19.06.2015 Views

WIND ENERGY SYSTEMS - Cd3wd

WIND ENERGY SYSTEMS - Cd3wd

WIND ENERGY SYSTEMS - Cd3wd

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Chapter 9—Wind Power Plants 9–25<br />

size of around 350 kcmil. Beyond that point, the wire cost increases more rapidly while the<br />

energy saved becomes smaller, so the cost per kWh begins a slow increase.<br />

The low voltage wire loss can be determined from Fig. 5, which shows a single turbine<br />

connected to a transformer T 1 by underground conductors in a trench of length D T .Allthe<br />

low voltage wire in a windfarm carries approximately the same current, so the total loss can<br />

be found by using the total low voltage trench length. There are two possibilities, either single<br />

circuit or double circuit, shown as Fig. 5b and Fig. 5c. Each of the three conductors in the<br />

single circuit case will carry the full turbine current I. The additional ampacity of the double<br />

circuit case is obtained by simply paralleling two conductors for each phase. There are now<br />

six conductors in the trench, each carrying a current I/2.<br />

The power dissipation in the single circuit case is<br />

while the power dissipation in the double circuit case is<br />

P s =3I 2 R s (10)<br />

P d =6(I/2) 2 R d =1.5I 2 R d (11)<br />

where R s and R d are the resistances of a conductor of length D T . Itistemptingtoassume<br />

that P d is smaller than P s because the multiplying factor is half as large (1.5 rather than 3).<br />

But it should be remembered that R d is larger because smaller wire is used in the double<br />

circuit case. In fact, the losses will be exactly the same if the conductor size in the double<br />

circuit case is half the size of the single circuit conductor. It does not make any difference<br />

in losses if the total conductor area of 500 kcmil, for example, is obtained from a single 500<br />

kcmil conductor or from two conductors, each of 250 kcmil area.<br />

Example<br />

A wind turbine rated at 220 A is located 300 ft from its circuit breaker CB1 and transformer T1.<br />

Assume that the trench for a single circuit costs $1/ft and $2/ft for a double circuit. Wire costs for<br />

600 V conductors are given in Table 9.5. What is the cost/ft for the single and double circuit cases<br />

and what is the power loss at rated current for each case?<br />

As mentioned above, the wire must have a rating of 1.15(220) = 253 A. We see in Table 9.2 that<br />

3/0 aluminum has a rating of 272 A in the single circuit case. Each of the individual conductors in<br />

the double circuit case must have a rating of 253/2 = 126.5 A. This is met by 2 AWG, rated at 151 A.<br />

The cost per ft for the single circuit case is<br />

Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!