fig. 2) (instead of 21 pin)<br />

Fig. 1<br />

DE60135<br />

Circuit-<strong>breaker</strong> fitted options<br />

Monitoring device<br />

Pilot module<br />

diagnosis by <strong>Schneider</strong> <strong>Electric</strong> expert<br />

DE60101<br />

Remote control<br />

remote control<br />

(electrical motor, gear reducer, shunt closing release, antipumping relay, operation counter)<br />

DE60102<br />

Second opening release<br />

DE60132<br />

DE60081<br />

shunt opening release (YO2) (fig. 1)<br />

undervoltage release (YN) (fig. 2)<br />

low energy release (MITOP) (fig. 3)<br />

Fig. 1 Fig. 2 Fig. 3<br />

DE60136<br />

Locking / interlocking<br />

open position <strong>circuit</strong>-<strong>breaker</strong> locking without lock<br />

Ronis or Profalux lock<br />

DE60092<br />

Indication<br />

operation counter<br />

36


DE60142<br />

Circuit-<strong>breaker</strong> fitted options (cond’t)<br />

Safety device<br />

operating mechanism auto discharge *<br />

230 mm phase distance <strong>circuit</strong>-<strong>breaker</strong><br />

250 mm phase distance <strong>circuit</strong>-<strong>breaker</strong><br />

* available end of 2004<br />

200295<br />

Rack-in / rack-out operation<br />

operating crank<br />

DE60084<br />

Cradle<br />

Phase distance<br />

phase distance<br />

230 mm<br />

250 mm<br />

DE55137<br />

Cradle accessories<br />

MT66049<br />

racked in/out position contacts (fig. 1)<br />

earthing sliding device (fig. 2)<br />

DE60107<br />

Fig. 1 Fig. 2<br />

DE60108<br />

LPCT tore sensor for 230 mm phase distance cradle (TLP 160)<br />

LPCT tore sensor for 250 mm phase distance cradle (TLP 190)<br />

TLP 160 TLP 190<br />

37


Evolis <strong>24</strong> kV frontal<br />

withdrawable<br />

38


Order form<br />

Only one box (ticked or filled in by<br />

the needed value) have to be considered between<br />

each horizontal line.<br />

A blue box corresponds to a non priced function.<br />

Basic frontal withdrawable <strong>circuit</strong>-<strong>breaker</strong><br />

Quantity<br />

Rated voltage Ur<br />

<strong>24</strong> kV<br />

Rated short-<strong>circuit</strong> breaking current Isc<br />

kA<br />

Rated normal current Ir<br />

A<br />

Indicators<br />

IEC standard labels and push button colours red-green red-black<br />

ANSI standard red-black red-green<br />

1st opening release (see possible choice in combination table below, 21-pin or 42-pin)<br />

shunt opening <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />

release (YO1) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />

220 Vdc<br />

undervoltage <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />

release (YN) 48 Vdc 125 Vdc 220-230 Vac (50 Hz)<br />

220 Vdc<br />

Circuit-<strong>breaker</strong> fitted options<br />

LV connection<br />

42 pin LV plug (instead of 21)<br />

Pilot monitoring device<br />

Pilot with connecting kit with LV plug without LV plug<br />

diagnosis by <strong>Schneider</strong> <strong>Electric</strong> expert (separate order)<br />

Remote control<br />

<strong>Electric</strong>al motor <strong>24</strong>… 32 Vdc 110… 127 Vdc/ac<br />

