WIND ENERGY SYSTEMS - Cd3wd
WIND ENERGY SYSTEMS - Cd3wd WIND ENERGY SYSTEMS - Cd3wd
Chapter 6—Asynchronous Generators 6–25 tization curve. Approximate curves for L m,pu for the two machines are presented in Fig. 13. We see that the inductance is constant for voltages less than about one-half of rated. The inductance then decreases as saturation increases. Figure 13: Per unit magnetizing inductance as a function of load voltage. We see that any detailed analysis is made difficult because of the variability of the machine parameters. Not only must a nonlinear solution technique be used, the solution must be obtained for the allowable range of machine parameters. This requires a great deal of computation, with the results being somewhat uncertain because of possible inadequacy of the machine model and because of inadequate knowledge of the parameter values. We shall leave such detailed analyses to others and turn now to an example of experimental results. Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001
Chapter 6—Asynchronous Generators 6–26 Figure 14 shows the variation of terminal voltage with input mechanical power for the 40-hp machine mentioned earlier. The rated voltage is 230 V line to line or 132.8 V line to neutral. Actual line to neutral voltages vary from 90 to 150 V for the data presented here. Figure 14: Variation of output voltage with input shaft power for various resistive and capacitive loads for a 40-hp self-excited induction generator. All resistance was disconnected from the machine in order to establish oscillation. Once a voltage close to rated value was present the load was reconnected and data collected. Voltage buildup would not occur for speed and capacitance combinations which produce a final voltage of less than 0.8 or 0.9 of rated. For example, with 285 µF of capacitance line to line, the voltage would not build up for speeds below 1600 r/min. At 1600 r/min the voltage would slowly build up over a period of several seconds to a value near rated. The machine could then be operated at speeds down to 1465 r/min, and voltages down to 0.7 of rated before oscillation would cease. Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001
- Page 225 and 226: Chapter 5—Electrical Network 5-35
- Page 227 and 228: Chapter 5—Electrical Network 5-37
- Page 229 and 230: Chapter 5—Electrical Network 5-39
- Page 231 and 232: Chapter 5—Electrical Network 5-41
- Page 233 and 234: Chapter 5—Electrical Network 5-43
- Page 235 and 236: Chapter 5—Electrical Network 5-45
- Page 237 and 238: Chapter 5—Electrical Network 5-47
- Page 239 and 240: Chapter 5—Electrical Network 5-49
- Page 241 and 242: Chapter 5—Electrical Network 5-51
- Page 243 and 244: Chapter 5—Electrical Network 5-53
- Page 245 and 246: Chapter 5—Electrical Network 5-55
- Page 247 and 248: Chapter 5—Electrical Network 5-57
- Page 249 and 250: Chapter 5—Electrical Network 5-59
- Page 251 and 252: Chapter 5—Electrical Network 5-61
- Page 253 and 254: Chapter 6—Asynchronous Generators
- Page 255 and 256: Chapter 6—Asynchronous Generators
- Page 257 and 258: Chapter 6—Asynchronous Generators
- Page 259 and 260: Chapter 6—Asynchronous Generators
- Page 261 and 262: Chapter 6—Asynchronous Generators
- Page 263 and 264: Chapter 6—Asynchronous Generators
- Page 265 and 266: Chapter 6—Asynchronous Generators
- Page 267 and 268: Chapter 6—Asynchronous Generators
- Page 269 and 270: Chapter 6—Asynchronous Generators
- Page 271 and 272: Chapter 6—Asynchronous Generators
- Page 273 and 274: Chapter 6—Asynchronous Generators
- Page 275: Chapter 6—Asynchronous Generators
- Page 279 and 280: Chapter 6—Asynchronous Generators
- Page 281 and 282: Chapter 6—Asynchronous Generators
- Page 283 and 284: Chapter 6—Asynchronous Generators
- Page 285 and 286: Chapter 6—Asynchronous Generators
- Page 287 and 288: Chapter 6—Asynchronous Generators
- Page 289 and 290: Chapter 6—Asynchronous Generators
- Page 291 and 292: Chapter 6—Asynchronous Generators
- Page 293 and 294: Chapter 6—Asynchronous Generators
- Page 295 and 296: Chapter 6—Asynchronous Generators
- Page 297 and 298: Chapter 7—Asynchronous Loads 7-2
- Page 299 and 300: Chapter 7—Asynchronous Loads 7-4
- Page 301 and 302: Chapter 7—Asynchronous Loads 7-6
- Page 303 and 304: Chapter 7—Asynchronous Loads 7-8
- Page 305 and 306: Chapter 7—Asynchronous Loads 7-10
- Page 307 and 308: Chapter 7—Asynchronous Loads 7-12
- Page 309 and 310: Chapter 7—Asynchronous Loads 7-14
- Page 311 and 312: Chapter 7—Asynchronous Loads 7-16
- Page 313 and 314: Chapter 7—Asynchronous Loads 7-18
- Page 315 and 316: Chapter 7—Asynchronous Loads 7-20
- Page 317 and 318: Chapter 7—Asynchronous Loads 7-22
- Page 319 and 320: Chapter 7—Asynchronous Loads 7-24
- Page 321 and 322: Chapter 7—Asynchronous Loads 7-26
- Page 323 and 324: Chapter 7—Asynchronous Loads 7-28
- Page 325 and 326: Chapter 7—Asynchronous Loads 7-30
Chapter 6—Asynchronous Generators 6–25<br />
tization curve. Approximate curves for L m,pu for the two machines are presented in Fig. 13.<br />
We see that the inductance is constant for voltages less than about one-half of rated. The<br />
inductance then decreases as saturation increases.<br />
Figure 13: Per unit magnetizing inductance as a function of load voltage.<br />
We see that any detailed analysis is made difficult because of the variability of the machine<br />
parameters. Not only must a nonlinear solution technique be used, the solution must<br />
be obtained for the allowable range of machine parameters. This requires a great deal of<br />
computation, with the results being somewhat uncertain because of possible inadequacy of<br />
the machine model and because of inadequate knowledge of the parameter values. We shall<br />
leave such detailed analyses to others and turn now to an example of experimental results.<br />
Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001