19.06.2015 Views

WIND ENERGY SYSTEMS - Cd3wd

WIND ENERGY SYSTEMS - Cd3wd

WIND ENERGY SYSTEMS - Cd3wd

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Chapter 9—Wind Power Plants 9–14<br />

nominal transformer rating. Should we select the next larger size of transformer, or might we<br />

get by with the next smaller size?<br />

Example<br />

Assume that we have five turbines rated at 50 kVA each. Should we select a 300 kVA transformer<br />

or a 225 kVA transformer?<br />

The smaller transformer would be operated at 11 percent over its rated value during the times<br />

when all turbines were operating at full power. We would save $6500 - $6000 = $500 of initial cost,<br />

and 554 - 481 = 73 W of no load losses, amounting to 648 kWh/year. The load losses are higher, of<br />

course. Copper losses are proportional to the square of the current, and the current is proportional to<br />

the load kVA (since voltage is essentially fixed). Therefore the copper losses at 250 kVA would be, for<br />

each transformer,<br />

P loss,225 =<br />

( ) 2 250<br />

(1476) = 1822 W<br />

225<br />

( ) 2 250<br />

P loss,300 = (1872) = 1300 W<br />

300<br />

The transformers must be operated at this power level for over 1200 hours per year before the extra<br />

copper losses exceed the reduced eddy current and hysteresis losses (no load losses) of the smaller<br />

transformer. The larger transformer will always have smaller load losses than the smaller transformer<br />

for the same load, but the total loss will be less for the smaller transformer whenever the load is less<br />

than about 20% of rated. This will be the situation for more than half the time at most wind farms,<br />

so a detailed economic study could easily show the smaller transformer to be the economic choice.<br />

But what about damage to the transformer by operating it in an overloaded condition?<br />

It turns out that these transformers can be operated at 113 percent of rated power for up<br />

to four hours in ambient temperatures of 40 o C (104 o F) without a reduction in normal life.<br />

This would be a no wind condition, but full power operation in a windfarm would always be<br />

accompanied by strong winds with resultant cooling. Also it would be rare indeed for full<br />

power to be maintained for over four hours at temperatures as high as 40 o C. Lower ambient<br />

temperatures would also increase the allowable overload. Therefore, it may be appropriate to<br />

select a transformer with a rating up to about 10 percent smaller than the generator rating,<br />

rather than the next size larger. If this is done, it may be necessary to monitor the transformer<br />

temperature during extended periods of high power operation. If the transformer temperature<br />

should exceed a safe level, one of the turbines can be shut down until the transformer has<br />

cooled down.<br />

5 SELECTION OF SIZES, DISTRIBUTION VOLTAGE EQUIP-<br />

MENT<br />

The next step is to select the wire size on the high voltage side of T 1 . The rated current is<br />

determined from<br />

Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!