48… 60 Vdc/ac 220… 250 Vdc/ac<br />

Shunt closing release<br />

(YF) <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />

48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />

220 Vdc<br />

2nd opening release (see possible choice in combination table below)<br />

shunt opening <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />

release (YO2) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />

220 Vdc<br />

undervoltage <strong>24</strong> Vdc 110 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)<br />

release (YN) 48 Vdc 125-127 Vdc 220-230 Vac (50 Hz)<br />

220 Vdc<br />

low energy release (MITOP)<br />

Locking / interlocking<br />

open position CB locking<br />

Ronis<br />

Profalux<br />

Indication<br />

operation counter (already included if remote control supplied)<br />

Safety device function<br />

auto discharge (available end of 2004)<br />

Earthing<br />

earth sliding device<br />

Operation<br />

operating crank<br />

Cradle<br />

Quantity<br />

Rated current up to 1250 A above<br />

and 25 kA<br />

Cradle accessories<br />

Rack in/rack out position contact<br />

LPCT-TLP up to 1250 A above<br />

and 25 kA<br />

Combination table<br />

No LV plug or<br />

21-pin<br />

42-pin LV plug<br />

LV plug<br />

Shunt opening release YO1 1 1 1 1 1<br />

Shunt opening release YO2 1<br />

undervoltage YN 1 1 1<br />

Mitop 1 1<br />

39


Evolis <strong>24</strong> kV frontal<br />

withdrawable<br />

Separate components<br />

The following components can be<br />

ordered separately and can<br />

be adapted or replaced<br />

by the customer<br />

<strong>MV</strong> and LV connection accessories<br />

<strong>MV</strong> connection accessories<br />

200190<br />

200188<br />

clusers set (including fingers) 630-1250 A AAA10 025<br />

2500 A AAA10 026<br />

arms set 630-1250 A AAA10 022<br />

2500 A AAA10 023<br />

DE60153<br />

LV connection<br />

21 pin LV plug 630-1250 A AAA10 031<br />

42 pin LV plug 2500 A AAA10 032<br />

MT66055<br />

200354<br />

Other <strong>circuit</strong>-<strong>breaker</strong> accessories<br />

200295<br />

Accessories fitted on the cradle<br />

DE60145<br />

DE55137<br />

Fig. 1 Fig. 2 Fig. 3<br />

bus section truck 1250 A / 230 mm AAA10 061<br />

2500 A / 250 mm AAA10 062<br />

busbar earthing truck 230 mm AAA10 063<br />

250 mm AAA10 064<br />

<strong>circuit</strong>-<strong>breaker</strong> insertion slope AAA10 089<br />

