Chapter 6—Asynchronous Generators 6–11<br />

application of rated dc voltage to the generator terminals will usually establish the proper<br />

residual magnetism. This should be applied while the generator is stopped, so current will<br />

be well above rated, and should be applied for only a few seconds at most. Only the field<br />

winding needs to experience this voltage, so if the brushes can be lifted from the commutator,<br />

both the generator and the dc supply will experience much less shock.<br />

3 PERMANENT MAGNET GENERATORS<br />

A permanent magnet generator is like the synchronous or ac generator discussed in the previous<br />

chapter except that the rotor field is produced by permanent magnets rather than current<br />

in a coil of wire. This means that no field supply is needed, which reduces costs. It also<br />

means that there is no I 2 R power loss in the field, which helps to increase the efficiency. One<br />

disadvantage is that the reactive power flow can not be controlled if the PM generator is<br />

connected to the utility network. This is of little concern in an asynchronous mode, of course.<br />

The magnets can be cast in a cylindrical aluminum rotor, which is substantially less expensive<br />

and more rugged than the wound rotor of the conventional generator. No commutator is<br />

required, so the PM generator will also be less expensive than the dc generator of the previous<br />

section. These advantages make the PM generator of significant interest to designers of small<br />

asynchronous wind turbines.<br />

One load which might be used on a PM generator would be a resistance heating system<br />

for either space or hot water. Such a system is shown in Fig. 5. The three line-to-neutral<br />

generated voltages E a , E b ,andE c are all displaced from each other by 120 electrical degrees.<br />

The line-to-neutral terminal voltages are also displaced from each other by 120 o if the threephase<br />

load is balanced (R a = R b = R c ). The current I a is given by<br />

E a<br />

I a =<br />

= V a<br />

A (10)<br />

R s + jX s + R a R a<br />

where X s is the synchronous reactance, R s is the winding resistance, and R a is the resistance<br />

of one leg or one phase of the load resistance.<br />

The neutral current I n is given by the sum of the other currents.<br />

I n = I a + I b + I c A (11)<br />

If the load is balanced, then the neutral current will be zero. In such circumstances, the<br />

wire connecting the neutrals of the generator and load could be removed without affecting<br />

any of the circuit voltages or currents. The asynchronous system will need the neutral wire<br />

connected, however, because it allows the single-phase voltages V a , V b ,andV c to be used for<br />

other loads in an unbalanced system. Several single-phase room heaters could be operated<br />

independently, for example, if the neutral wire is in place.<br />

Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001