Chapter 9—Wind Power Plants 9–8<br />

should be valid.<br />

Table 9.1. Price list for motor starters<br />

NEMA Rated List<br />

Size Current Price<br />

0 18 906<br />

1 27 936<br />

2 45 1326<br />

3 90 1896<br />

4 135 4314<br />

5 270 9627<br />

6 540 19659<br />

7 810 26403<br />

8 1215 38745<br />

9 1800 51273<br />

The left hand column shows the NEMA (National Electrical Manufacturers Association)<br />

size. The larger sizes indicate larger enclosures with greater rated currents, shown in the next<br />

column. Each NEMA size can be purchased for nominal motor voltages of 200, 230, 460, and<br />

575 V. The corresponding nominal line voltages are 208, 240, 480, and 600 V. A windfarm in<br />

the United States would most likely use 480 V.<br />

There are actually several different types of enclosures. For example, the general purpose<br />

enclosure would be used in indoor, dry locations. The watertight enclosure would be used<br />

in very wet locations, like a dairy barn where a high pressure hose may be used to clean<br />

equipment. The hazardous location starter would be used in grain elevators or refineries<br />

where dust or fumes could be a problem. The values given in this table are for a dust tight<br />

and rain proof enclosure which would be appropriate for a windfarm.<br />

The turbine generator should have a rated operating current listed on its nameplate. If<br />

not, this can be computed from the maximum generator power and the voltage. For a voltage<br />

of 480 V and a power of P tur ,thisis<br />

I trat =<br />

P tur<br />

√<br />

3(480) cos θ<br />

(6)<br />

If the power factor cos θ is not specified, it can be assumed as being about 0.85 without<br />

serious error.<br />

The circuit breaker CB1 would be located at the base of the turbine tower if supplied by<br />

the turbine manufacturer or at T 1 if supplied by the windfarm developer.<br />

Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001