operating crank for racking in/out 59449<br />

1 bushing kit for cradle (fig.1) 630 - 1250 A AAA10 016<br />

2500 A AAA10 018<br />

6 field deflectors for cradle bushings 630-1250 A AAA10 020<br />

(fig.2) 2500 A AAA10 021<br />

4 racked in/out position contacts (fig.3) 59173<br />

(to be installed in the cradle)<br />

DE60107<br />

DE60108<br />

LPCT toroidal sensor TLP 160 (up to 1250 A) AAA10 094<br />

TLP 190 (above) AAA10 095<br />

TLP 160 TLP 190<br />

DE60141<br />

Cradle without bushings<br />

phase distance 230 mm AAA10 015<br />

250 mm AAA10 017<br />

40


The following components can be<br />

ordered separately and can<br />

be adapted or replaced<br />

by the customer<br />

DE60102<br />

DE60154<br />

DE60132<br />

DE60133<br />

DE60101<br />

Accessories incorporated in the operating mechanism<br />

Shunt opening release<br />

Shunt closing release<br />

Undervoltage release<br />

<strong>Electric</strong>al motor<br />

Other accessories of the operating mechanism<br />

<strong>24</strong> Vdc AAA10 115<br />

48 Vdc AAA10 116<br />

110 Vdc AAA10 117<br />

125-127 Vdc AAA10 118<br />

220 Vdc AAA10 119<br />

110 Vac 50 Hz AAA10 120<br />

220-230 Vac 50 Hz AAA10 121<br />

120 Vac 60 Hz AAA10 122<br />

<strong>24</strong> Vdc AAA10 106<br />

48 Vdc AAA10 107<br />

110 Vdc AAA10 108<br />

125-127 Vdc AAA10 109<br />

220 Vdc AAA10 110<br />

110 Vac 50 Hz AAA10 111<br />

220-230 Vac 50 Hz AAA10 112<br />

120 Vac 60 Hz AAA10 113<br />

<strong>24</strong> Vdc AAA10 1<strong>24</strong><br />

48 Vdc AAA10 125<br />

110 Vdc AAA10 126<br />

125-127 Vdc AAA10 127<br />

220 Vdc AAA10 128<br />

110 Vac 50 Hz AAA10 129<br />

220-230 Vac 50 Hz AAA10 130<br />

120 Vac 60 Hz AAA10 131<br />

<strong>24</strong>… 32 Vdc AAA10 027<br />

48… 60 Vac/dc AAA10 028<br />

100… 127 Vac/dc AAA10 029<br />

220… 250 Vac/dc AAA10 030<br />

gear reducer AAA10 065<br />

open position <strong>circuit</strong>-<strong>breaker</strong> locking AAA10 092<br />

41


Evolis <strong>24</strong> kV frontal<br />

withdrawable<br />

Services<br />

The following components can only be adapted or replaced on<br />

site by personnel trained by <strong>Schneider</strong> <strong>Electric</strong>:<br />

b Pilot monitoring device,<br />

b remote control (incl.: motor, gear reducer, shunt closing release, antipumping<br />

relay, operation counter),<br />

b operation counter,<br />

b low energy release (MITOP),<br />

b interlocking kit between <strong>circuit</strong>-<strong>breaker</strong> position and LV plug,<br />

b racking device,<br />

b operating mechanism auto-discharge,<br />

b frontal <strong>circuit</strong>-<strong>breaker</strong> front cover.<br />

42


Evolis Pilot monitoring<br />

device<br />

Contents<br />

Function description p.44<br />

PE60053<br />

Two specific features p.44<br />

Pilot main characteristics p.44<br />

Detailed features p.44<br />

Local or remote data collection p.45<br />

Easy to install module p.45<br />

Added at any time p.45<br />

Operation and service p.45<br />

Pilot<br />

43


Evolis Pilot monitoring<br />

device<br />

Function description<br />

DE60053<br />

Fitted on the <strong>circuit</strong>-<strong>breaker</strong>,<br />

the Pilot monitors its operating<br />

conditions.<br />

The Pilot <strong>circuit</strong>-<strong>breaker</strong> monitoring device<br />

has two specific features<br />

Monitoring operating conditions<br />

The device monitors external conditions and provides alarms if they are out of the<br />

specified range.<br />

Recording <strong>circuit</strong>-<strong>breaker</strong> operating data<br />

Similarly to an aircraft black box the monitor device logs the <strong>circuit</strong>-<strong>breaker</strong>’s key data<br />

over time, allowing a diagnosis on its mechanical conditions.<br />

Pilot main characteristics<br />

DE60058<br />

YL<br />

YM<br />

Energy<br />

supply<br />

Characteristics<br />

Supply V AC 50/60 Hz 100/250 -15% to +10%<br />

V DC <strong>24</strong>/250 -30% to +10%<br />

Service temperature °C -25°C to +70°C<br />

Consumption VA or W > 3<br />

Measurement inputs V AC 50/60 Hz 100/250 -15% to +10%<br />

V DC <strong>24</strong>/250 -30% to +10%<br />

Events recording capacity 1000<br />

Conditions record capability 1000<br />

Maintenance notes record capacity<br />

256 (x 256 characters)<br />

M<br />

Communication<br />

Detailed features<br />

DE60055<br />

Aux. voltage<br />

45°C 50°C<br />

θ °C<br />

40°C 55°C<br />

N > 20000<br />

Operating<br />

I > 360j<br />

Pilot<br />

ON OK<br />

Reset alarm<br />

Monitoring operating conditions<br />

b The module continuously monitors<br />

v opening auxiliary voltage,<br />

v <strong>circuit</strong>-<strong>breaker</strong> ambient temperature,<br />

v number of operations,<br />

v time between operations,<br />

v and sends alarms if the set points are exceeded.<br />

b Alarms are visible on the front of the device and can also be transferred to<br />

the LV compartment, or supervision system.<br />

b Operating conditions are recorded: minimum and maximum values of auxiliary<br />

voltage and ambient temperature are time-tagged and stored every <strong>24</strong>h.<br />

