Chapter 9—Wind Power Plants 9–10<br />

250,000 circular mils = 250 kcmil.<br />

Table 9.2. Ampacities of three single insulated<br />

conductors, 600 V class.<br />

COPPER ALUMINUM<br />

AWG one two one two<br />

kcmil circuit circuits circuit circuits<br />

8 98 92 77 72<br />

6 126 118 98 92<br />

4 163 152 127 118<br />

2 209 194 163 151<br />

1 236 219 184 171<br />

1/0 270 249 210 194<br />

2/0 306 283 239 220<br />

3/0 348 321 272 250<br />

4/0 394 362 307 283<br />

250 429 394 335 308<br />

350 516 474 403 370<br />

500 626 572 490 448<br />

750 767 700 605 552<br />

1000 887 808 706 642<br />

1250 979 891 787 716<br />

1500 1063 965 862 783<br />

1750 1133 1027 930 843<br />

2000 1195 1082 990 897<br />

Older literature will show the units of thousands of circular mils as MCM rather than<br />

kcmil. The first ”M” in MCM stands for the Roman unit of one thousand, and would be a<br />

translation of the Greek kilo for the same quantity. Changing the name of the unit from MCM<br />

to kcmil is a big improvement because it allows a consistent use of multipliers. Using English<br />

units is bad enough without also using the Roman notation for multipliers!<br />

The AWG numbers get smaller as the cable diameter gets larger, which is always confusing<br />

to the newcomer. There are also four AWG sizes larger than the AWG number 1, which is<br />

also confusing. These are 0, 00, 000, and 0000, (or 1/0, 2/0, 3/0, and 4/0) pronounced one<br />

ought, two ought, three ought, and four ought. See Appendix C for a more detailed discussion<br />

of wire sizes and resistance.<br />

This ampacity table is for insulation rated at 75 o C. Higher temperature insulations can<br />

also be used, as mentioned earlier, but this is a commonly used value, mostly for economic<br />

reasons.<br />

The headings of the columns refer to “one circuit” and “ two circuits”. The one circuit<br />

case for a three-phase system requires three conductors, plus a neutral conductor of the same<br />