19.06.2015 Views

WIND ENERGY SYSTEMS - Cd3wd

WIND ENERGY SYSTEMS - Cd3wd

WIND ENERGY SYSTEMS - Cd3wd

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Chapter 9—Wind Power Plants 9–30<br />

be prevented for long term operation. However, reverse power may be acceptable or even<br />

necessary during some operating conditions, so considerable sophistication may be required.<br />

If the turbines need to be started by utility power, as in the case of Darrieus turbines, then<br />

reverse power will flow during the starting cycle. Also, depending on the length and energy<br />

requirements of the turbine shut-down and start-up cycles, it may be justified to allow reverse<br />

power flow during wind lulls if the average power flow over a 10 or 30 minute period is toward<br />

the utility.<br />

Another relay which would be required for the main circuit breaker at least would be one<br />

that detects reverse phase or the loss of one phase of the three-phase system. Actual reversed<br />

phase sequence would be unlikely after the windfarm electrical system is once correctly wired,<br />

but the loss of one phase is not uncommon, caused either by a broken line or the failure of a<br />

circuit breaker to reclose properly. Induction generators would try to support the voltage on<br />

the lost phase, with possible heavy fault currents.<br />

A synchronism check relay prevents a circuit breaker from closing if the windfarm generators<br />

are out of phase with the utility. It would not be required during normal startup<br />

conditions with induction generators since these would not have a voltage present at the time<br />

of connection to the utility. However, if the utility should have a circuit breaker opened elsewhere<br />

on the system, perhaps due to lightning, which recloses after a few tenths of a second,<br />

the induction generator voltages will not have had time to decay to zero, and will most probably<br />

be out of phase. The resulting high currents and torques could easily damage both the<br />

generators and the turbines. The safest approach would be to do a complete shutdown of the<br />

windfarm when utility power is lost for any reason, and then initiate a standard startup. With<br />

more experience, and fast acting solid state controls, it may be possible to add capacitance<br />

and local resistive load at the windfarm to maintain voltage, frequency, and phase so that<br />

automatic reclosing of the windfarm into the utility would be feasible.<br />

Other relays may be considered for specific protection of devices. A differential relay may<br />

be used on the main transformer to detect differences between input and output, which would<br />

indicate an internal fault. It could also be used on the generators, but may be difficult to<br />

justify economically in the windfarm setting. A ground overcurrent relay may be used to<br />

detect large currents flowing in the ground connection of a wye connected transformer, which<br />

would indicate certain types of system failure. Other relays could be used as well.<br />

9 <strong>WIND</strong>FARM COSTS<br />

We have considered the costs of the electrical equipment necessary to connect wind turbines<br />

to the utility grid, hopefully in enough detail to illustrate the process. Prices of electrical<br />

equipment can change substantially over short periods of time, and labor costs vary with the<br />

part of the country, the remoteness of the site, and the site terrain, so the actual figures used<br />

for examples will not be accurate in most situations. One should always call suppliers and<br />

contractors to get current prices.<br />

Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!