Recording <strong>circuit</strong>-<strong>breaker</strong> data<br />

b All <strong>circuit</strong>-<strong>breaker</strong> events are time-tagged and stored (opening, closing, motor<br />

charging, energizing, voltage set point, temperature set point, number of operations,<br />

time between operations).<br />

b A <strong>circuit</strong>-<strong>breaker</strong> expert can analyse the stored data in order to check the correct<br />

mechanical functioning of the <strong>circuit</strong>-<strong>breaker</strong>, 1000 events are stored in the<br />

module.<br />

Servicing note-pad<br />

b The device incorporates this useful feature to record any information related to<br />

servicing the <strong>circuit</strong>-<strong>breaker</strong> (250x250 - character note-pad).<br />

44


Local or remote data collection<br />

PE60037<br />

DE60056<br />

RS485<br />

Ethernet network<br />

Web server<br />

Local use<br />

Alarms are displayed on the device itself.<br />

A dry contact relay collates the faults and can be wired to the low voltage<br />

compartment.<br />

A laptop user-machine Interface can be used to set parameters and to display<br />

and upload data.<br />

Aux. voltage<br />

45°C 50°C<br />

θ °C<br />

40°C 55°C<br />

N > 20000<br />

Operating<br />

I > 360j<br />

Pilot<br />

ON OK<br />

Reset alarm<br />

Remote use<br />

The monitoring device can be connected to a supervisor or concentrator<br />

for connection to the Web via a local RS485 Modbus network.<br />

The supervisor can display, process and acknowledge alarms.<br />

Data is then either processed in the supervision system or in the remote<br />

web-enabled system.<br />

Easy to install module<br />

DE60057<br />

b The module is inserted in the special housing reserved for it on the front of the<br />

<strong>circuit</strong>-<strong>breaker</strong>.<br />

This module may be added at any time<br />

during the <strong>circuit</strong>-<strong>breaker</strong>'s service life<br />

b The module may be factory-mounted within the <strong>circuit</strong>-<strong>breaker</strong>: connection and<br />

parameter setting, are done by <strong>Schneider</strong> <strong>Electric</strong>.<br />

b The module may be added after <strong>circuit</strong>-<strong>breaker</strong> commissioning: connection,<br />

parameter setting and testing, are done by a specialized service provider (<strong>Schneider</strong><br />

<strong>Electric</strong> or other).<br />

The customer is provided with the product manual and the CDrom containing the<br />

computerized manual and UMI PC software.<br />

Operation and service<br />

The "Pilot" monitoring device can be used on two levels:<br />

b Information on operating conditions.<br />

b Diagnosis of mechanical <strong>circuit</strong>-<strong>breaker</strong> conditions: performed by a <strong>circuit</strong>-<strong>breaker</strong><br />

expert (from <strong>Schneider</strong> <strong>Electric</strong>), by analyzing the recorded data.<br />

45


Note<br />

46


Note<br />

47


Note<br />

48


<strong>Schneider</strong> <strong>Electric</strong> Industries SAS<br />

Postal address<br />

<strong>MV</strong> department<br />

F-38050 Grenoble cedex 9<br />

Tel: +33 (0)4 76 57 60 60<br />

http://www.schneider-electric.com<br />

RSC Nanterre B 954 503 439<br />

As standards, specifications and designs change from time to time, please ask for confirmation of<br />

the information given in this publication.<br />

Publishing: <strong>Schneider</strong> <strong>Electric</strong> SA<br />

Technical writing: P. Andréani<br />

Design, production: HeadLines<br />

Printing: Imprimerie du Pont de Claix<br />

AMTED302014EN © 2004 <strong>Schneider</strong> <strong>Electric</strong> - All rights reserved<br />