Chapter 5—Electrical Network 5–57<br />

TABLE 5.3 Communication and Control<br />

between a Large Wind Turbine Generator<br />

and a Dispatch Center<br />

Under Local Control<br />

(a) Start Capability<br />

(b) Synchronization<br />

(c) Stand-Alone Capability<br />

(d) Protection<br />

Information to Dispatch Center<br />

(a) Operating Mode (on/off)<br />

(b) Power Flow<br />

(c) Voltage Magnitude<br />

(d) Revenue Metering<br />

Control from Dispatch Center<br />

(a) Change Operating Mode<br />

(b) Change Power Level<br />

If there were 75 wind turbines being monitored and controlled by the dispatch center,<br />

and all the dispatch center costs were to be allocated to them, each wind turbine would be<br />

responsible for $10,000 of equipment at the dispatch center and another $10,000 of equipment<br />

at the turbine. This $20,000 would present a major obstacle to the purchase of a 5 kW wind<br />

generator priced at $8000, but not nearly as much of an obstacle to a 2.5 MW wind generator<br />

priced at $2,000,000. In one case the monitoring and control equipment cost 2.5 times as<br />

much as the wind generator itself, and only 1 percent of the wind generator cost in the second<br />

case. This is another economy of scale for wind generators. In addition to turbine cost per<br />

unit area decreasing with size, and power output per unit area increasing with size because of<br />

greater height and therefore better wind speeds, the cost of monitoring and control per unit<br />

area also decreases with turbine size.<br />

The probable result of these economic factors is that small wind generators, less than<br />

perhaps 20 kW maximum power rating, will not be monitored and controlled by a dispatch<br />

center. Each small wind generator will have its own start, stop, and protective systems. The<br />

utility will somehow assure itself that voltage magnitudes are within acceptable limits and<br />

that electrical islands cannot operate on wind power alone and continue to operate the system<br />

in a manner much like the past. This should be satisfactory as long as the total installed wind<br />

generator capacity is significantly less than the minimum load on a feeder line.<br />

On the other hand, large wind turbines will almost certainly be monitored and controlled<br />

by the appropriate dispatch center. This control can result in significant benefits to both the<br />

utility and the wind turbine, with acceptable costs.<br />

Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001