19.06.2015 Views

WIND ENERGY SYSTEMS - Cd3wd

WIND ENERGY SYSTEMS - Cd3wd

WIND ENERGY SYSTEMS - Cd3wd

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Chapter 9—Wind Power Plants 9–16<br />

= 29,400 kVA. A windfarm with a rating larger than this would need to have two loops, each<br />

loop having two circuit breakers CB2 connected to the low voltage bus on transformer T 2 .It<br />

might be cheaper and more efficient to design for two loops for power levels well under this<br />

level. Two single circuit loops of approximately the same length as one double circuit loop<br />

would certainly be cheaper. The question would be whether the savings in cable would offset<br />

the cost of two additional circuit breakers.<br />

Costs for underground conductors in dollars per 1000 ft are given in Table 9.5. The table<br />

includes both the 600 V and the 15,000 V rating. The former would be used between the<br />

turbine and the transformer T 1 and the latter after T 1 . The thicker insulation of the 15<br />

kV conductor obviously makes it substantially more expensive. There will be three of these<br />

conductors in a three-phase circuit (six for the double circuit case), so these prices must be<br />

multiplied by three (or six) to get the circuit cost per foot. The price of the 15 kV wire<br />

includes a neutral wrapped around the insulation of each conductor, so no additional neutral<br />

wire needs to be purchased.<br />

In addition to the cost of conductors, we have the cost of trenching. This will cost about<br />

one dollar per foot for the single circuit case in good trenching situations and more where<br />

there are rocks or other problems. The cost of trenching will approximately double for the<br />

double circuit case.<br />

Table 9.5. Underground aluminum conductor<br />

cost in dollars per 1000 ft of conductor<br />

Size 600 V 15 kV<br />

6 $107<br />

4 135<br />

2 178 $690<br />

1 253 780<br />

1/0 287 860<br />

2/0 303 1070<br />

3/0 363 1280<br />

4/0 425 1500<br />

250 585 2060<br />

350 799 2800<br />

500 1100 3850<br />

750 1600 5300<br />

1000 2063 7220<br />

The total trench length required for both the low voltage and distribution voltage circuits<br />

can be best calculated from a sketch of the site layout. For cases where several turbines are to<br />

be connected to one unit transformer it would be wise to check total trench length for more<br />

than one possible configuration. For example, if eight turbines are to be connected to one<br />

transformer, is it better to put all eight in one row, or should the transformer be connected<br />

Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!